QuickSpecs
R7000 Uninterruptible Power System (UPS)
Overview
The innovative Minimally Switched Technology used in the new HP R7000 UPS improves the performance over traditional line­interactive UPS designs while reducing the cost, weight, and size of traditional double-conversion online UPS designs. The digital signal processing (DSP) enables complete digital control of the UPS resulting in increased power conditioning, lower system cost, and enhanced user interface interactivity.
DSP technology enables the practical implementation of sophisticated UPS topologies and controls. The DSP can simultaneously control multiple power converters to optimize system efficiency and other performance characteristics such as: enhanced battery management for extended battery life, and improved output voltage regulation. The result is a higher performance UPS in smaller, lighter, more reliable designs-an advantage for space-constrained equipment racks and cost conscious, co-located data center applications.
Front View:
1.
Escape Button
2.
Scroll up button
3.
Scroll down button
4.
Enter/Select button
5.
Power button
Rear View:
1.
Load segment 1 circuit breaker (controls L6-30R receptacle for NA/JPN, Item 3)
2.
Load segment 2 circuit breaker (controls L6-30R receptacle for NA/JPN, Item 15)
3.
Large output NEMA L6-30R receptacle (NA/JPN) or IEC-60309 32A receptacle on short cords (INTL) associated with load segment 1
4.
Cord retention clip attachment locations
5.
Load segment 1 circuit breaker (controls the C19 receptacles, but does not control the large output receptacle)
6.
3 x IEC C19 receptacles on load segment 1
7.
HP UPS Network Module
8.
Input power line cord with NEMA CS8265C plug (NA/JPN) or IEC-309-32A plug (INTL)
9.
Ground bonding screw
10.
Serial communications port
11.
USB communications port
12.
REPO port
13.
3 x IEC C19 receptacles on load segment 2
14.
Load segment 2 circuit breaker (controls the C19 receptacles, but does not control the large output receptacle)
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 1
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
R7000 Uninterruptible Power System (UPS)
Overview
15.
Large output NEMA L6-30R receptacle (NA/JPN) or IEC-60309 32A receptacle on short cords (INTL) associated with load segment 2
16.
ERM communication port
17.
ERM connector for the large plug on the split ERM cable
Models
NOTE:
#0D1 will appear after the part number on the sales order if HP factory integration is indicated.
HP R7KVA 4U 50A High Voltage NA/JP Uninterruptible Power System HP R7KVA 4U IEC-32A High Voltage INTL Uninterruptible Power System
Kit Contents
HP UPS R7000 HP UPS Network Module Power Products Documentation CD Depth adjustable fixed rack mounting rails, mounting brackets, cord retention clips Communications cable Two 7xC13 Extension Bars
AF462A AF463A
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 2
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Standard Features
Key Features
4U Power Packed Design
Rated at unity power at 7200VA /7200W for the NA/Japan model, and 6500VA/6500W on the international model, the HP UPS R7000 packs more power in space-conserving rack-mount design, allowing you to support more critical equipment in your rack.
R7000 Uninterruptible Power System (UPS)
High power density with up to 7200 VA /7200 Watts of power packed in just 3U rack space Greater system uptime with support for Extended Runtime Modules (ERM) Easy configuration through enhanced front panel display Enterprise-wide intelligent manageability with bundled UPS Network Module and HP Power Protector software More efficient voltage regulation with revolutionary technology Ultimate long-term battery reliability with HP Enhanced Battery Management Enhanced system flexibility with two independently controlled load segments Support for Remote Emergency Power Off (REPO) circuitry Easy serviceability through modular design Hot-Swappable Battery Backed by a three year warranty with the first year including parts and labor. HP's Pre-Failure warranty, and a $250,000 load protection guarantee*. (Certain restrictions and exclusions apply;
*Load protection guarantee available in North America only.
Optional Extended Runtime Modules (ERM) increase batter runtime during a power failure
)
Increase System Uptime with Extended Runtime Modules
Lower Cost of Ownership with Innovative Technology
Investment Protection with HP Enhanced Battery Management
Enhanced Flexibility
The Extended Runtime Modules are rack mounted battery modules that occupy 3U (5.25 inches) of rack space. The HP UPS R7000 supports up to four Extended Runtime Modules (ERM), which extend your overall battery runtime.
The HP UPS R7000 utilizes a the Digital Signal Processing industry-leading technology that continually conditions and regulates power without using the battery, thereby increasing the life of the battery. The output voltage is automatically regulated, based on the connected load and the input voltage.
HP UPS R7000 incorporates Enhanced Battery Management: an exclusive, patented technology that doubles battery service life, optimizes battery recharge time, and provides advance notice of pending battery failure. With Enhanced Battery Management, you can save 2-3 battery replacements over the life of the UPS saving hundreds of dollars giving you a lower total cost of ownership while still receiving the power protection for your critical equipment.
Six C19 outlets, and two L6-30 outlet (2x 32A IEC on the International model) provide a wide range of connection options. Two included Extension Bars provide an addition 14 C13 outlets if needed. Adding additional HP PDU Extension Bars, AF500A, provides additional C13 outlets making the R7000 and extremely flexible UPS for all environments.
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 3
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Standard Features
Remotely Monitor UPSs on the Network
Easy Configuration via Enhanced Front Panel Display
Independently Controllable Load Segments
Ease of Maintenance with Hot-Swappable Batteries and Electronics Modules
The installed UPS Network Module enables network administrators to remotely monitor UPSs and reboot network devices. It provides SNMP functionality, including power event alerts, network power diagnostics, and remote UPS reboot and testing. Used in conjunction with HP Systems Insight Manager or other SNMP capable Network Management Software, power-related problems on the network are quickly discovered and remedied.
LCD system integrated into the front panel with five button controls (three buttons for UPS power control and one button under the front bezel for configuration)
With two load segments, you have the flexibility to configure scheduled startups and shutdowns, in addition to independently control the separate load segments. Working in conjunction with HP UPS Network Module, the HP UPS R7000 can be configured to extend the runtime for more critical devices.
The UPS R7000 is modular in design, and both the battery and the electronics modules are hot swappable. HP UPSs are designed with simple access through the front panel. Users can safely install new batteries without ever powering down connected server and server options.
R7000 Uninterruptible Power System (UPS)
Extended Runtime Module (ERM), R7000
HP Quality
Compatibility
Warranty
The UPS R7000 supports up to four Extended Runtime Modules. Each module is 3U (5.25 inches), a rack mountable battery module that extends your overall battery runtime.
HP's hardware qualification is the toughest in the industry. Extensive evaluation, testing, product improvement, and an unsurpassed warranty guarantee the highest level of system protection, electrical performance, product quality and compatibility.
Compatible with all HP servers, storage, racks, rack options, and other rack mountable HP equipment. For PDU options please refer to the UPS/PDU compatibility matrix on
The HP UPS R7000 is covered by a three year warranty, with the first year including parts and labor. Also, standard on all HP UPS units, is our exclusive Battery Pre-Failure Warning which extends the advantage of a HP three-year, limited warranty by applying it to the battery before it actually fails. This warranty is offered worldwide. Specifically, the Pre-Failure Battery Warranty ensures that when customers receive notification from the HP UPS Network Module that the battery may fail, the battery is replaced free of charge under the warranty.
All HP Rackmount UPSs are also automatically covered to the full service level of ProLiant Care Packs in the same rack so there is no need to purchase additional Care Packs for the UPSs. Batteries are not covered under Care Pack Coverage
NOTE:
$250,000 Computer/Load Protection Guarantee is also provided in NA, in addition to the HP three
year, limited warranty.
www.hp.com/products/ups
.
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 4
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
R7000 Uninterruptible Power System (UPS)
Service and Support
Service and Support
Recommended HP Care Pack Services for optimal satisfaction with your HP product Recommended Services
Related HP Care Pack Services to enhance your HP product experience Related Services
HP Technology Services
HP Technology Services offers you consultants and support experts to solve your most complex infrastructure problems. We help keep your business running, boost availability and avoid downtime.
Protect your business beyond warranty with HP Care Pack Services
When you buy HP Options, it's also a good time to think about what level of service you may need. HP Care Pack services provide total care and support expertise with committed response choices designed to meet your IT and business need.
3-Year HP 24x7 4 hour Response, Hardware Support Onsite Service
Provides you with rapid remote support and if required an HP authorized representative who will arrive on site any time and day of the year to begin hardware maintenance service within 4 hours of the service request being logged.
http://h20195.www2.hp.com/V2/GetPDF.aspx/5982-6547EEE
HP ProLiant Server Hardware Installation
Provides for the basic hardware installation of HP branded servers, storage devices and networking options to assist you in bringing your new hardware into operation in a timely and professional manner
http://h20195.www2.hp.com/V2/GetPDF.aspx/5981-9356EN
3-Year HP 6 hour Hardware Support Onsite Call-to-Repair Service
Provides an IT manager with a team of support specialists who will quickly begin troubleshooting the system to help return the hardware to operating condition within 6 hours of the initial service request to the HP Global Solution Center
http://h20195.www2.hp.com/V2/GetPDF.aspx/5982-6547EN
Insight Remote Support
Parts and materials
Coverage
HP Proactive Select Service
Provides a flexible way to purchase HP best-in-class consultancy and technical services. You can buy Proactive Select Service Credits when you purchase your hardware and then use the credits over the next 12 months.
Delivers secure remote monitoring and support for HP servers and storage, 24x7 at no additional cost. Available as part of HP Warranty, Care Pack and Service Contract offers.
HP will provide HP-supported replacement parts and materials necessary to maintain the covered hardware product in operating condition, including parts and materials for available and recommended engineering improvements. Supplies and consumable parts will not be provided as part of this service; standard warranty terms and conditions apply. Parts and components that have exceeded their maximum supported lifetime and/or the maximum usage limitations as set forth in the manufacturer's operating manual or the technical product data sheet will not be provided, repaired or replaced as part of this service.
For ProLiant servers and storage systems, this service covers HP-branded hardware options qualified for the server, purchased at the same time or afterward, internal to the enclosure, as well as external monitors up to 22" and tower UPS products; these items will be covered at the same service level and for the same coverage period as the server unless the maximum supported lifetime and/or the maximum usage limitation has been exceeded. Coverage of the UPS battery is not included; standard warranty terms and conditions apply.
The defective media retention service feature option applies only to Disk or eligible SSD/Flash Drives replaced by HP due to malfunction. It does not apply to any exchange of Disk or SSD/Flash Drives that have not failed. SSD/Flash Drives that are specified by HP as consumable parts and/or that have exceeded maximum supported lifetime and/or the maximum usage limit as set forth in the manufacturer's operating
http://h20195.www2.hp.com/V2/GetPDF.aspx/4AA2-3842ENN
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 5
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Service and Support
manual or the technical data sheet are not eligible for the defective media retention service feature option.
For more information
To learn more on services for HP ESSN Options, please contact your HP sales representative or HP Authorized Channel Partner. Or visit:
www.hp.com/services/bladesystem
R7000 Uninterruptible Power System (UPS)
http://www.hp.com/services/proliant
or
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 6
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Related Options
HP UPS Options
HP Care Pack
HP R5KVA and R7KVA 3U Extended Runtime Module
NOTE:
integration is indicated.
HP Install Universal Power Supply 3KVA to Below 6KVA Service
R7000 Uninterruptible Power System (UPS)
AF464A
#0D1 will appear after the part number on the sales order if HP factory
U4693E
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 7
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
UPS Model Matrix
High Voltage Models
Part Number
Voltage Settings
AF462A (NA/JPN)
AF463A (International)
* Factory default setting.
220, 230*, 240 6300VA/ 6300W
Operating
200/208
*
7200VA/7200W
Power Out
(VA/Watts)
@230V input
R7000 Uninterruptible Power System (UPS)
Input Connection
Hubble CS8265C,
3m cord
IEC-309 32Amp,
3m cord
Output Connection
LS1: 15A CB - 3 x C19 + 1 x L6-30R LS2: 15A CB - 3 x C19 + 1 x L6-30R
LS1: 15A CB - 3 x C19 + + one pigtailed receptacle IEC-309 32Amp LS2: 15A CB - 3 x C19 + + one pigtailed receptacle IEC-309 32Amp
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 8
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Estimated Backup Times Chart (Minutes)
All Models
Load (Percent*)
20 52 62 98 117 301 359
50 13 15 33 37 103 115
80 6 7 18 21 57 66
100 4 5 13 15 39 50
NOTE:
Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
Estimated battery runtime
(minutes)
NA/JPN
INTL
R7000 Uninterruptible Power System (UPS)
With One Extended Runtime
Module
NA/JPN
(Minutes)
INTL
With Four Extended Runtime
Modules
NA/JPN
(Minutes)
INTL
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 9
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Technical Specifications
Unit Dimensions
Unit Weight
Shipping Weight
BTU Break Down
Electrical Input
Electrical Output
Battery
Maximum wattage based on voltage input
Communications
Environmental and Safety
(HxWxD)
6.75 in (17.1 cm) x 17.2 in (43.7 cm) x 28.9 in (73.4 cm)
165 lbs/75 kg
210 lbs/100 kg
BTU On Line
BTU On Battery
Battery String Voltage
Battery Type
Battery Quantity
Voltage Range
Frequency
Input Plug
Online Efficiency
REPO
Online Regulation
On battery Regulation
Voltage Wave Form
Connections
Output Protection
Type
Extended Batteries
Backup Time
Recharge Time
Battery String Voltage
Battery Type
Battery Quantity
AF426A NA/JPN
AF463A INTL
Serial Ports
Included
LED Indicators
Operating Temperature
Transit Temperature
Storage Temperature
Operating Humidity
R7000 Uninterruptible Power System (UPS)
649 INTL, 581 NA/JPN
1290 INTL, 1501 NA/JPN
216V
12V 45W
18
160-253V at 200/208V nominal; 160-253V at 220, 230, and 240V nominal
50/60 Hz
Part number AF462A: Hubble CS6285C, 3m cord Part number AF463A: IEC-309 32Amp, 3m cord
95%
Remote Emergency Power-Off disables AC power to load
-10% to +6% of nominal voltage
±5% of nominal voltage
Sine wave
See Model Selection Matrix; divided into 2 Load Segments
Re-settable circuit protectors
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Up to four ERMs supported
See Backup Times Chart
<3 hours to 80% usable capacity; <48 hours for complete recharge
216V
12V 45W
18
200-240V: 7200VA/7200W
220V: 6100VA/6100W 230V: 6300VA/6300W 240V: 6500VA/6500W
Standard DB-9 ports (ships with communication cable)
HP UPS Network Module
LED and switch membrane integrated into the front panel; with four-button control (three buttons for UPS power control and one button under the front bezel for configuration).
50° to 104° F (10° to 40° C )
-13° to 131° F (-25° to 55° C)
32° to 77° F (0° to 25° C )
20% to 80% (non-condensing)
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 10
RETIRED: Retired products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may
have older product names and model numbers that differ from current models.
QuickSpecs
Technical Specifications
Storage Humidity
Operating Altitude
Transit Altitude
Audible Noise
Safety Markings
Safety Certifications
EMC Markings
Emissions
Immunity
REPO Port
Environment-friendly Products and Approach
End-of-life Management and Recycling
R7000 Uninterruptible Power System (UPS)
5% to 95%
Up to 6,562 ft (2000 m) above sea level
49,212 ft (15,000 m) above sea level
<46db (at 1m from surface of unit)
NA/JPN: UL, cUL Int'l: GS, CE, GOST
UL1778, UL60950-1; CSA22.2 No.107.3, No.60-1950; EN50091-1-1; EN60950-1 IEC62040-1-1
NA/JPN: FCC, VCCI, ICES, CISPR Int'l: BSMI, C-Tick, CISPR
FCC CFR 47, Part 15 Class A, EN50091-2
IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5
Meets NEC code 645-11 intent and UL requirements
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to:
http://www.hp.com/go/green http://www.hp.com/go/green
Products returned to HP will be recycled, recovered or disposed of in a responsible manner.
. To recycle your product, please go to: or contact your nearest HP sales office.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.
© Copyright 2013 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice.
The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.
http://www.hp.com/go/green
. These instructions may be
DA - 14110 Worldwide — Version 5 — August 23, 2013
Page 11
Loading...