HPE Rackmountable 3 Phase Uninterruptible Power Systems
Overview
HPE Rackmountable 3 Phase Uninterruptible Power Systems
(UPS R8000/3 and R12000/3)
Crowded data centers and racks filled to capacity with storage devices, monitors, servers, communications devices, and other
equipment are driving the need for uninterruptible power with increased power density and power efficiency. The
3 Phase
Uninterruptible Power Systems provide just that. These rack
ms provide up to 12,000 watts
(W) of power in a 6-U rack form factor. This equates to 2 KW per U space, which leads the industry in power density. The UPS
R8000/3 and the R12000/3 use digital signal processing and a new On
to answer the demands
for increased power density and power efficiency.
line
UPS when power fluctuates beyond acceptable limits. Hot swappable batteries and electronics modules and an automatic bypass
reduce MTTR (mean time to repair) – down time in the event service is needed.
UPS R8000/3 and R12000/3 front view
UPS R8000/3 and R12000/3 rear view
Battery compartment (behind bezel)
Communications terminal block
Status and alarm LED display
Electronics module compartment (behind bezel)
Input/output location R8000/3, input location R12000/3 1
Output connector R12000/3
Extended Options provide an extended catalog of products tailored for customers in specific markets or with specific workloads,
requiring the utmost in performance or value. Fully integrated into the HPE management and security experience, Extended Options
represent great value and performance but typically have a longer lead-time.
HPE
-mountable Uninterruptible Power Syste
-line On Demand hybrid technology
-line On Demand combines the efficiency of a line interactive UPS, up to 97%, with the stability of a double conversion on-

HPE Rackmountable 3 Phase Uninterruptible Power Systems
HPE R8000/3 8000kVA Three Phase NA 6U Rackmount Uninterruptible Power System (Extended)
HPE R8000/3 8000kVA Three Phase INTL 6U Rackmount Uninterruptible Power System (Extended)
HPE R12000/3 12000VA Three Phase NA 6U Rackmount Uninterruptible Power System (Extended)
HPE R12000/3 12000VA Three Phase INTL 6U Rackmount Uninterruptible Power System (Extended)

HPE Rackmountable 3 Phase Uninterruptible Power Systems
Standard Features
• Unity Rated, volt amperage out equals wattage out
swappable battery and electronics modules provide ease of maintenance and faster time
failure warranty
and a load protection guarantee in North America
Superior Battery
Management
HPE UPS HPE 3 Phase UPS incorporates Enhanced Battery Management: an exclusive, patented
technology that doubles battery service life, optimizes battery recharge time, and provides advance
notice of pending battery failure. With Enhanced Battery Management, you have a lower total cost of
ownership and receive the best in the industry protection for your critical equipment.
Ease of serviceability
through hot
batteries and electronics
modules.
The HPE 3 Phase UPSs have a modular design architecture, consisting of separate, hot swappable
battery and electronics modules. Further, a built-in intelligent automatic bypass feature ensures
continuous power to your connected load even while the modules are being replaced. Ease of
maintenance and serviceability
• Increased flexibility through modular design
Increase battery back-up
time with up to four
Extended Runtime
Modules
HPE 3 Phase UPS supports a maximum of four Extended Runtime Modules (ERM), to further increase
your battery back
be automatically detected and configure when attached to the UPS. For more information on battery
backup
Multiple management
options increase
flexibility
The HPE 3 Phase UPS systems can be fully configured and monitored from the front management LCD.
For remote management the
UPS Management Module is included at no charge and provides
additional features such as out of band communications with up to 5 servers and UPS clustering for
redundancy.
Remote Emergency
Power Off Feature
The HPE 3 Phase UPS includes an isolated REPO (Remote Emergency Power Off) port. The REPO
feature allows the power to the UPS outlets to be switched off from a remote location. For more
information, refer the HPE 3 Phase UPS user’s manual.
The HPE UPS Management Module enables you to monitor and manage power environments through
comprehensive control of
UPS Management Module can support either a single
UPS configuration or provides additional power protection with support for dual redundant UPS
configuration for no
failure. The additional serial ports will provide greater power
management
The management module can be configured to send alert traps to
Systems Insight Manager and
other SNMP management programs or used as a standalone management system. This flexibility
• Highest wattage per U space. Up to 12000 VA/12KW in only 6U
• Industry leading efficiency with On-line On Demand hybrid technology
• Attached line cords for easier and faster connection to your facility power
• Hot-
to repair (MTTR)
• Industry leading efficiency with On-line On Demand hybrid technology
• Attached line cords for easier and faster connection to your facility power
• Extra-long battery life with Enhanced Battery Management (EBM)
• Extended battery run time with optional Extended Runtime Modules (ERMs)
• Easy configuration through enhanced front panel display or HPE
(included)
• Backed by a limited three-year warranty, the Hewlett Packard Enterprise pre-
-swappable
• Faster time to repair (MTTR)
• Automatic and manual bypass
times, please refer to the Back-up Times Chart.
-up time, should you have a sudden brief power outage. Each ERM is 3U high and can
HPE
HPE UPSs. The HPE
control and flexible monitoring.
-single-point-of-
HPE

HPE Rackmountable 3 Phase Uninterruptible Power Systems
enables you to monitor and manage UPSs through the network. To facilitate day-to-day maintenance
tasks, the embedded management software provides detailed system logs.
UPS Management Module provides remote management of a UPS by connecting the UPS
directly to the network. Configur
via a
standard web browser.
https://www.hpe.com/us/en/integrated-systems/rack-power-cooling.html
UPSs are backed by
a standard three year limited warranty; 3 year parts, 1 year Labor, 1 year onsite. Optional UPS
packaged services are also available for purchase. You can choose the precise level of support
Failure Battery Warning is proactively detected and notified by a LED indicator light,
y
failure. This indicator provides ample time to order a spare battery Avoid storing battery spares
because of short shelf life of the battery. The battery warranty coverage is 3 years
Uninterruptible Power System (UPS) units, extends the
year limited warranty by applying it to the battery before it actually
ensures that when customers receive the
UPS that the battery may fail, the battery is replaced free of charge
UPSs are covered by a $250,000 equipment protection guarantee. Should
your connected equipment get damaged due to a UPS failure, then your damaged equipment
HPE
ation & Management of the UPS from anywhere and at any time
For more information on the UPS Management Module please see:
Standard three year warranty with first year including parts and labor. HPE
based on your needs, from basic to business critical.
• Pre-Failure Battery Warning and its associated Warranty.
The Preshowing that the battery needs to be replaced. This notice is given 30 days prior to the batter
as a backup
for parts. The warranty for the first year of ownership includes parts and labor.
• Warranty, standard on all HPE
advantage of a HPE threefails. Specifically, the Pre-Failure Battery Warranty
notification from their HPE
under the warranty. Hewlett Packard Enterprise maintains the highest standards in the industry,
as evidenced by the HPE Pre-Failure Battery Warranty.
• In addition, HPE
is covered to up to $250,000.
The $250,000 Equipment Protection Guarantee is offered only in North America.

HPE Rackmountable 3 Phase Uninterruptible Power Systems
Service and Support
HPE Pointnext
operational services
HPE Pointnext operational services include Hewlett Packard Enterprise branded hardware options
qualified for the server, purchased at the same time or afterwards, internal to the enclosure, as well as 22"
and smaller external monitors and rack mounted UPS options.
Uninterruptible Power Systems will
be covered at the same service level and coverage period as the server. For servers or storage systems
installed within a rack, service also covers all
, contact any of our worldwide
sales offices or resellers or visit our worldwide Web site on the internet at:
http://h20565.www2.hpe.com/
Services offerings, customers and resellers, please visit
us at:
NOTE: Additional information regarding worldwide limited warranty and technical support is available
ct to change without notice and is provided "as is"
without warranty of any kind.
and services are set forth in the
express limited warranty statements accompanying such products and services.
Hewlett Packard Enterprise will provide HPE-supported replacement parts and materials necessary to
maintain the covered hardware product in operating condition, including parts and materials for available
and recommended engineering
Parts and components that have reached their maximum supported lifetime and/or the maximum usage
limitations as set forth in the manufacturer's operating manual, product quick-specs, or the technical
product data sheet will not be provided,
The defective media retention service feature option applies only to Disk or eligible SSD/Flash Drives
replaced by Hewlett Packard Enterprise due to malfunction.
HPE
HPE qualified rack options installed within the same rack.
For more information on HPE Pointnext operational services
portal/site/hpsc/
For more complete information on HPE
https://www.hpe.com/us/en/support.html
http://h20564.www2.hpe.com/hpsc/wc/public/home
The information contained herein is subje
The warranties for Hewlett Packard Enterprise products
improvements.
repaired, or replaced as part of these services.

HPE Rackmountable 3 Phase Uninterruptible Power Systems
Related Options
HPE Management Card for XR UPS
NOTE:
by connecting the UPS directly to the network. Configuration & Management of the
UPS from anywhere and at any time via a standard web browser.
HPE UPS R8000/3 R12000/3 Extended Runtime Module (Extended)
NOTE: HPE 3 PHASE UPS supports a maximum of four Extended Runtime Modules
(ERM), to further increase your battery back-up time. Each ERM is 3U high and can
be automatically detected and configure when attached to the UPS. For more
information on battery backup times, please refer to the Back-up Times Chart.
Serial Adapters for UPS
Management Module
HPE RJ45-DB89 DCE Female 5 Pack Serial Adapter
NOTE:
direct (serial) connections to up to 5 servers with
the UPS Management Module for out of band communications in the event of a
power failure.
HPE C13 - C14 WW 250V 10Amp 1.4m Jumper Cord (Recommended)
HPE C13 - C14 WW 250V 10Amp 0.7m Jumper Cord (Recommended)
HPE C19 - C20 WW 250V 16Amp 2.5m Jumper Cord (Extended)
HPE C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord (Extended)
HPE C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord (Extended)
NOTE: For more information on HPE power cords please go to:
https://h20195.www2.hpe.com/v2/getpdf.aspx/4AA6-6836ENW.pdf
HPE Pointnext
operational services
HPE Install Universal Power Supply 6KVA or Greater Service
The HPE UPS Management Module provides remote management of a UPS
The serial adapters allow

HPE Rackmountable 3 Phase Uninterruptible Power Systems
Technical Specifications
50-60 Hz auto-detection (Normal mode)
50 or 60
Output Frequency
Variation
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
100–110%: load transfers to Bypass mode after 10 minutes
110
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Sine wave; 2% THD with typical PFC load
50°F to 104°F (10°C to 40°C)
Optimal battery
performance
41°F to 77°F (5°C to 25°C)
Non-operating
Temperature
-13°F to 131°F (-25°C to 55°C)
Up to 3300 ft (1,000 meters) above sea level;
up to 6600 ft (2,000 meters) with 1% derating per +330 ft (100 meters)
Up to 49,212 ft (15,000 meters) above sea level
1266 BTU/hr maximum at 100% rated load (High Efficiency mode)
Less than 50 dBA at 1 meter (Normal mode)
Less than 55 dBA at 1 meter (Battery mode)
Delta
400v 3Φ Wye
208v 3Φ Delta
400v 3Φ Wye
Hz (Battery mode)
–125%: load transfers to Bypass mode after 1 minute

HPE Rackmountable 3 Phase Uninterruptible Power Systems
UL 1778 4th
edition; CSA
C22.2, No. 107.3
UL 1778 4th
edition; CSA
C22.2, No. 107.3
14.4 x 26 x 10.3 in (441 x 660 x 261 mm) 6U
25 x 38 x 46 in (635 x 965 x 1169 mm)
17.2 x 26 x 5.2 in (438 x 660 x 131 mm) 3U
47.25 x 31.5 x 37 in (1207 x 800 x 940 mm)
Unit Weight
Estimated Backup Times Chart (Minutes) R8000/3
Estimated Backup Times Chart (Minutes) R12000/3
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
Environment-friendly
Products and Approach
Hewlett Packard Enterprise offers end-of-life Hewlett Packard Enterprise product return, trade-in, and
recycling programs
(WxDxH)
Module (ERM)
(WxDxH)
62040-1-1
62040-1-1
-
in many geographic areas for our products

HPE Rackmountable 3 Phase Uninterruptible Power Systems
End-of-life Management
and Recycling
The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each
product type for use by treatment facilities. This information (product disassembly instructions) is posted
on the
instructions may be used by recyclers and other
WEEE treatment facilities as well as Hewlett Packard Enterprise OEM customers who integrate and re
sell Hewlett Packard Enterprise equipment.
Hewlett Packard Enterprise web site.These
-

HPE Rackmountable 3 Phase Uninterruptible Power Systems
Summary of Changes
SKU descriptions were updated.
Care Pack naming and Service and Support- Parts and Materials updated.
Technical Specifications section was revised.
Overview, Standard Features, and Related Options were revised.
Models and Related Options product descriptions were revised
NOTE was removed from Superior Battery Management.
The URL was corrected in UPS Management Module in the Product
Highlights section.
Change made in the Technical Specifications section only.
A note was added to the Product Highlights section.
Changes were made to the Production Highlights, Warranty and
Technical Specifications sections.
Changes were made to the Key Features, Production Highlights and
Related Options sections.
UPS Management Model from Related Options.
© Copyright 2018 Hewlett Packard Enterprise Development LP. The information contained herein is
subject to change without notice. The only warranties for Hewlett Packard Enterprise products and
services are set forth in the express warranty statements accompanying such pro
Nothing herein should be construed as constituting an additional warranty. Hewlett Packard Enterprise
shall not be liable for technical or editorial errors or omissions contained herein.
c04123376 - 12857 - Worldwide - V12 - 02-July-2018
Key Features and Warranty were moved into Standard Features
Product Highlights was changed to Standard Features
HPE Care Pack and Warranty Information were removed from Service and
ducts and services.