warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall
not be liable for technical or editorial errors or omissions contained herein.
Before you begin ....................................................................................................................................... 6
Fire detection ............................................................................................................................................ 7
Life safety systems ....................................................................................................................... 19
Life safety overview ................................................................................................................................. 19
EPO system ............................................................................................................................................ 19
ECS touchscreen and EPO indicators ............................................................................................... 20
Battery backup during an EPO event ................................................................................................ 21
Fire detection system ................................................................................................................................ 22
VESDA air sampling smoke detection system ..................................................................................... 22
Manual fire pulls ........................................................................................................................... 22
Fire alarm panel ............................................................................................................................ 23
Fire alarm indicators ...................................................................................................................... 23
Power, electrical, and controls ...................................................................................................... 25
Site electrical system ................................................................................................................................ 25
Power safety ........................................................................................................................................... 25
Grounding and bonding ................................................................................................................ 25
Power feeders ......................................................................................................................................... 27
Drop boxes ............................................................................................................................................ 32
Rack power ............................................................................................................................................ 32
Environmental control system ........................................................................................................ 34
Contents 3
Environmental control system overview ....................................................................................................... 34
Using the ECS ......................................................................................................................................... 34
Components of the ECS .................................................................................................................. 35
Satellite control boxes .................................................................................................................... 35
Facility connections to the ECS .................................................................................................................. 35
Connecting to the ECS through the demarcation box .......................................................................... 36
Connecting to the ECS through connection portals ............................................................................. 36
Managing the ECS from the HP POD 240e NA .......................................................................................... 37
Configuring the ECS ...................................................................................................................... 38
Logging in remotely to the ECS ........................................................................................................ 40
Fire box ................................................................................................................................................. 68
Adding a phone ...................................................................................................................................... 68
Standard components .................................................................................................................. 70
Air filter sensor ........................................................................................................................................ 70
General specifications ............................................................................................................................. 72
Power up procedure ................................................................................................................................ 79
Standard power up procedure ........................................................................................................ 79
Cold weather power up procedure .................................................................................................. 80
Power down procedure ............................................................................................................................ 83
Full power down procedure ............................................................................................................ 83
Contacting HP ............................................................................................................................ 84
Before you contact HP .............................................................................................................................. 84
HP contact information ................................................................................................................... 84
Index ......................................................................................................................................... 91
Contents 5
Overview
Before you begin
For more information about site requirements, specifications, power, management requirements, and
supported facility connections, see the HP Performance Optimized Datacenter 240e NA Site Preparation and Requirements Guide.
The location of various components or subsystems in the HP POD 240e NA might vary from this
documentation. For final placement specifications, see the data sheets that are included in the operations
Operator safety
and maintenance manual.
The HP POD 240e NA is not habitable or suitable for human occupancy. The HP POD 240e NA is Listed as
a Product that provides service access areas for periodic maintenance and service. These areas must be
controlled and available for use only by owner-authorized personnel and qualified personnel who are
trained in the maintenance and service of the HP POD 240e NA components.
WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with PPE
requirements when opening or working inside areas of the HP POD 240e NA that are marked as
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
WARNING: To avoid the risk of personal injury, hearing protection must be worn at all times
when working inside the HP POD 240e NA.
WARNING: To avoid the risk of personal injury or damage to the equipment, do not insert
anything inside the electrical busways, except for the approved HP busway drop boxes.
Before completing the installation of the HP POD 240e NA, the customer, or a designated agent, is
responsible for completing any Environmental Health and Safety evaluation of the HP POD 240e NA or any
attached structural component purchased through HP. The customer, or their designated agent, must also
complete an arc flash assessment and breaker coordination study of the HP POD 240e NA and the
associated electrical supply system for operation and maintenance. The individual or organization that
completes the arc flash assessment must also create and provide all required labeling for all electrical panels
on the HP POD 240e NA.
Component safety
CAUTION: If the HP POD 240e NA is shut down for an extended period of time, such as during
routine maintenance, use desiccant units or materials to eliminate condensation within the HP
POD 240e NA. Condensation causes damage to IT equipment and HP POD 240e NA controls.
Overview 6
CAUTION: Electrostatic discharge might damage electronic components. Be sure that you are
properly grounded (earthed) by wearing approved grounding straps before beginning any
installation procedure or repair.
CAUTION: If any racks contain empty RU space, use the HP POD 240e NA filler panels to
maintain the efficiency of the HP POD 240e NA thermal system. Filler panels are available from
HP in 10-pack quantities (part number AQ682A) and 100-pack quantities (part number
AS993A).
Fire detection
The fire detection system is supplied as a component of the HP POD 240e NA, and is Manufacturer Designed
specifically for this HP product, in compliance with national standards.
HP does not certify that the fire detection system that is installed in the HP POD 240e NA meets all local and
jurisdictional requirements. The customer is responsible for the following actions:
• Verifying that the POD fire detection system meets local codes, including specific local requirements for
initial and periodic inspections
• Arranging for and receiving all required local permits, including initial commissioning as well as
standard and repair maintenance
• General maintenance of the fire detection system must be completed by an authorized technician
For more information, see the HP Performance Optimized Datacenter 240e NA Maintenance and
Service guide.
Any additional local requirements are not covered as part of the installation and deployment services of the
fire detection system, unless specifically included in an executed SOW.
Preventative maintenance
You are responsible for creating and performing detailed preventative maintenance based on HP
recommendations. Data sheets or additional operation and maintenance manuals will be provided for this
task.
CAUTION: Failure to implement a comprehensive preventative maintenance schedule may result
in reduced efficiency in the HP POD 240e NA, failure of main or subsidiary systems, and loss of
warranty on third party components.
Environmental considerations
CAUTION: To maintain accurate environmental conditions and minimize condensation inside
the HP POD 240e NA, do not leave the HP POD 240e NA doors open during operation.
Overview 7
Component identification
Structural component identification
The HP POD 240e NA documentation frequently refers to these specific components of the HP POD 240e
NA.
The following figure shows the assembled HP POD 240e NA structural components.
The following figure shows the exploded view of the individual sections of the HP POD 240e NA.
Component identification 8
Item Component Description
1
2
3
4
5
6
Canopy The canopy has two 6.10 m (20 ft) parts that are installed on top of the HP
POD 240e NA.
Adiabatic units and
Each of the four cradles contain three Adiabatic units.
cradles
AHU service area end
The HP POD 240e offers AHU service access in these two locations.
walls
IT section A (primary
structure)
The IT section A (primary structure) contains the ECS. Conditioned air passes
through the IT section A and IT section B structures to force cool air through the
IT equipment.
Hot aisle The hot aisle structure is a separate space where hot exhaust air from the
servers can be expelled out of the structure or recirculated. The HP POD 240e
isolates the IT sections from the hot aisle for efficiency.
IT section B (secondary
structure)
IMPORTANT: You must consult with the AHJ to determine the egress requirements for the hot-aisle
The IT section B (secondary structure) is similar to the IT section A (primary
structure), but IT section B does not contain the ECS.
service area that you must provide. Requirements might include landings and stairs to be installed
at both ends of the hot aisle service area for emergency egress.
Parts and part number identification
Review all of the contents to identify the following for each component:
Regulatory model number
The following figure shows the location of the regulatory model number and the POD solution serial numbers
on the inside of each IT section, adjacent to the bump out.
Interior side view shown
CSC Safety Approval placard
Component identification 9
Each HP POD 240e NA Adiabatic AHU has a CSC Safety Approval placard that includes model number,
serial number, and proof load. Each AHU has a different serial number. The following figure shows the CSC
Safety Approval placard locations.
Side view single AHU cradle shown
Life safety component identification
Internal life safety components
Top view shown
Item Component Description
1
2
3
Emergency switch locations There are six emergency switch boxes, one by each personnel access
door throughout the HP POD 240e NA. Each emergency switch box
includes items (2) and (3).
Fire alarm manual pull Enables manual initiation of the fire system, which includes the
activation of the interior and exterior fire strobe lights.
EPO button Disconnects the HP POD 240e NA from main power feeds and
activates the red EPO indicator light on the outside of the HP POD 240e
NA.
To reset the EPO button, switch the EPO to the Active position. Failure to
do so prevents the HP POD 240e NA from being able to restart.
Exit sign locations
Component identification 10
Top view shown
Internal emergency lighting
Top view shown
Internal emergency status indicators
Component identification 11
Top view shown
•
•
•
There is one fire strobe light in each aisle of the HP POD 240e NA. When illuminated, these lights indicate
a fire alarm condition within the HP POD 240e NA.
External emergency status indicators
Item Component Description
1
External EPO status indicator Indication of operating status:
Fire strobe light Indicates a fire alarm condition within the HP POD 240e NA.
There is one fire strobe light on each side of the HP POD 240e NA.
Component identification 12
requirements when opening or working inside areas of the HP POD 240e NA that are marked as
•
•
•
Electrical power component identification
WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with PPE
End view shown
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with
electrical warning labels when operating and maintaining the electrical panels and systems of the
HP POD 240e NA.
Item Component Description
1
Demarcation box Customer communication connection point:
ECS Access control Phone
2
3
4
5
6
7
8
Fire box Connection location for fire emergency and VESDAnet signals
415/240V 3-phase, wye,
A feed power for IT Section A electrical busways and house power
4-wire
415/240V 3-phase, wye,
B feed power for IT Section A electrical busways and house power
4-wire
Mechanical power feed
A and B feed power for the IT Section A AHU
cabinet
Mechanical power feed
A and B feed power for the IT Section B AHU
cabinet
415/240V 3-phase, wye,
B feed power for IT Section B electrical busways and house power
4-wire
415/240V 3-phase, wye,
A feed power for IT Section B electrical busways and house power
4-wire
Main breaker locations
Component identification 13
End view shown
External safety labels
End view shown
Callout Electrical safety label Description
1
2
3
4
Danger sign Reminds you that the electrical panels must only be
accessed by authorized personnel.
Disconnect label Provides the disconnect order for all of the electrical
panels.
Caution Cautions you about isolating power from the product.
Arc flash warning Reminds you of arc flash danger and required PPE.
The customer must complete an arc flash assessment of the HP POD 240e NA and the associated electrical
supply system for such things as operation and maintenance.
Internal panel labels
Component identification 14
End view shown
•
•
•
•
•
Callout Electrical safety label Description
1
2
3
4
Input power Lists the input power information
Panel schedule/circuit breaker
table
Fuse type table Lists all fuse types and sizes
Wire color code 415/240V wye color codes
Lists the layout and designation for all circuit breakers on the
panel
Purple/Brown Purple/Orange Purple/Yellow Purple/White—Neutral Green and yellow—Equipment ground
Electrical power disconnect map label location
Component identification 15
Control cabinet component identification
•
•
ECS modules and terminal
Used for ECS communication, I/O connections, and terminal block
All circuits in the control cabinet are labeled with the panel name and circuit breaker number.
Each IT section has one control cabinet that houses the various control components for that IT section.
IT section A control cabinet
The ECS and fire panel controls are located in the IT section A control cabinet.
Item Component Description
1
2
VESDA air sampling smoke
detection unit
Fire alarm control panel
An early warning laser scan smoke detection unit
Controls all fire systems within the HP POD 240e NA,
including the smoke detection system and manual fire pulls
Includes a battery backup system to provide backup power to
the fire system in the event of power loss to the HP POD 240e
NA
3
4
5
6
7
8
9
10
11
UPS Provides backup power to the IT section A VESDA in the event of
power loss to the HP POD 240e NA
Access control module Controls and organizes information that is monitored by the HP
POD 240e NA access control components
Customer access control
junction box
ECS relays Relays for the ECS control
blocks
House power fuses and terminal
blocks
Power supply* Provides 24V DC power to the PLC, ECS, and LED lighting
UPS* Provides battery backup power to the PLC and ECS in the event of
240/120V transformer Provides house power to IT section A convenience outlets
Provides a location for the facility access control components and
connects the facility to the HP POD 240e NA
connections
Provide house power to the HP POD 240e NA convenience outlets
and lighting
power loss to the HP POD 240e NA
Component identification 16
Item Component Description
NA
*These components are only installed in the IT section A control cabinet.
PLC* The computer located on the inside door of the control cabinet that
controls the ECS system
IT section B control cabinet
Item Component Description
1
2
3
4
5
6
7
VESDA air sampling smoke
detection unit
Fire system junction box Junction box to connect the IT section B fire system to IT section A
UPS Provides backup power to the IT section B VESDA in the event of
DIN rail with EPO modules Sends a signal to all of the connected EPO devices
DIN rail with terminals and ECS
communication modules
DIN rail with terminals and fuses Sends information from IT section B to the PLC in IT section A
240/120V transformer Provides house power to IT section B for convenience outlets
An early warning laser scan smoke detection unit
power loss to the HP POD 240e NA
For more information, see "EPO system (on page 19)."
Sends information from IT section B to the PLC in IT section A
For more information about the specific control components within the control cabinet, see the Operations
and Maintenance Manual for the HP Performance Optimized Datacenter 240e North America (Adiabatic).
Security component identification
The security system components are located in the hot aisle porch.
Component identification 17
Top view shown
Item Component Description
1
2
3
4
5
Racks
The HP POD 240e NA has 22 IT racks per IT section, for a total of 44 IT racks per HP POD 240e NA.
For more information about racks and network cabling, see the HP POD 240e NA Networking Guide.
Security panel and Mag lock
power supply
Security card access door
termination
Security card access battery
backup
Main security controller board Controls all security components
Cross connect for IT section A
and B doors
CAUTION: If any racks contain empty RU space, use the HP POD 240e NA filler panels to
Provides power for the security panel and the personnel access
door Mag locks
Controls card readers on the personnel access doors
Provides battery backup for the card readers on the personnel
access doors
Provides power and sends signals to the installed access control
components
maintain the efficiency of the HP POD 240e NA thermal system. Filler panels are available from
HP in 10-pack quantities (part number AQ682A) and 100-pack quantities (part number
AS993A).
Component identification 18
Life safety systems
Life safety overview
The HP POD 240e NA has multiple life safety systems that work together to protect the HP POD 240e NA
equipment and personnel. The following life safety systems are included on the HP POD 240e NA:
• EPO system (on page 19)
• Fire detection system (on page 22)
• Emergency egress (on page 24)
• Facility connections to ECS ("Facility connections to the ECS" on page 35)
EPO system
If the HP POD 240e NA must be shut down during an emergency, the EPO system automatically powers off
the HP POD 240e NA, activates the EPO indicator on the ECS panel door, and changes the EPO status light
tree that is located on the POD exterior to red.
To be sure that all rack-mounted UPS devices are shut down during an EPO event, verify that each
rack-mounted UPS device is connected to the HP POD 240e NA EPO system.
The EPO system can be activated two ways:
• Excessive high temperature in the hot aisle—The HP POD 240e NA includes two thermisters. If both
thermisters reach 60°C (140°F), an EPO shutdown is triggered automatically.
Side view
• Manual initiation—To manually trigger an EPO shutdown, press any of the EPO buttons. There are EPO
buttons located next to the personnel access doors in the POD.
For the location of EPO buttons, see "Life safety component identification (on page 10)."
Life safety systems 19
IMPORTANT: The EPO system must be reset before you can power up and restart the HP POD
•
•
•
240e NA.
To reset the EPO system:
1. Determine and correct the reason for EPO system initiation.
2. If the EPO was triggered manually, the EPO button that was pushed must be reset by rotating the button
as indicated.
3. Verify the key control for the EPO mode is in the Armed position.
4. Press and release the white EPO reset button.
ECS touchscreen and EPO indicators
The ECS touchscreen and EPO indicators are located on the IT section A control panel door.
The touchscreen enables easy configuration of environmental parameters and access data, and also
monitors environmental, life safety, and security conditions within the HP POD 240e NA.
The EPO indicators provide the EPO status and enable the EPO system mode to be adjusted.
Indicates the operating status of the HP
POD 240e NA
Red—EPO shutdown mode
Power on White Indicates the EPO power status
2
EPO shutdown Red Indicates an EPO shutdown or alarm
3
EPO armed White Indicates the EPO system is armed and
4
EPO bypass mode Yellow Indicates the EPO is operating in bypass
5
EPO bypassed Green Indicates that the EPO functionality and
6
condition
operational
mode
shutdown is bypassed
Life safety systems 20
Item Component Indicator color Description
•
•
•
EPO mode Key control The key control allows you to select the
7
EPO reset White button Select to reset the EPO system
8
EPO modes
The EPO system has three operating modes:
• Armed—The EPO system is armed and operational.
• Test—The EPO system is in test mode and will not power off the HP POD 240e NA in the events that
would normally trigger an EPO.
• Bypass—The EPO system is non-operational and will not power off the HP POD 240e NA in any events
that normally trigger an EPO.
For more information, see "ECS touchscreen and EPO indicators (on page 20)."
EPO mode:
Armed Test Bypass
The illuminated external EPO status indicator displays the current EPO mode.
• White—The EPO system is armed and operational.
• Red—There has been an EPO event and the HP POD 240e NA is shutdown.
• Yellow—The EPO system is operating in test mode.
EPO accidental activation
To help prevent accidentally pressing the EPO button and activating the EPO system, each EPO button is
covered with a clear Lexan cover.
Battery backup during an EPO event
The following components are equipped with a UPS to help be sure that service is not interrupted during a
loss of power to the HP POD 240e NA:
• Environmental control system (on page 34)
• VESDA air sampling smoke detection system (on page 22)
• Fire detection system (on page 22)
• Lighting (on page 33)
IMPORTANT: All critical IT UPS devices with batteries that exceed 700VA must be connected to
the HP POD 240e NA EPO system, to be sure that the UPS batteries are disconnected during an
EPO event. For more information about connecting UPS devices to the EPO system, see the HP Performance Optimized Datacenter 240e NA Maintenance and Service Guide.
Life safety systems 21
Fire detection system
Each HP POD 240e NA is equipped with a fire alarm panel that is integrated with the fire detection system.
The fire system is designed as a stand-alone system, but the system can also interface with customer site fire
alarm systems. Customer site connections are the responsibility of the customer. Consult with HP for
connection locations.
The fire protection system includes:
• VESDA air sampling smoke detection system (on page 22)
• Manual fire pulls (on page 22)
• Fire alarm panel (on page 23)
• Fire alarm indicators (on page 23)
VESDA air sampling smoke detection system
CAUTION: Excess dust within the HP POD 240e NA can cause the VESDA smoke detector to
The VESDA system features a single zone laser scan early warning smoke detector to provide the earliest
warning of a potential fire.
The orange VESDA piping that runs throughout the HP POD 240e NA includes inlets for smoke sampling. The
VESDA uses a high-efficiency aspirator to continuously draw in air from the HP POD 240e NA and circulate
the air through a dual-stage filter:
• Stage 1—A filter removes dust and dirt from the air sample.
• Stage 2—An ultra-fine filter removes remaining contaminants in the air sample.
After the air passes through the dual-stage filter, it enters a calibrated detection chamber where a laser scans
the air sample for the presence of smoke. The VESDA system cycles through two levels if smoke is detected:
• Level 1—Smoke concentration reaches the first setpoint, and the VESDA system sends an alarm signal
• Level 2—Smoke concentration reaches the second setpoint, and the VESDA system indicates that a fire
trigger a fire alarm.
indicating that a fire might exist.
exists in the HP POD 240e NA.
IMPORTANT: The VESDA filter must be changed regularly to be sure that smoke detection
readings are accurate. For more information about changing the VESDA filters, see the HP
Performance Optimized Datacenter 240e NA Maintenance and Service Guide.
Manual fire pulls
The HP POD 240e NA has six fire pulls; two in each aisle. They are located in the life safety switch cabinet
next to each personnel door of the HP POD 240e NA.
Manually activating a fire pull does the following:
• Triggers a fire alarm
• Activates the fire alarm system horn and strobe lights
Life safety systems 22
Fire alarm panel
The fire alarm panel is located in the control cabinet in IT section A and receives signals from the VESDA or
manual fire pulls if an alarm condition exists. If an alarm condition does exist, the fire alarm panel activates
the fire alarm indicators and sends a signal to the site fire alarm system, if installed.
The fire alarm panel also has a battery backup system that provides backup power to the fire detection
system in the event of power loss to the HP POD 240e NA.
The control panel includes the following components:
• Alarm status LED
• Trouble status LED
• Input status LED
• Output status LED
• Acknowledge button
• Alarm Silence button
• System Reset button
Fire detection sequence of operations
There are two initiation sequences for the fire detection system, automatic (VESDA) initiation and manual
initiation. The fire strobe light is activated by either initiation sequence.
The fire alarm horn will sound in a temporal mode for any VESDA or manual fire pull initiation.
The fire system operator panel indicates which initiation sequence is active, using the indicator lights and a
panel alarm. These signals are also available to the site BMS system, if they are connected.
VESDA initiation
When smoke is detected, the VESDA fire detection system cycles through two levels, as described below.
• Level 1—Indicates the potential for a fire is present. The strobes illuminate and the horns sound.
• Level 2—Indicates that a fire exists. VESDA level 1 might have be reached; the strobes illuminate and
the horns sound.
Manual initiation
Manual initiation triggers the fire alarm, causes the fire strobe lights to illuminate, and sounds the horn.
Fire alarm indicators
Upon activation of a fire alarm within the HP POD 240e NA, the following alarms alert personnel:
• Strobe lights
o Internal—The HP POD 240e NA has three fire strobe lights; one in each aisle.
o External—The HP POD 240e NA has two fire strobe lights; one on each side.
• Audible horn—The HP POD 240e NA has three horns; located with the three internal strobe lights
• Alarm within the ECS
Life safety systems 23
Emergency egress
The HP POD 240e NA includes the following features for life safety egress on all access doors:
• Exit signs
• Panic bar
• Door strikes
o Standard hardware—Door strikes
o Optional hardware—Electric door strikes
Each personnel door includes a standard panic bar to be sure there is a safe exit. Any of the optional egress
hardware that is included in the HP POD 240e NA (including electric panic bar, electric strikes, and
magnetic locks) are tied to the fire alarm to enable uninhibited egress in the event of an emergency.
Life safety systems 24
Power, electrical, and controls
requirements when opening or working inside areas of the HP POD 240e NA that are marked as
Site electrical system
To be sure that the POD solution is completely and safely integrated with your facility, HP requires that you
complete the following actions for the installed electrical system prior to the installation of the HP POD
solution:
• Short circuit analysis
• Arc flash study
• Circuit breaker coordination study
These actions must be performed for all associated parts of the electrical power train. The majority of the
details and factors that are required to complete these studies are associated with the existing installed
facility infrastructure.
CAUTION: Failure to complete these studies can cause serious issues with the electrical
integration of the POD into your electrical system.
Power safety
WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with PPE
Grounding and bonding
The HP POD 240e NA must be properly earthed to be sure that a common return path for electric current
exists, limit the build-up of static electricity, and absorb an unlimited amount of current without changing its
potential. To properly ground the HP POD 240e NA to the earth, you must connect the POD to building steel,
a ground rod, or a properly installed ground well that is connected to a building’s grounding system. The
grounding electrode conductor connection point is located on the cold aisle side adjacent to the power
cabinet.
Grounding
A certified electrician must test and verify the HP POD 240e NA is properly grounded.
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
WARNING: To avoid the risk of personal injury or electric shock, the HP POD 240e NA must be
properly earthed (grounded), and each of the individual sections must be bonded together per
NFPA 70 in accordance with NEC (NA) and IEC (EMEA and APJ).
The HP POD 240e NA includes the following types of grounding.
Earth ground
Power, electrical, and controls 25
Side view shown
Bonding
All structural sections of the HP POD 240e NA are bonded by connecting all metallic, non-current carrying
items throughout the HP POD 240e NA to protect from electric shock. If all steel-to-steel areas are bonded to
one another, each object then has the same electrical potential which ultimately dissipates any high voltage
or shock across the entire HP POD 240e NA, minimizing any effects from a lightning strike, per NFPA 70 in
accordance with NEC (NA) and IEC (EMEA and APJ).
Lightning protection
The HP POD 240e NA structure and internal components are all bonded together. A common grounding
electrode conductor connection point is provided. Proper bonding and grounding of the HP POD 240e NA
minimizes the effects of a lightning strike. A surge protection device is provided on the HP POD 240e NA
input connection to protect the HP POD 240e NA electrical system from voltage transients. If your site is in an
area that is subject to frequent lightning strikes, the HP POD 240e NA must be protected in accordance with
NFPA 70 (NA) and IEC (EMEA and APJ). HP recommends that you contact a certified lightning protection
consultant.
Capacities
Each HP POD 240e NA is unique and the specific power and cooling capacities vary for each POD that uses
Adiabatic cooling. For specific capacity information, see your HP Performance Optimized Datacenter 240e NA Customized Supplement.
Power, electrical, and controls 26
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.