HP 6236a, 6237b schematic

TRIPLE OUTPUT POWER SUPPLY
MODELS 6236B AND 6237B
OPERATING AND SERVICE MANUAL FOR: MODEL 6236B, SERIALS 1705A-00101 AND ABOVE MODEL 6237B, SERIALS 1706A-00101 AND ABOVE
* For instruments with serial numbers above those listed, a change
page may be included. Refer to Appendix A for manual back­dating changes applying to Model 6236A and 6237 A supplies.
HP Part No. 5950-1782
Printed: February 1977.
SECTION I GENERAL INFORMATION
1-1 INTRODUCTION
1-2 This manual covers two triple output power supply models, the 6236B and 6237B. Both models are com­pact general purpose bench supplies that are particularly useful for powering developmental IC circuits, both linear and digital. Unless one model or the other is specifically identified, all information in this manual applies to both the 6236B and the 6237B.
——— CAUTION ———
Carefully read Sections II and III of this manual before attempting to operate the power supply.
1-3 DESCRIPTION
1-4 These constant-voltage/current-limiting triple output supplies combine two 0 to ±20V tracking outputs rated at 0.5 amps with an additional single output that in the Model 6236B is rated at 0 to+6 volts and up to 2.5 amps, and in the Model 6237B is rated at 0 to +18 volts and 1 amps. The +20V and -20V tracking outputs can also be used in series as a single 0 to 40V 0.5-amp output. Connections to the supply's output and to chassis ground are made to binding posts on the front panel. The supply's three outputs share a common output terminal, which is isolated from chassis ground so that anyone output term­inal can be grounded.
1-5 All outputs are protected against overload and short-circuit damage.The+18V output in the 6237B and the ±20V outputs in both models are protected by circuits that limit the output current to 110% of its nominal maxi­mum.The overload protection circuit for the +6V output in the 6236B has a current foldback characteristic that reduces the output current as an overload increases until only 1 amp flows through a short circuit. The 6V output's current limit depends on the output terminal voltage and varies linearly between 2.75 amps at 6 volts and 1 amp at zero volts.
located on the front panel. One voltage control sets the 0 to+6V (or+18V) output and another sets the voltages of the 0 to +20V and 0 to -20V outputs simultaneously. These dual tracking outputs are made more versatile by the provision of a tracking ratio control in addition to the usual voltage control. With the tracking ratio control turned fully clockwise to its "fixed" position, the dual outputs have a fixed 1:1 tracking ratio. As the ±20V voltage control is adjusted, the voltage of the negative supply tracks the posi­tive output within ±1%. Turning the tracking ratio control away from its fully-clockwise position switches the dual tracking outputs into a variable tracking ratio mode. In this mode the voltage of the negative output can be set lower than that of the positive output. The tracking ratio control allows the negative supply's output to be set to any value between a maximum that is within 10% of the positive supply's output and a minimum that is less than 0.5 volts. Once a ratio is established by the tracking ratio control, the ratio of the positive output voltage to the negative output voltage remains constant as the ±20V voltage control
varies the 0 to+20V output over its range.
1-7 The front panel also contains a line switch and a pilot light, a voltmeter and an ammeter, and a meter switch that selects one of the supply's three outputs to be monitored on both dual-range meters.
1-8 In addition to the standard 104-to-127Vac 47-to­63Hz input, three other line voltage options are available for nominal inputs of 100, 220, and 240Vac. The supply is furnished with a permanently attached 5-foot 3-wire ground­ing type line cord. The ac line fuse is in an extractor type fuseholder on the rear heatsink.
1-9 SPECIFICATIONS
1-10 Table 1-1 lists detailed specifications for the power supply.
1-11
1-12 Options are factory modifications of a standard instrument that are requested by the customer. The follow­ing options are available for the instruments covered by this manual.
OPTIONS
1-6 All controls, meters, and output terminals are
1-1
OPTION NO. DESCRIPTION
100
220
240
910
Input Power: 87-106Vac,47-63Hz,
single-phase.
Input Power: 191-233Vac,47-63Hz,
single-phase.
Input Power: 208-250Vac,47-63Hz,
single-phase. One additional operating and service manual shipped with the power supply.
The user can convert an instrument from one line voltage option to another by following the instructions in paragraph 3-4.
1-14 ACCESSORIES
1-15 The accessories listed below may be ordered from your local Hewlett-Packard field sales office either with the power supply or separately. (Refer to the list at the rear of the manual for addresses.)
1-13 Before the supply is shipped from the factory, an internalline voltage selector switch is set and the proper fuse installed for the line voltage specified on the order. A label on the rear heatsink identifies this line voltage option.
———
Before applying power to the supply, make certain that its line voltage selector switch (S3) is set for the line voltage to be used. (See CAUTION notice in paragraph 3-2 for additional information.)
CAUTION
———
Table 1-1. Specifications, Model 6236B and 6237B
NOTE
Specifications apply to both models unless otherwise indicated.
INPUT POWER:
Standard: 104-127Vac (120Vac nominal), 47-63Hz, single-phase, 112W, 140VA (Other line voltage options are listed in paragraph 1-12).
HP PART NO.
14513A
14523A
Model 6237 B 0 to +18V Output: Maximum rated output current is
1.0A. Short circuit output current is 1.1A ±5% and a fixed current limit circuit limits the output to this maximum at any output voltage setting.
TRACKING ACCURACY: The +20V and -20V outputs track within 1% with the TRACKING RATIO control in the FIXED position.
Rack Mounting Kit for mounting one 3 1/2" high supply in a standard 19" relay rack.
Rack Mounting Kit for mounting two 3 1/2" high supplies side by side in a standard 19" relay rack.
DESCRIPTION
DC OUTPUT AND OVERLOAD PROTECTION:
0 to ±20V Outputs: Maximum rated output current is
0.5A. Short circuit output current is 0.55A ±5% and a fixed current limit circuit limits the output of each supply to this maximum at any output voltage setting. Unbal­anced loads within current rating are permitted. (Switching to the variable tracking ratio mode allows the -20V output to be varied from less than -0.5V to within ±10% of the voltage setting of the +20V output.)
Model 6236B
0 to +6V Output: Maximum rated output current is 2.5A at 6V. The maximum available output current decreases with the output voltage setting. A current foldback circuit limits the output to 2.75A ±5% at 6 volts and, with decreasing voltage, reduces the current limit linearly to 1A ±15% at zero volts (short circuited).
LOAD EFFECT (Load Regulation):
All Outputs: Less than 0.01% plus 2mV for a full load
to no load change in output current.
SOURCE EFFECT (Line Regulation):
All Outputs: Less than 0.01% plus 2mV for any line
voltage change within rating.
PARD (Ripple and Noise):
All Outputs: Less than 0.35mV rms and 1.5mV p-p
(20 Hz to 20 MHz).
DRIFT (Stability):
All Outputs: Less than 0.1% plus 5mV (dc to 20Hz) during 8 hours at constant line, load, and ambient after an initial warm-up time of 30 minutes.
1-2
1-16
INSTRUMENT AND MANUAL
IDENTIFICATION
1-17 Hewlett-Packard power supplies are identified by a two part serial number. The first part is the serial number prefix, a number-letter combination that denotes the date
of a significant design change and the country of manufac­ture. The first two digits indicate the year (10 = 1970, 11= 1971, etc.) the second two digits indicate the week, and the letter "A" designates the U.S.A. as the country of manufacture. The second part is the power supply serial number. A different sequential number is assigned to each power supply, starting with 00101.
Table 1-1. Specifications, Models 6236B and 6237B (Continued)
1-18 If the serial number on your instrument does not agree with those on the title page of the manual, Change Sheets supplied with the manual or Manual Backdating Changes define the difference between your instrument and the instrument described by this manual.
1-19
1-20 One manual is shipped with each power supply unless Option 910 is ordered for each extra manual. Addi­tional manuals may be purchased from your local Hewlett­Packard field office (see the list at the rear of this manual for addresses). Specify the model number, serial number prefix, and the HP Part Number provided on the title page.
ORDERING ADDITIONAL MANUALS
LOAD EFFECT TRANSIENT RECOVERY TIME:
All Outputs: Less than 50µsec for output recovery to within 15mV of nominal output voltage following a load change from full load to half load (or vice versa).
OUTPUT VOLTAGEOVERSHOOT:
All Outputs: During turn-on or turn-off of ac power, output plus overshoot will not exceed 1 V if the output control is set for less than 1V. If the control is set for 1V or higher, there is no overshoot.
TEMPERATURE COEFFICIENT:
All Outputs: Less than 0.02% plus 1 mV voltage change per degree Celsius over the operating range from 0 to 40°C after 30 minutes warm-up.
*OUTPUT IMPEDANCE (typical):
0 to +20V Output: 0.5m
0 to -20V Output: 0.5m
Model 6236B
0 to +6V Output: 0.3m
Model 6237B
0 to +18V Output: 0.3Ω plus 1.5µH
plus 1.5µH plus 1.5µH
plus 1µH
RESOLUTION:
(Minimum output voltage change obtainable using front
panel voltage control)
0 to ±20V Outputs: 70mV Model 6236B 0 to +6V Output: 20mV
Model 6237B 0 to +18V Output: 70mV
TEMPERATURE RATINGS:
Operating: 0 to +40°C ambient. At higher temperatures, output current is derated linearly to 50% at 55°C maximum temperature.
Storage:-40°C to+75 °C.
METER RANGES:
0 to +20V Output: 0-25V, 0-0.6A
0 to -20V Output: 0-25V, 0-0.6A
Model 6236B 0 to +6V Output: 0-7V, 0-3A
Model 6237B 0 to +18V Output: 0-21V, 0-1.2A
* Operating characteristics listed as typical are provided for the user's information only and are not warranteed specifications.
METER ACCURACY:
±4% of full scale
DIMENSIONS:
3.47 in. H x 8.22 in. W x 12.56 in. D (88mm H x 209mm W x 319mm D)
WEIGHT:
9.5 lb (4.3kg)
1-3
SECTION II
INSTALLATION
2-1 INITIAL INSPECTION
2-2 Before shipment, this instrument was inspected and found to be free of mechanical and electrical defects. As soon as the instrument is unpacked, inspect for any damage that may have occurred in transit. Save all packing materials until the inspection is completed. If damage is found, file claim with carrier immediately. The Hewlett­Packard Sales and Service office should be notified as soon as possible.
2-3 Mechanical Check
2-4 This check should confirm that there are no broken knobs or connectors, that the cabinet and panel surfaces are free of dents and scratches, and that the meter is not scratched or cracked.
2-5 Electrical Check
2-6 The instrument should be checked against its elec trical specifications. Section V includes an "in-cabinet" per­formance check to verify proper instrument operation.
Figure 2-1. Outline Diagram
2-7 INSTALLATION DATA
2-8 The instrument is shipped ready for bench operation. Before applying power to the instrument, see the CAUTION notice in paragraph 3-2.
2-9 Location
2-10 This instrument is air cooled. Sufficient space should be allotted so that a free flow of cooling air can reach the rear of the instrument when it is in operation. It should be used in an area where the ambient temperature does not exceed 40°C (up to 55°C with derating).
2-11 Outline Diagram
2-12 Figure 2-1 illustrates the outline shape and dimen­sions of this supply.
2-13 Rack Mounting
2-14 This instrument may be rack mounted in a standard 19-inch rack panel either by itself or alongside a similar unit. Figures 2-2 and 2-3 show the components of the rack mounting kits available for this power supply. Ordering information for rack mounting accessories is given in para­graph 1-14.
Figure 2-2. Rack Mounting, One Unit
Figure 2-3. Rack Mounting, Two Units
2-1
2-15 Input Power Requirements
2-16 Depending on the line voltage option ordered, the supply is ready to be operated from one of the power sources listed in Table 2-1. The input voltage range, and the input current and power at high line voltage and full load is listed for each option. A label on the rear heat sink identifies the line voltage option of your supply. All options of this model operate from a 47-63 Hz single-phase line.
2-17 If desired, the user can easily convert the unit from any of these options to another by following the instructions in paragraph 3-4. A unit is converted by resetting an internal line voltage selector switch, replacing the fuse, and changing the line voltage tag.
2-20 To preserve the protection feature when operating the instrument from a two-contact outlet, use a three-prong to two-prong adapter (if permitted by local regulations) and connect the green lead on the adapter to ground.
2-21 Model 6236B and 6237B supplies are equipped at the factory with a power cord plug appropriate for the user's location. Figure 2-4 illustrates the standard configu­rations of power cord plugs used by HP. Above each draw­ing is the HP option number for that configuration of power connector pins. Below each drawing is the HP Part Number for a replacement power cord equipped with a plug of that configuration. Notify the nearest HP Sales and Service Office if the appropriate power cord is not included with the instrument.
2-22 Repackaging for Shipment
———
If the supply might possibly have been converted to a line voltage option other than the one marked on its identifying label without being relabeled in some way, check the setting of the line voltage selector switch and the fuse rating before applying
power. (See CAUTION in paragraph 3-2.)
CAUTION
———
2-18 Power Cable
2-19 To protect operating personnel, the National Electrical Manufacturers Association (NEMA) recommends that the instrument panel and cabinet be grounded. This instrument is equipped with a three conductor power cable. The third conductor is the ground conductor and when the cable is plugged into an appropriate receptacle, the instru­ment is grounded. The offset pin on the power cable three­prong connector is the ground connection. In no event shall this instrument be operated without an adequate cabinet ground connection.
2-23 To insure safe shipment of the instrument, it is recommended that the package designed for the instrument be used. The original packaging material is reusable. If it is not available, contact your local Hewlett-Packard field office to obtain the materials. This office will also furnish the address of the nearest service office to which the instrument can be shipped and provide the Authorized Return label necessary to expedite the handling of your instrument return. Be sure to attach a tag to the instrument which specifies the owner, model number, full serial number, and service required, or a brief description of the trouble.
Figure 2-4. Power Cord Configurations
Table 2-1. Input Power Requirements
Option Line Voltage Range Input Current Input Power
100 (100 Vac) 87-106 Vac 1.3A 140 VA Standard (120 Vac) 104-127 Vac 1.1A 140 VA 220 (220 Vac) 191-233 Vac 0.6A 140 VA 240 (240 Vac) 208-250 Vac 0.55A 140 VA
2-2
SECTION III
OPERATING INSTRUCTIONS
a. Connect line cord to power source and turn LINE switch { on. LINE ON indicator | will light.
Figure 3-1. Controls and Indicators
3-1 TURN-ON CHECKOUT PROCEDURE
3-2 The following steps describe the use of the Model 6236B or 6237B front panel controls and indicators illus­trated in Figure 3-1 and serve as a brief check that the sup­ply is operational. Follow this checkout procedure or the more detailed performance test of paragraph 5-6 when the instrument is received and before it is connected to any load equipment. Proceed to the more detailed procedures beginning in paragraph 5-6 if any difficulties are encountered.
CAUTION
——
Before applying power to the supply, make certain that its line voltage selector switch (S3) is set for the line voltage to be used. This switch is mounted on the circuit board behind the voltmeter and is visible through the perforations in the top cover. The positions of the two white marks on the switch indicate the switch setting (see Figure 3-2). If the switch setting does not correspond to the intended power source, proceed to paragraph 3-4 before applying power.
———
b. Set METER switch }
no load connected, vary +6V VOLTAGE control ~ over its range and check that the voltmeter responds to the control setting and the ammeter indicates zero.
c. Set the +6V VOLTAGE control for a 6-volt meter indication and short the +6V output terminal to COM (common) terminal ammeter should indicate a short-circuit output current of approximately 1.0A (1.1 A in the 6237B). Remove the short from the output terminals.
d. Set the METER switch to the +20V position and
turn TRACKING RATIO control FIXED position. With no load connected, vary ±20V VOL­TAGE control meter responds to the control setting and the ammeter indicates zero.
e. Set the ±20V VOLTAGE control for a 20-volt meter indication and short the +20V output terminal to the com­mon terminal with an insulated test lead. The ammeter should indicate a short-circuit output current of 0.55A ±5%. Remove the short from the output terminals.
f. Repeat steps (d) and (e), but substitute the -20V position of the METER switch and the -20V output ter­minal.
g. Adjust the +20V output for a 20V meter indication. Then set the METER switch to the -20V position and check the effect of the TRACKING RATIO control on the voltage of the -20V output. The -20V output should be adjustable from less than 0.5 volts to a maximum of 18 to 22 volts.
3-3 If this brief checkout procedure or later use of the supply reveals a possible malfunction, see Section V of this manual for detailed test, troubleshooting, and adjustment procedures.
over its range and check that the volt-
to the +6V position and, with
with an insulated test lead. The
fully clockwise to the
NOTE
For the Model 6237B, substitute+18V for +6V in the following steps.
3-4 LINE VOLTAGE OPTION CONVERSION
3-5 To convert the supply from one line voltage option to another, the following three steps are necessary:
3-1
Figure 3-2. line Voltage Selector (Set for 120 Vac)
1. After making certain that the line cord is discon­nected from a source of power, remove the top cover from the supply and set the two sections of the line voltage selector switch for the desired line voltage (see Figure 3-2).
2. Check the rating of the installed fuse and repla­ce it with the correct value, if necessary. For options 100 or 120, use a normal time-constant 2-amp fuse (HP Part No. 2110-0002). For Options 220 or 240, use a normal time­constant 1-amp fuse (HP Part No. 2110-0001).
3. Mark the instrument clearly with a tag or label indicating the correct line voltage to be used.
3-6 OPERATION
3-10 Overload Protection Circuits
3-11 ±20-Volt Current Limit. The +20V and -20V
outputs are individually protected against overload or short­circuit damage by separate current limit circuits adjusted at the factory to limit the output current to 0.55A ±5%. (This is 110% of the maximum rated output.) The current limits can be set by adjusting resistor R6 for the +20V output and R26 for the -20V output. (See paragraph 5-47 for current limit calibration instructions.) No deterioration of supply performance occurs if the output current remains below the current limit setting. If a single load is connected between the +20V and -20V outputs, the circuit set for the lesser current limit will limit the output.
3-12 +6V Current Foldback (Model 6236B). The over­load and short-circuit protection circuit for the +6V output of the Model 6236B reduces the output current limit as the output terminal voltage decreases. (The operating region of the +6V output is enclosed by heavy lines in Figure 3-3). The maximum rated output current is 2.5A and the current limit is factory-adjusted to operate at 2.75A ±5% when the output is 6 volts. At lower output voltages, the circuit reduces the maximum obtainable output current linearly until 1A ±15% flows when the output is shorted. The shortcircuit current cannot be adjusted, but R46 can be set to limit the maximum current at 6V to 2.75A ±5%. (See paragraph 5-47 for current limit calibration instruction.)
3-7 This power supply can be operated individually or in parallel with another supply (see paragraph 3-19). All output terminals are isolated from ground. The ±20V and +6V or +18V outputs use a single common output terminal. This common (COM) terminal or anyone of the other output terminals may be grounded to the chassis at
the front panel ground terminal ( outputs may be left floating. Loads can be connected separately between each of the 0 to 20V output terminals and the COM terminal, or between the -20V and the +20V terminals for a 0 to 40V output.
in Figure 3-1 ), or all
3-8 Tracking Ratio Control
3-9 With the TRACKING RATIO control in the FIXED position, the voltage of the -20V supply tracks that of the +20V supply within 1% for convenience in varying the symmetrical voltages needed by operational amplifiers and other circuits using balanced positive and negative inputs. Turn the TRACKING RATIO control counterclock­wise out of the FIXED position to set the voltage of the ­20V supply lower than that of the +20V supply. The negative supply can be set from a minimum of less than
0.5 volts to a maximum within 10% of the +20V supply's output. Once this is done, the ±20V VOLTAGE control still controls both outputs and maintains a constant ratio between their voltages.
3-13 +18Volt Current Limit (Model 6237B). The +18­volt output of the Model 6237B is protected by a fixed cur­rent limit circuit that operates at 1.1 A (110% of its maxi­mum rated output). The circuit is similar to the ones in the ±20-volt supplies. (See paragraph 5-47 for calibration instructions.)
3-14 Operation Beyond Rated Output
3-15 The supply may be able to provide voltages and currents greater than its rated maximum outputs if the line voltage is at or above its nominal value. Operation can ex­tend into the shaded areas on the meter faces without damage to the supply, but performance cannot be guaranteed to meet specifications. If the line voltage is maintained in the upper end of the input voltage range, however, the supply probably will operate within its specifications.
3-17 Connect each load to the power supply output terminals using separate pairs of connecting wires. This minimizes mutual coupling between loads and takes full advantage of the low output impedance of the supply. Load wires must be of adequately heavy gauge to maintain satisfactory regulation at the load. Make each pair of connecting wires as short as possible and twist or shield
3-2
them to reduce noise pick-up. If shielded wire is used, connect one end of the shield to the power supply ground terminal and leave the other end unconnected.
3-18 If load considerations require locating output power distribution terminals at a distance from the power supply, then the power supply output terminals should be connected to the remote distribution terminals by a pair of twisted or shielded wires and each load should be connected to the remote distribution terminals separately.
3-19 Parallel Operation
3-20 Two or more power supplies can be connected in parallel to obtain a total output current greater than that available from one supply. The total output current is the sum of the output currents of the individual supplies. The output voltage controls of one power supply should be set to the desired output voltage, and the other supply set for a slightly larger output voltage. The supply set to the lower output voltage will act as a constant voltage source, while the supply set to the higher output will act as a current-limited source, dropping its output voltage until it equals that of the other supply. The constant voltage source will deliver only that fraction of its rated output current necessary to fulfill the total current demand.
3-24 Reverse Current Loading. An active load connected to the power supply may actually deliver a reverse current to the supply during a portion of its operating cycle. An external source cannot be allowed to pump current into the supply without risking loss of regulation and possible damage to the output capacitor. To avoid these effects, it is necessary to preload the supply with a dummy load resistor so that the power supply delivers current through the entire operating cycle of the load device.
3-25 Reverse Voltage Protection. Internal diodes con­nected with reverse polarity across the output terminals protect the output electrolytic capacitors and the driver transistors from the effects of a reverse voltage applied across a supply output. Since series regulator transistors cannot withstand reverse voltage either, diodes are also connected across them. When operating supplies in parallel, these diodes protect an unenergized supply that is in parallel with an energized supply.
3-21 Special Operating Considerations
3-22 Pulse Loading. The power supply will automatically
cross over from constant-voltage to current-limit operation
in response to an increase in the output current over the preset limit. Although the preset limit may be set higher than the average output current, high peak currents as occur in pulse loading may exceed the preset current limit and cause crossover to occur and degrade performance.
3-23 Output Capacitance. An internal capacitor across the output terminals of the power supply helps to supply high-current pulses of short duration during constant-volt­age operation. Any capacitance added externally will im­prove the pulse current capability, but will decrease the load protection provided by the current limiting circuit. A high-current output pulse may damage load components before the average output current is large enough to cause the current limiting circuit to operate.
Figure 3-3. Current Limit Characteristics of the 6V Supply
(Model 6236B)
3-3
SECTION IV
PRINCIPLES OF OPERATION
4-1 OVERALL DESCRIPTION
4-2 This section presents the principles of operation of the Models 6236B and 6237B Triple Output Power Supply. Throughout this section refer to the combined schematic diagram of Figure 7-1.
NOTE
All information in this section applies to both
models unless otherwise indicated.
4-3 The two primary windings of the power transformer are connected in one of four different ways by setting the two slide switches mounted on the circuit board. These switches select one of the nominal ac input voltages for which the supply is designed: 100V, 120V, 220V, or 240V.
4-4 The transformer secondaries, together with rectifiers and capacitor filters, provide raw dc for the three output regulator circuits and for another regulator that pro­vides reference and bias voltages to the output regulators.
4-5 By comparing its output to a high-stability refer­ence, the 0 to +6-volt regulator (6236B) or 0 to +18­volt regulator (6237B) holds its output voltage at the value determined by a front panel control. Any error in the actual output as compared to the desired output is amplified by an operational amplifier and applied as feedback to control the conduction of a series regulator transistor. As a result, the voltage across the series transistor varies so as to hold the output voltage constant at the desired level. The high gain of the voltage comparison amplifier and the stability of the reference voltage ensure that input voltage or load current variations have little effect on the output voltage.
4-6 The 0 to +6-volt output in the Model 6236B is protected by a current foldback limiter to minimize dissipation in the series regulator transistor during overloads. In a current foldback circuit, the current limit depends on the output terminal voltage and in this regulator ranges from 2.75A±5% at 6 volts to 1A±15% with the output shorted. (An output of 2.75A is 110% of the 2.5A rated maximum at 6 volts.) The operating region of the +6-volt regulator output is enclosed by a heavy line in Figure 3-3. If the operating point reaches the diagonal current limit line, a decrease in load resistance moves the operating point down the line, reducing the output voltage
and current. Current foldback is controlled by a second operational amplifier in the regulator that monitors the dc output current. This current comparison amplifier takes control of the output away from the voltage comparison amplifier when the current reaches the design limit. Removing the overload restores constant voltage operation automatically.
4-7 The +20-volt regulator has a fixed current limit at 110% of its 0.5 amp maximum rated output but is otherwise similar to the +6-volt regulator.
4-8 The 0 to -20-volt regulator is, in turn, similar to the +20-volt regulator except that it resembles a complementary mirror image of the latter. The output voltages of the +20volt and -20-volt supplies are both set by the same front panel control and track each other within 1% in the fixed tracking ratio mode. Precise tracking of the two outputs is achieved by controlling the positive output conventionally and using that output as the reference voltage for the negative output.
4-9 The 0 to +18-volt regulator in the Model 6237B is similar to the +20-volt regulator. It has a fixed current limit at 110% of its 1.0 amp output.
4-10 The reference and bias supply provides reference and bias voltages for the output regulators.
4-11 The turn-on/turn-off control circuit prevents output transients when the supply is turned on or off. It does this by delaying the application of certain bias and reference voltages at turn-on and removing them shortly after turn-off.
4-12 A three-position meter switch selects which of the supplies has its output voltage and current indicated on the front panel meters. The proper range of the dual­range meters is selected automatically
4-13 DETAILED CIRCUIT DESCRIPTION
4-14 0 To +20-Volt Regulator
4-15 Voltage Comparison Amplifier. The voltage com­parison amplifier in the +20-volt supply controls the conduc­tion of series regulator transistor Q1 so that the voltages at the two inputs of the amplifier remain equal. A fixed voltage divider holds its inverting input (U1-2) at -16mV. Its non­inverting input (U1-3) monitors the output voltage in series
4-1
with the voltage across R1. Since R2 is connected between the -6.2V reference supply and a point that feedback action holds near -16mV, its current remains constant. This current flows through R1 to produce a voltage drop across R1 proportional to its resistance setting, thus the output voltage of the supply is proportional to the resistance setting of R1. At the output of the voltage comparison amplifier (U1-1), a positive voltage change corresponds to a decrease in the conduction of Q1.
and returning control to the voltage comparison amplifier.
4-20 Turn-On/Turn-Off Control. When the power supply is turned on or off, Q15 in the turn-on control circuit with­holds turn-on bias from Q1 while the regulator bias voltages are too low. This prevents an output voltage transient from occurring before the amplifiers are properly biased. The output of the -6.2V reference supply is also temporarily held at a low voltage by Q14, which conducts to short that output.
4-16 CR2 and CR3 protect the input of the amplifier against transient overloads, C2 and R4 speed up loop response time, and C4 and R12 stabilize the supply's high frequency characteristics.
4-17 OR-Gate. To permit either the voltage comparison amplifier or the current comparison amplifier to control the series regulator transistor, the outputs of both amplifiers are connected to the base of driver Q2 through an OR-gate composed of CR5 and CR6. CR5 is normally reverse biased by a negative output from the current comparison amplifier, permitting the voltage comparison amplifier to drive Q2 through CR6. An overload drives the output of the current comparison amplifier positive, forward biasing CR5 and reducing the supply output. When the overload is removed, CR5 is reverse biased again and the voltage com­parison amplifier resumes control of the output.
4-18 Driver and Series Regulator. The -12.4V output of the bias supply provides the turn-on bias for series regulator transistor Q1. Its complete current path includes Q15, CR59, R 14, and Q1, and returns to common through current monitoring resistor R8. (It is because this bias current flows through R8 that the output ammeter requires the zero offset bias circuit described in paragraph 4-43.) Through the OR-gate, either the voltage or the current comparison amplifier controls the conduction of driver Q2, which regulates the flow of turn-off bias through Q1's base-emitter circuit. The algebraic sum of the nearly constant turn-on bias through R14 and the variable turn-off bias through Q2 controls the conduction of series regulator transistor Q1.
4-19 Current Limit Circuit. In the +20-volt regulator, the current comparison amplifier compares the voltage across current monitoring resistor R8 to the fixed voltage across part of current limit adjust potentiometer R6. The current limit adjustment is set so that the input voltage to the current comparison amplifier is negative in the normal operating region, but becomes zero when the output current increases to 0.55 amps. When the amplifier's input voltage reaches zero, it takes control of the regulator output voltage and reduces it as necessary to keep the output current from exceeding 0.55 amps. When the overload is removed, the output of the current comparison amplifier goes negative, reverse biasing CR5
4-21 Circuit Protection Components. Diodes CR1, CR7, and CR9 each protect the +20-volt supply from specific hazards. Output diode CR1 protects the supply components if a reverse voltage is applied to the output terminals. A common way for this to occur is for an unenergized supply to be connected in series with another that is energized. If the output voltage is turned down quickly while a large capacitor is connected across the output, CR7 protects driver Q2 from excessive dissipation by shunting some of its base current to common. The series regulator diode, CR9, protects the series regulator transistor from reverse voltage. Reverse series regulator voltage could occur if a deenergized supply were connected in parallel with an energized one.
4-22 0 To -20-Volt Regulator
4-23 Instead of using an NPN driver and a PNP series regulator in the negative output line as in the +20-volt regulator, the -20-volt regulator uses a PNP driver and an NPN series regulator in the positive output line. The -20­volt regulator circuit is the complementary equivalent of the +20-volt circuit in other respects, as well. Their current limit circuits operate similarly. At the outputs of the current and voltage comparison amplifiers in the -20­volt circuit, a negative voltage change corresponds to a decrease in series regulator conduction. The turn-on bias for its series regulator transistor, Q3, is supplied from a positive voltage source, the +7.5V bias supply, and is switched on and off by Q13 in the turn-on control circuit.
4-24 The -20-volt supply uses the output of the +20­volt supply as its reference voltage. As a result, both outputs are set by a single front panel control and track each other with in 1% in the fixed tracking ratio mode. Two resistors in resistor network Z1 are connected in series between the +20volt and -20-volt outputs. These resistors are closely matched in resistance and temperature coefficient so that the voltage across each is exactly half of the total. The midpoint of this divider is connected to the non-inverting input of the -20-volt supply's voltage comparison amplifier. The amplifier's inverting input is connected to common through R32 to hold it at zero volts. The amplifier keeps its differential input voltage at zero by matching the output voltage of the -20-volt supply to that of the +20-volt supply.
4-2
Loading...
+ 24 hidden pages