HP H5M59A User Manual

QuickSpecs
HP Basic Power Distribution Units

Overview

HP Basic PDUs are designed for simple installation, reliability and cost effective power distribution. They come in a variety of form factors and outlet configurations to meet the needs of today's high-density data center rack environments. With effective power distribution supporting from 12 to 42 outlet receptacles and power levels ranging from 1.9 kVA through 19.9 kVA, HP has the Basic single or 3-phase PDU for any application.
The low profile single piece design on these PDU's provides ease of access to rear devices for maintenance consideration and provides multiple mounting options. They are designed for HP racks but will also work in a large variety of third party racks as well. They can be installed on either side of the rack with outlets facing the back of the rack for easy access and improved clearance. Also for higher power density they can be installed side by side on both sides of the rack with the outlets facing in towards the center of the rack.
Basic PDU, 1U/0U Models (H5M54A shown)
Basic PDU, Mid Height Models (H5M62A/H5M70A shown)
Basic PDU, Half Height Models (H5M55A shown)
Basic PDU, Full Height Models (H5M67A/H5M73A shown)
DA - 14557 North America — Version 7 — October 1, 2013
Page 1
QuickSpecs
Overview
HP Basic Power Distribution Units
Basic PDU, 480V Half Height model (H3X07A shown)
Basic PDU, 480V Full Height model (H3X08A shown)
DA - 14557 North America — Version 7 — October 1, 2013
Page 2
QuickSpecs

Models

HP Basic Power Distribution Units
HP Basic PDU Models
HP 1.9kVA 120 Volt 12 Outlet NA/JP Basic Power Distribution Unit HP 2.8kVA 120 Volt 18 Outlet NA/JP Basic Power Distribution Unit HP 3.6kVA 200-240 Volt 12 Outlet WW Basic Power Distribution Unit HP 3.6kVA 200-240 Volt 20 Outlet WW Basic Power Distribution Unit HP 4.9kVA 208 Volt 20 Outlet NA/JP Basic Power Distribution Unit HP 4.9kVA 208 Volt 30 Outlet NA/JP Basic Power Distribution Unit HP 8.3kVA 208 Volt 36 Outlet NA/JP Basic Power Distribution Unit HP 8.6kVA 208 Volt Three Phase 18 Outlet NA/JP Basic Power Distribution Unit HP 8.6kVA 208 Volt Three Phase 30 Outlet NA/JP Basic Power Distribution Unit HP 5.7kVA 208 Volt Three Phase 27 Outlet NA/JP Dual Voltage Basic Power Distribution
Unit HP 8.6kVA 208 Volt Three Phase 30 Outlet NA/JP Dual Voltage Basic Power Distribution
Unit HP 11kVA 400 Volt Three Phase 42 Outlet NA Basic Power Distribution Unit HP Hardwired 200-240 Volt 36 Outlet WW Basic Power Distribution Unit HP 13.2kVA 480 Volt Three Phase 15 Outlet NA Basic Power Distribution Unit HP 19.9kVA 480 Volt Three Phase 30 Outlet NA Basic Power Distribution Unit
H5M54A H5M55A H5M56A H5M57A H5M58A H5M59A H5M60A H5M61A H5M62A H5M63A
H5M64A
H5M67A H5M75A
H3X07A H3X08A
DA - 14557 North America — Version 7 — October 1, 2013
Page 3
QuickSpecs

Standard Features

HP Basic Power Distribution Units
Features List
Key Features
Multiple models for flexible installation
One piece rack mount PDUs Industry standard button and keyhole mounting Easily accessible outlet receptacles and improved cable management Models range from 1.9kVA to 19.9kVA
Ultra-thin design does not interfere with rear maintenance 1U/0U and vertical form factors with flexible mounting options Easy drop in installation
The HP Basic PDUs is available in four form factors for a variety of racks and environments. All HP Basic PDUs can be mounted to stay completely out of the critical rear maintenance path needed to service IT equipment in the rack. All vertical models use industry standard button and keyhole mounting for simple drop in installation in HP 11000 G2 and Intelligent Series racks and many third party racks.
1U/0U Basic PDUs
Mounts in 1U of space in any EIA standard rack these PDUs can also mount in the side of an HP rack for 0U mounting. Available in either a low voltage model with twelve NEMA 5-20 receptacles or a high voltage model with twelve IEC C13 outlets.
Vertical Basic PDUs
A variety of sizes meet the needs of many environments Mounts vertically on either side in the rear of the rack using industry standard button and keyhole mounting. Standard mounting faces the outlet towards the rear of the rack. This configuration fully prevents interference in the maintenance zone between rear RETMA rails. Using the optional configuration of facing the outlets into the rack, multiple PDUs can be mounted on one side of the rack for higher power density.*
NOTE:
Facing the outlets into the rack will interfere with the lower few rack U spaces of the rear
maintenance zone due to breakers on the PDUs.
DA - 14557 North America — Version 7 — October 1, 2013
Page 4
QuickSpecs
Standard Features
HP Basic Power Distribution Units
Vertical PDU Form Factors
Half Height Basic PDU
Designed to fit in 22U and taller racks Available in low voltage and three phase models with up to 20 outlets. Up to 4 Half Height PDUs can be mounted in one side of a 42U or 47U rack using the optional inward facing configuration.
Mid Height Basic PDUs
Designed to fit in 36U and taller racks Available in high voltage and three phase models with a combination of C13 and C19 outlets for up to 36 outlets. New Three Phase Dual Voltage models provide three NEMA 5-20 convenience outlets for low voltage equipment in a high voltage rack.
Full Height Basic PDUs
Designed for 42U and taller racks. Available in three phase only with 36 x C13 and 6x C19 for a total of 42 outlets.
480V Basic PDUs
480V three phase 5 wire input provides 277V single phase output. Unique outlets prevent connection of non-277V compatible equipment. Available in a 15 outlet Half Height and a 30 outlet Full Height model.
NOTE:
When mounted in the standard rear facing configuration only 1 Mid or Full Height Basic PDU can be mounted per side of the rack. Up to 2 Half Height Basic PDUs can be mounted per side in the standard rear facing configuration in a 42U or taller rack.
NOTE:
HP 480V Basic PDUs can only be mounted in the standard rear facing configuration.
Easy Installation and compatibility
Warranty Upgrade Options
Standard button and keyhole mounting provides simple drop in installation in HP 11000 G2 and Intelligent Series Rack and many third party racks.
HP Basic PDUs are backed by a limited 3-year warranty. HP Basic PDUs automatically assume the Care Pack coverage level of any covered ProLiant server in the same rack.
DA - 14557 North America — Version 7 — October 1, 2013
Page 5
QuickSpecs

Service and Support

HP Basic Power Distribution Units
HP Care Pack Services
Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical.
A full range of HP Care Pack hardware and software services are available including:
Installation and start up Education courses Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and VMWare-based IT solutions helping to deliver high level of application availability. Response times range from 30 mins for critical problems to 2 hours. System Management, Performance Services and Mission Critical Support Solution
NOTE:
For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at:
NOTE:
For more complete information on HP Services offerings, customers and resellers, please visit us at:
http://www.hp.com/hps
NOTE:
Additional information regarding worldwide limited warranty and technical support is available at:
http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
http://www.hp.com/hps/carepack
DA - 14557 North America — Version 7 — October 1, 2013
Page 6
QuickSpecs

Related Options

HP Basic Power Distribution Units
HP Country specific C19 PDU Inlet Cords for H5M56A and H5M57A (required)
HP Jumper Cables
HP C19 - Nema L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord HP 240 VAC 4.5M C19-Unterminated End NA Power Cord
NOTE:
HP Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to country
specific plug inlet cord which is sold separately.
NOTE:
Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions:
HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord HP IEC C13-C14 Cable Option Kit HP IEC320-C14 to C13 (10A/4.5ft/1.37m) PDU Cable HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord HP IEC320-C14 to C13 10A/4.5ft/1.37m/ 15 PDU Cable HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord HP IEC320-C14 to C13 (10A/8ft/2.5m) PDU Cable HP C13 Straight - C14 Straight WW 250V 10AMP 3.0m Jumper Cord HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord HP 200-250V 10A C15 to C14 .76m Jumper Cable
NOTE:
Please refer to the Power Cord Matrix for more information on power cords/cable
part numbers, input/output descriptions:
http://www.hp.com/go/powercordmatrix
http://www.hp.com/go/powercordmatrix
AF593A AF592A AF584A AF582A AF583A AF577A AF581A AF576A AF580A AF579A
359615-031
E7806A
.
A0K03A 142257-B28 142257-006
A0K04A 142257-007
A0K02A
AF573A 142257-002 142257-003
A0K06A
AF590A
AF575A
AF574A 295633-B22
E7807A
.
HP Mounting Brackets
HP 277 Volt options for H3X07A and H3X08A
HP Vertical PDU 10KG2 Mounting Kit
NOTE:
Allows HP Basic PDU vertical models to be mounted in HP 10000 G2 series racks
and in the HP V142 rack.
HP LS-26 to LS-25 277 Volt 15Amp AC 0.76m Jumper Cord HP LS-26 to LS-25 277 Volt 15Amp AC 1.37M Jumper Cord HP 800VA - 277V Input / 230V Output NA Rack Mount Transformer
DA - 14557 North America — Version 7 — October 1, 2013
H6L32A
TK801A TK802A
H3X09A
Page 7
QuickSpecs
Related Options
NOTE: NOTE:
part numbers, input/output descriptions:
HP Basic Power Distribution Units
720 watt, 2U transformer converts 277V to 230V for up to 4 devices. Please refer to the Power Cord Matrix for more information on power cords/cable
http://www.hp.com/go/powercordmatrix
.
DA - 14557 North America — Version 7 — October 1, 2013
Page 8
QuickSpecs

Basic PDU Family Information

Model Selection Matrix HP Basic PDUs 1U/0U models
HP Basic Power Distribution Units
Model
1.9kVA PDU
3.6kVA PDU
Half Height vertical models
Model
2.8kVA PDU
3.6kVA PDU
4.9kVA PDU
7.3kVA PDU
8.6kVA PDU
Mid Height vertical models
4.9kVA PDU
7.3kVA PDU
8.3kVA PDU
11kVA PDU
Part Number
H5M54A
H5M56A
Part Number
H5M55A
H5M57A
H5M58A
H5M68A
H5M61A
H5M59A
H5M70A
H5M60A
H5M71A
Input Circuit
100-127V 20A
200-240V 16-20A
Input Voltage
100-127V 30A
200-240V 16-20A
200-240V 30A
200-240V 32A
200-208V 30A 3 phase Delta
200-240V 30A
200-240V 32A
200-240V 50A
200-240V 63A
Current Maximum
16A
16A
Current Maximum
24A
16A
24A
32A
41.5A
24A
32A
40A
48A
Load capacity
1920VA @120V
3680VA @230V
Load capacity
2880VA @120V
3680VA @230V
4992VA @208V
7360VA @230V
8646VA@208V3Ø
4992VA @208V
7360VA @230V
8320VA @208V
11040VA @230V
Input Connection
8ft(2.4m) cord with attached NEMA L5-20P
Detachable input power cord with an IEC 320-C20 inlet
Input Connection
8ft(2.4m) cord with attached NEMA L5-30P
Detachable input power cord with an IEC 320-C20 inlet
8ft(2.4m) cord with attached NEMA L6-30P
8ft(2.4m) cord with attached IEC 332P6
8ft(2.4m) cord with attached NEMA L15-30
8ft(2.4m) cord with attached NEMA L6-30P
8ft(2.4m) cord with attached IEC 332P6
8ft(2.4m) cord with attached CS8265C
8ft(2.4m) cord with attached IEC 363P6
*
*
Output circuit breakers
1 x 20A
1 x 16A
Output circuit breaker
2 x 20A
2 x 16A
2 x 20A
2 x 16A
3 x 20A
3 x 20A
3 x 16A
3 x 20A
3 x 16A
Outlet Connections
12 x NEMA 5­20R
12 x IEC C13
Outlet Connections
18 x NEMA 5­20R
20 x IEC C13
20 x IEC C13
20 x IEC C13
18 x IEC C13
24 x IEC C13 6 x IEC C19
24 x IEC C13 6 x IEC C19
30 x IEC C13 6 x IEC C19
30 x IEC C13 6 x IEC C19
DA - 14557 North America — Version 7 — October 1, 2013
Page 9
QuickSpecs
Basic PDU Family Information
HP Basic Power Distribution Units
Hardwired PDU
5.7kVA Dual Voltage PDU
8.6kVA Dual Voltage PDU
8.6kVA PDU
11kVA PDU
Full Height vertical models
11kVA PDU
11kVA PDU
480/277 Volt models
13.2kVA PDU
19.9kVA PDU
*
NOTE:
HP Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to country specific plug inlet cord which is sold separately.
NOTE: Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions.
http://www.hp.com/go/powercordmatrix.
Disclaimer:
determine the best connector or receptacle for your specific needs.
H5M75A
H5M63A
H5M64A
H5M62A
H5M72A
H5M73A
H5M67A
H3X07A
H3X08A
HP makes no recommendations regarding power connector manufactures. Please consult a licensed professional to
200-240V 50-63A
200-208V 20A 3 phase WYE
200-208V 30A 3 phase WYE
200-208V 30A 3 phase Delta
380-415V 16A 3 phase WYE
380-415V 16A 3 phase WYE
380-415V 30A 3 phase WYE
480V 30A 3 phase WYE
480V 30A 3 phase WYE
46A
27.7A
41.5A
41.5A
16A per phase
16A per phase
24A per phase
16A per phase
24A per phase
11040VA @230V
5764VA @208 3Ø
8646VA @208 3Ø
8646VA @208 3Ø
11084VA @ 400V 3Ø
11040VA @ 400V 3Ø
11040VA @400V 3Ø
13301VA @480V 3Ø
19952VA @480V 3Ø
Terminal block for hardwired installation
8ft(2.4m) cord with attached NEMA L21-20P
8ft(2.4m) cord with attached NEMA L21-30P
8ft(2.4m) cord with attached NEMA 15-30P
8ft(2.4m) cord with attached IEC 516P6
8ft(2.4m) cord with attached IEC 516P6
8ft(2.4m) cord with attached IEC 530P6
9.8ft(3M) cord with attached IEC 530P7
9.8ft(3M) cord with attached IEC 530P7
3 x 20A
3 x 20A
3 x 20A
3 x 20A
3 x 16A
3 x 16A
3 x 20A
3 x 20A
6 x 20A
30 x IEC C13 6 x IEC C19
20 x IEC C13 3 x NEMA 5­20R
20 x IEC C13 3 x IEC C19 3 x NEMA 5­20R
24 x IEC C13 6 x IEC C19
24 x IEC C13 6 x IEC C19
36 x IEC C13 6 x IEC C19
36 x IEC C13 6 x IEC C19
15 x LS-26
30 x LS-26
DA - 14557 North America — Version 7 — October 1, 2013
Page 10
QuickSpecs

Technical Specifications

HP Basic Power Distribution Units
All PDUs
Operating Temperature
Operating Relative Humidity (%)
Operating Elevation
Storage Temperature
Storage Relative Humidity (%)
Storage Elevation
Input Plug Length (attached cord units)
Conformance Standards
Mechanical Dimensions (WxHxD) - 1U/0U models
Mechanical Dimensions (WxHxD) - Half Height models
Mechanical Dimensions (WxHxD) - Mid Height models
Mechanical Dimensions (WxHxD) - Full Height models
Mechanical Dimensions (WxHxD) - 480V Half Height Model
Mechanical Dimensions (WxHxD) - 480V Full Height Model
Kit Contents - All Basic PDUs
50° to 122° F (10° to 50° C)
10% to 90%
0 to 10,000 ft (0 to 3048 m)
-4° to 140° F (-20° to 60° C)
5% to 95%
0 to 30,000 ft (0 to 9144 m)
96 inches (243.8 cm)
UL, CUL - NA/JPN models UL, CUL, CE, TUV, KC, EAC - WW models
17.5 x 1.66 x 6 in (44.45 x 4.2x 15.3 cm)
1.9 x 29.02 x 3.75.0 in (48 x 73.7x 9.5 cm)
1.9 x 55.12 x 9.5in (48 x 140 x 9.5 cm)
1.9 x 61.07 x 3.75 in (48 x 155.1 x 9.5 cm)
1.98 x 32.4 x 3.15 in ( 5.03 x 82.3 x 8 cm)
1.98 x 62.9 x 3.15 in ( 5.03 x 159.7 x 8 cm)
All models ship with:
Environment-friendly Products and Approach
End-of-life Management and Recycling
Mounting brackets/hardware Cord Retention bracket Tie wraps Shipping bracket Read me first card
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to:
http://www.hp.com/go/green http://www.hp.com/go/green
Products returned to HP will be recycled, recovered or disposed of in a responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.
http://www.hp.com/go/green
. To recycle your product, please go to: or contact your nearest HP sales office.
. These instructions may be
DA - 14557 North America — Version 7 — October 1, 2013
Page 11
QuickSpecs
HP Basic Power Distribution Units
Technical Specifications
© Copyright 2013 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice.
The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.
DA - 14557 North America — Version 7 — October 1, 2013
Page 12