HP E7671A, E7674A, E7675A, E7676A Installation Manual

Page 1
power distribution unit
kit
fits hp 19-inch racks
E7671A E7674A E7675A E7676A
Page 2
Contents
Notice
The information contained in this document is subject to change without notice. HEWLETT-PACKARD COMPANY MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THIS
MATERIAL, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Hewlett-Packard Company shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.
This document contains proprietary information, which is protected by copyright. All rights are reserved. No part of this document may be photocopied, reproduced, or translated into another language without the prior written consent of Hewlett-Packard Company.
Copyright: 2002 by HEWLETT-PACKARD COMPANY .
WARNING!
IMPORTANT SAFETY NOTE FOR INSTALLATION
For installations using wide-voltage-range-rated switchless power distribution units (PDU part numbers E7671-63001, E7674-63001, E7675-63001, and E7676-63001) for connection to an uninterruptable power supply (UPS) or other AC source:
n CHECK THE VOLTAGE before connecting any equipment to the PDU! Failure to check the voltage could lead to severe equipment damage!
The voltage of the PDU receptacles equals the voltage of the receptacle to which the PDU is connected. This voltage must be within the input voltage range of the equipment installed in the rack.
n CHECK THE POWER SOURCE RECEPTACLE to be sure it is installed near the rack and is easily accessible, so that the plug on the PDU power supply cord can serve as the disconnect device for the rack.
n CHECK THE TOTAL INPUT CURRENT ratings of the equipment installed in the rack to avoid overloading the PDU or any uninterruptable power supply (UPS) to which it may be connected.
The output current rating of the PDU equals the output current rating of the power source to which the PDU is connected, but not more than the maximum current rating (amperage) marked on the PDU.
n CHECK THE GROUNDING, because when installing rack-mounted products with this PDU, there is a risk of high leakage current. Reliable ground circuit continuity is vital for safe operation of this product. To reduce the risk of electric shock, earth (ground) connection is essential before connecting the PDU. Never operate this PDU with the ground conductor disconnected.
2
Page 3
DECLARATION OF CONFORMITY
according to ISO/IEC Guide 22 and EN 45014
Manufacturer's Name: Hewlett-Packard Company Manufacturer's Address: 10955 Tantau Avenue
Cupertino, CA 95014 USA
declares, that the product
Product Name: Power Distribution Units Model Number(s): E7670-63001, E7671-63001, E7672-63001
E7674-63001, E7675-63001, E7676-63001
Product Options: ALL
conforms to the following Product Specifications:
Safety: IEC 950:1991+A1+A2+A3+A4
EN 60950:1992+A1+A2+A3+A4
Contents
Supplementary Information: The product herewith complies with the requirements of the Low Voltage Directive 73/23/EEC and 93/68/EEC and carries the CE-Marking accordingly.
Mt. View, CA 94043 1 November, 2002 Location Date Susan Kipers, Business Manager
For Compliance Information: European Contact: Your Local Hewlett-Packard Sales and Service Office or
Hewlett-Packard Gmbh, Department ZQ / Standards Europe, Herrenberger Strasse 130, D-71034 Boeblingen
(FAX: +49-7031-14-3143
3
Page 4
Contents
Contents
PDU Kits: E7671A, E7674A, E7675A, and E7676A
Item Quantity P/N Description
1 2 0515-2991 Screw, Machine (Torx)
M5x10mm
2 2 0535-0081 Nut, Hex, with captive star
washer, M5
3 1 E7671-63001 16 amp PDU
E7674-63001 16 amp PDU E7675-63001 16 amp PDU E7676-63001 16 amp PDU
4 1 5981-1470EN Installation guide
Tools Needed:
T-25 Torx™ driver
Overview
The HP Power Distribution Units (PDUs) are designed to provide flexibility for your power requirements. The PDUs can be mounted both vertically and horizontally on the rear rack columns, depending on your rack configuration. Use the EIA holes for horizontal mounting, and the accessory holes for vertical mounting.
4
Page 5
5
Overview
Page 6
Installation
Installation
Caution: Turn off power to all devices in your rack before installing the PDUs. Note: Do not use sheet metal nuts to mount the PDU, because the sheet metal nuts do not assure
positive grounding.
Installing PDUs Vertically
PDUs can be installed vertically on the rear rack columns.
1. Determine where you will place the PDU on the rear rack column. Consider if you need access to any of the rack equipment, or if any components need to slide toward the rear of the rack, then locate the PDU so the power cables do not hinder access to the equipment.
Note: If the PDU will be used to connect to the wall outlet, be sure to place the PDU toward the
bottom of the rack. This allows the cable to extend easily out the bottom of the rack, under the rear door (if a rear door is installed).
2. Attach the PDU to the accessory (outside) holes in the rack column with the Torx screws and hex nuts. Use the hex inserts located toward the top and bottom of each rack column if possible. Do not use the EIA holes located to the inside of the column.
Sockets facing center of rack
M5 Threaded Inserts
3. Tighten the screws to force the star washers to pierce the paint and make solid contact with the metal column. This connects the rack chassis with earth ground to protect against possible electric shock.
6
Page 7
7
Installation
4. When connecting the PDU to the wall outlet, be sure to secure the main power cable with the clamp, as shown in the figure below.
Tighten clamp around cable
5. Connect power cables from devices to the PDU, then connect PDU to the wall outlet or UPS.
6. Turn on power to devices.
Installing PDUs Horizontally
The PDUs can be installed horizontally, with the each end of the PDU secured to each of the rear rack columns. However, you must use the EIA holes (the row of holes on the inner edge of the rack column) for this configuration.
1. Determine where you will place the PDU on the rear rack columns (usually across the top or across the bottom). Consider if you need access to any of the rack equipment, then locate the PDU so the power cables do not hinder access to the equipment.
Note: If the PDU will be used to connect to the wall outlet, be sure to place the PDU toward the
bottom of the rack. This allows the cable to extend easily out the bottom of the rack, under the rear door (if a rear door is installed).
2. Attach the PDU to the EIA holes in the rack column with the Torx screws and hex nuts.
Page 8
Installation
3. Tighten the screws to force the star washers to pierce the paint and make solidcontact with the metal column. This connects the rack chassis with earth ground to protect against possible electric shock.
4. Connect the power cables from the devices to the PDU.
5. When connecting the PDU to the wall outlet or UPS, be sure to secure the main power cable with the clamp, as shown in the figure below.
Tighten clamp around cable
6. Plug main cable into wall outlet or UPS.
7. Turn on power to devices.
Note: If the PDU is placed at the bottom of a rack containing ballast, the sockets on the PDU must be
facing the top of the rack.
8
Page 9
Installation
Electrical Connection
Circuit Breakers
The PDU is equipped with a circuit breaker for each power phase. If one phase shorts or overloads, one or both of the circuit breakers in the PDU may trip. Unplug the PDU before trying to locate and correct the electrical problem, then reset both circuit breakers on the PDU to restore power to the rack.
European Cabling
Some products sold in Europe are shipped without a power plug on the end of the PDU cable. It is the responsibility of the customer to supply the correct installation according to local electrical and building codes.
Optional Cables
P/N Voltage/Current Connector Plug Type Length
E7742A 250V / 10AMP C13 C14 2.5m (8.2’) E7743A 125V / 10 AMP C13 5-15P 2.5m (8.2’’) E7798A 250V / 16AMP C19 C20 2.5m (8.2’) E7802A 125V / 16AMP C19 5-20P 4.5m (14.8’) E7803A 250V / 16AMP C19 L6-20P 4.5m (14.8’) E7804A 250V / 16AMP C19 C20 4.5m (14.8’) E7805A* 250V / 16AMP C19 L6-30P 4.5m (14.8’) E7806A 250V / 16AMP C19 none 4.5m (14.8’) E7807A 250V / 10AMP C15 C14 0.8m (2.6’) E7808A 250V / 16AMP C19 IEC309 4.5m (14.8’) E7809A 250V / 16AMP C19 CEE7 / 7 4.5m (14.8’) E7810A 250V / 16AMP C19 China 16A 4.5m (14.8’) E7811A 250V / 16AMP C19 SI 32 4.5m (14.8’) E7812A 250V / 16AMP C19 AR20S 4.5m (14.8’)
* For use with an Uninterruptable Power Supply (UPS) only.
9
Page 10
Technical information in this document is subject to change without notice.
© Copyright Hewlett-Packard Company 2002. All Rights Reserved.
Reproductions, adaptations, or translation without prior written permission is prohibited, except as allowed under the copyright laws.
November, 2002 Document Part Number: 5981-1470EN