![](/html/c9/c975/c975f37448dbe4641fc4b37a17080581f7f5247887291e6000daa810ed31acfe/bg1.png)
power distribution unit
kit
fits hp 19-inch racks
E7671A
E7674A
E7675A
E7676A
![](/html/c9/c975/c975f37448dbe4641fc4b37a17080581f7f5247887291e6000daa810ed31acfe/bg2.png)
Contents
Notice
The information contained in this document is subject to change without notice.
HEWLETT-PACKARD COMPANY MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THIS
MATERIAL, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Hewlett-Packard Company shall not be liable for errors contained herein or for incidental or
consequential damages in connection with the furnishing, performance, or use of this material.
This document contains proprietary information, which is protected by copyright. All rights are reserved.
No part of this document may be photocopied, reproduced, or translated into another language without
the prior written consent of Hewlett-Packard Company.
Copyright: 2002 by HEWLETT-PACKARD COMPANY .
WARNING!
IMPORTANT SAFETY NOTE FOR INSTALLATION
For installations using wide-voltage-range-rated switchless power distribution units (PDU part
numbers E7671-63001, E7674-63001, E7675-63001, and E7676-63001) for connection to an
uninterruptable power supply (UPS) or other AC source:
n CHECK THE VOLTAGE before connecting any equipment to the PDU! Failure to check
the voltage could lead to severe equipment damage!
The voltage of the PDU receptacles equals the voltage of the receptacle to which the PDU is
connected. This voltage must be within the input voltage range of the equipment installed
in the rack.
n CHECK THE POWER SOURCE RECEPTACLE to be sure it is installed near the rack
and is easily accessible, so that the plug on the PDU power supply cord can serve as the
disconnect device for the rack.
n CHECK THE TOTAL INPUT CURRENT ratings of the equipment installed in the rack
to avoid overloading the PDU or any uninterruptable power supply (UPS) to which it may be
connected.
The output current rating of the PDU equals the output current rating of the power source to
which the PDU is connected, but not more than the maximum current rating (amperage)
marked on the PDU.
n CHECK THE GROUNDING, because when installing rack-mounted products with this
PDU, there is a risk of high leakage current. Reliable ground circuit continuity is vital for safe
operation of this product. To reduce the risk of electric shock, earth (ground) connection is
essential before connecting the PDU. Never operate this PDU with the ground conductor
disconnected.
2
![](/html/c9/c975/c975f37448dbe4641fc4b37a17080581f7f5247887291e6000daa810ed31acfe/bg3.png)
DECLARATION OF CONFORMITY
according to ISO/IEC Guide 22 and EN 45014
Manufacturer's Name: Hewlett-Packard Company
Manufacturer's Address: 10955 Tantau Avenue
Cupertino, CA 95014 USA
declares, that the product
Product Name: Power Distribution Units
Model Number(s): E7670-63001, E7671-63001, E7672-63001
E7674-63001, E7675-63001, E7676-63001
Product Options: ALL
conforms to the following Product Specifications:
Safety: IEC 950:1991+A1+A2+A3+A4
EN 60950:1992+A1+A2+A3+A4
Contents
Supplementary Information:
The product herewith complies with the requirements of the Low Voltage Directive
73/23/EEC and 93/68/EEC and carries the CE-Marking accordingly.
Mt. View, CA 94043 1 November, 2002
Location Date Susan Kipers, Business Manager
For Compliance Information:
European Contact: Your Local Hewlett-Packard Sales and Service Office or
Hewlett-Packard Gmbh,
Department ZQ / Standards Europe, Herrenberger Strasse 130, D-71034 Boeblingen
(FAX: +49-7031-14-3143
3