Only qualified service technicians should attempt to service or maintain this icemaker.
No such service or maintenance should be undertaken until the technician has
thoroughly read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call or write to the HOSHIZAKI Technical Support Department for
assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City , GA 30269
Attn: HOSHIZAKI T echnical Support Department
Phone: 1-800-233-1940 T echnical Service
(770) 487-2331
Fax:(770) 487-3360
NOTE: T o expedite assistance, all correspondence/communication MUST include the following
information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
Please review this manual. It should be read carefully before the icemaker is serviced
or maintenance operations are performed. Only qualified service technicians should
service and maintain the icemaker. This manual should be made available to the
technician prior to service or maintenance.
CONTENTS
PAGE
I. SPECIFICATIONS .................................................................................................... 5
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROX. ICE PRODUCTION
PER 24 HR.
lbs./day ( kg./day )
Reference without *marks
SHAPE OF ICE
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W ( KWH/100 lbs. )
WATER gal./24 HR. ( gal./100 lbs. )
EXTERIOR DIMENSIONS ( WxDxH )
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
- DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- REQUIRED
OPERATION CONDITIONS
208-230/60/1 ( 3 wire with neutral for 115 V )
12.6 A ( 5 min. freeze AT 104° F / WT 80° F )
20A
20A
30.1 lbs. ( 13.7 kg. ) 1440 pcs.
N/A
90° F / 70° F70° F / 50° F
2235 ( 4.75 )2180 ( 4.08 )
247 ( 21.9 )479 ( 37.3 )
48" x 273¦8" x 273¦8" ( 1219 x 695 x 695 mm. )
Stainless steel, Galvanized Steel ( Rear )
Net 275 lbs. ( 125 kg. ) Shipping 315 lbs. ( 143 kg. )
Permanent Connection
Inlet 1¦2" FPT
Outlet 3¦4" FPT
3
¦8" ID Pipe
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled, Overflow Pipe
N/A
Thermostat
Hermetic, Model CS14K6E-PFV
Air-cooled, Fin and Tube type
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve
R404A, 3 lbs. 14 oz. ( 1750 g. )
High 467 PSIG, Low 230 PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
N/A
Ice Storage Bin
VOLTAGE RANGE 187 - 264 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESS. 10 - 113 PSIG
1249 (566) 1178 (535) 1053 (478)
We reserve the right to make changes in specifications and design without prior notice.
5
2. KM-1300SWF (Water-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROX. ICE PRODUCTION
PER 24 HR.
lbs./day ( kg./day )
Reference without *marks
SHAPE OF ICE
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W ( KWH/100 lbs. )
WATER gal./24 HR. ( gal./100 lbs. )
WATER COOLED CONDENSER
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- REQUIRED
OPERATION CONDITIONS
We reserve the right to make changes in
specifications and design without prior notice.
208-230/60/1 ( 3 wire with neutral for 115 V )
9.7 A ( 5 MIN. Freeze AT 104° F / WT 80° F )
20A
20A
Ambient Water Temp. (°F)
Temp. (°F) 50 70 90
70
80
90
100
*1252 ( 568 ) 1233 ( 559 ) 1176 ( 533 )
1238 ( 561 ) 1209 ( 548 ) 1134 ( 514 )
1233 ( 559 ) *1188 ( 539 ) 1119 ( 508 )
1211 ( 549 ) 1172 ( 532 ) 1056 ( 479 )
Crescent Cube
30.1 lbs. ( 13.7 kg. ) 1440 pcs.
N/A
90° F / 70° F70° F / 50° F
2050 ( 4.0 )1975 ( 3.8 )
325 ( 27.4 )623 ( 49.8 )
1521 ( 128 )964 ( 77 )
48" x 273¦8" x 273¦8" ( 1219 x 695 x 695 mm. )
Stainless steel, Galvanized Steel ( Rear )
Net 265 lbs. ( 120 kg. ) Shipping 315 lbs. ( 143 kg. )
Permanent Connection
Inlet
Outlet
1
¦2" FPTCondenser Inlet1¦2" FPT
3
¦4" FPTCondenser Outlet3¦8" FPT
3
¦8" ID Pipe
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled, Overflow Pipe
Water Regulator
Thermostat
Hermetic, Model CS14K6E-PFV
Water-cooled, Tube in Tube type
Vertical type, Stainless Steel and Copper
Thermostatic ExpansionValve
R404A, 2 lb. 2 oz. ( 950 g. )
High 427 PSIG, Low 230 PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
N/A
Ice Storage Bin
VOLTAGE RANGE187 - 253 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESS. 10 - 113 PSIG
6
3. KM-1300SRF (Remote air-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROX. ICE PRODUCTION REFERENCE
PER 24 HR.
lbs./day ( kg./day )
Reference without *marks
SHAPE OF ICE
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W ( KWH/100 lbs. )
WATER gal./24 HR. ( gal./100 lbs. )
EXTERIOR DIMENSIONS ( WxDxH )
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
- DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
We reserve the right to make changes in
specifications and design without prior notice.
208-230/60/1 ( 3 wire with neutral for 115 V )
14.5 A ( 5 min. freeze AT 104° F / WT 80° F )
20A
20A
Ambient Water Temp. (°F)
Temp. (°F) 50 70 90
70*1296 (588) 1248 (566) 1173 (532)
80
90
100
Crescent Cube
30.1 lbs. ( 13.7 kg. ) 1440 pcs.
N/A
90°F/70°F70°F/50°F
2350 ( 4.98 )2300 ( 4.26 )
273 ( 24.1 )456 ( 35.2 )
48" x 273¦8" x 273¦8" ( 1219 x 695 x 695 mm. )
Stainless steel, Galvanized Steel (Rear)
Net 255 lbs. ( 116 kg. ) Shipping 315 lbs. ( 143 kg. )
Permanent Connection
Inlet 1¦2" FPT
Outlet 3¦4" FPT
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled, Overflow Pipe
N/A
Thermostat
Hermetic, Model CS14K6E-PFV
Air-cooled remote, Condenser Unit URC-12F
recommended
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve,
Condensing Pressure Regulator on URC-12F
R404A, 11 lbs. 7 oz. ( 5200 g. )
( Ice maker 7 lbs.; Cond. unit 4 lbs. 7 oz. )
HIGH 467 PSIG, LOW 230 PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
N/A
Ice Storage Bin, Remote Condenser Unit
VOLTAGE RANGE 187 - 264 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESS. 10 - 113 PSIG
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROX. ICE PRODUCTION
PER 24 HR.
lbs./day ( kg./day )
Reference without *marks
SHAPE OF ICE
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W ( KWH/100 lbs. )
WATER gal./24 HR. ( gal./100 lbs. )
EXTERIOR DIMENSIONS ( WxDxH )
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
- DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- REQUIRED
OPERATION CONDITIONS
208-230/60/3
7.8 A ( 5 min. freeze AT 104° F / WT 80° F )
20A
20A
30.1 lbs. ( 13.7 kg. ) 1440 pcs.
N/A
90° F / 70° F70° F / 50° F
2275 ( 5.0 )2150 ( 3.9 )
292 ( 21.9 )488 ( 37.3 )
48" x 273¦8" x 273¦8" ( 1219 x 695 x 695 mm. )
Stainless steel, Galvanized Steel ( Rear )
Net 275 lbs. ( 125 kg. ) Shipping 315 lbs. ( 143 kg. )
Permanent Connection
Inlet 1¦2" FPT
Outlet 3¦4" FPT
3
¦8" ID Pipe
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled, Overflow Pipe
N/A
Thermostat
Hermetic, Model CS14K6E-TF5
Air-cooled, Fin and Tube type
Vertical type, Stainless Steel and Copper
Thermostatic ExpansionValve
R404A, 3 lbs. 14 oz. ( 1750 g. )
High 467 PSIG, Low 230 PSIG
High Voltage Cut-out; Low Voltage Cut-out (Internal)
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
N/A
Ice Storage Bin
VOLTAGE RANGE187 - 253 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESS. 10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
8
5. KM-1300SWF3 (Water-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMP ACITY
MAXIMUM FUSE SIZE
APPROX. ICE PRODUCTION
PER 24 HR.
lbs./day ( kg./day )
Reference without *marks
SHAPE OF ICE
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W ( KWH/100 lbs. )
WATER gal./24 HR. ( gal./100 lbs. )
WATER COOLED CONDENSER
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
EVAPORATOR
REFRIGERANT CONTROL
REFRIGERANT CHARGE
DESIGN PRESSURE
P.C. BOARD CIRCUIT PROTECTION
COMPRESSOR PROTECTION
REFRIGERANT CIRCUIT PROTECTION
LOW WATER PROTECTION
ACCESSORIES - SUPPLIED
- REQUIRED
OPERATION CONDITIONS
208-230/60/3
6.9 A ( 5 MIN. Freeze AT 104° F / WT 80° F )
20A
20A
30.1 lbs. ( 13.7 kg. ) 1440 pcs.
N/A
90° F / 70° F70° F / 50° F
2125 ( 4.0 )2075 ( 3.8 )
342 ( 27.7 )648 ( 49.8 )
1372 ( 112 )885 ( 68 )
48" x 273¦8" x 273¦8" ( 1219 x 695 x 695 mm. )
Stainless steel, Galvanized Steel ( Rear )
Net 265 lbs. ( 120 kg. ) Shipping 315 lbs. ( 143 kg. )
Permanent Connection
Inlet
Outlet
1
¦2" FPTCondenser Inlet1¦2" FPT
3
¦4" FPTCondenser Outlet3¦8" FPT
3
¦8" ID Pipe
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled, Overflow Pipe
Water Regulator
Thermostat
Hermetic, Model CS14K6E-TF5
Water-cooled, Tube in Tube type
Vertical type, Stainless Steel and Copper
Thermostatic ExpansionValve
R404A, 2 lb. 2 oz. ( 950 g. )
High 427 PSIG, Low 230 PSIG
High Voltage Cut-out, Low Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
N/A
Ice Storage Bin
VOLTAGE RANGE187 - 253 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESS. 10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
9
6. KM-1300SRF3 (Remote air-cooled)
AC SUPPLY VOLTAGE
AMPERAGE
MINIMUM CIRCUIT AMPACITY
MAXIMUM FUSE SIZE
APPROX. ICE PRODUCTION REFERENCE
PER 24 HR.
lbs./day ( kg./day )
Reference without *marks
SHAPE OF ICE
ICE PRODUCTION PER CYCLE
APPROXIMATE STORAGE CAPACITY
ELECTRIC & WATER CONSUMPTION
ELECTRIC W ( KWH/100 lbs. )
WATER gal./24 HR. ( gal./100 lbs. )
EXTERIOR DIMENSIONS ( WxDxH )
EXTERIOR FINISH
WEIGHT
CONNECTIONS - ELECTRIC
- WATER SUPPLY
- DRAIN
CUBE CONTROL SYSTEM
HARVESTING CONTROL SYSTEM
ICE MAKING WATER CONTROL
COOLING WATER CONTROL
BIN CONTROL SYSTEM
COMPRESSOR
CONDENSER
¦8" x 273¦8" ( 1219 x 695 x 695 mm. )
Stainless steel, Galvanized Steel (Rear)
Net 255 lbs. ( 116 kg. ) Shipping 315 lbs. ( 143 kg. )
Permanent Connection
Inlet
1
¦2" FPT
Outlet 3¦4" FPT
3¦8" ID Pipe
Float Switch
Hot Gas and Water, Thermistor and Timer
Timer Controlled, Overflow Pipe
N/A
Thermostat
Hermetic, Model CS14K6E-TF5
Air-cooled remote, Condenser Unit URC-12F
recommended
Vertical type, Stainless Steel and Copper
Thermostatic Expansion Valve,
Condensing Pressure Regulator on URC-12F
R404A, 11 lbs. 7 oz. ( 5200 g. )
( Ice maker 7 lbs.; Cond. unit 4 lbs. 7 oz. )
HIGH 467 PSIG, LOW 230 PSIG
High Voltage Cut-out ( Internal )
Auto-reset Overload Protector ( Internal )
Auto-reset High Pressure Control Switch
Float Switch
N/A
Ice Storage Bin, Remote Condenser Unit
VOLTAGE RANGE 187 - 264 V
AMBIENT TEMP. 45 - 100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESS. 10 - 113 PSIG
10
7. CONDENSING UNIT
URC-12F
11
MODEL: URC-12F
SPECIFICATIONS
EXTERIOR
DIMENSIONS (W x D x H)
REFRIGERANT CHARGE
URC-12F
WEIGHT
CONNECTIONS
REFRIGERANT
ELECTRICAL
CONDENSER
HEAD PRESSURE CONTROL
AMBIENT CONDITION
Galvanized Steel
35 - 11/16” x 15-11/16” x 21-15/16”
(907.2 x 398 x 557.8 mm)
R404A 4 lbs. 7 oz. (2000 g)
Net 80 lbs. (36 kg)
Shipping 87 lbs. (39 kg)
One Shot Couplings (Aeroquip)
Permanent Connection
Air-cooled
Condensing Pressure Regulator
Min. -20°F - Max. +122°F
(-29°C to +50°C)
Outdoor use
12
II. GENERAL INFORMATION
1. CONSTRUCTION
[a] KM-1300SAF/3
13
[b] KM-1300SWF/3
14
[c] KM-1300SRF/3
15
2. CONTROLLER BOARD
[a] SOLID-STATE CONTROL
1) A HOSHIZAKI exclusive solid-state control is employed in KM-1300SAF,
KM-1300SWF, KM-1300SRF, KM-1300SAF3, KM-1300SWF3 and KM-1300SRF3
Stackable Crescent Cubers.
2) A Printed Circuit Board (hereafter called “Controller Board”) includes a stable and
high quality control system.
3) All models are pretested and factory-adjusted.
[b] CONTROLLER BOARD
CAUTION
1. Fragile, handle very carefully.
2. A controller board contains integrated circuits, which are susceptible to
failure due to static discharge. It is especially important to touch the
metal part of the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the
board to prevent damage to the board.
4. Do not change wiring and connections. Especially, never misconnect
K3, K4 and K5, because the same connector is used for the Thermistor
and Float Switch. K4 is not connected.
5. Do not fix the electronic devices or parts on the board in the field.
Always replace the whole board assembly when it goes bad.
6. Do not short out power supply to test for voltage.
16
KM-1300S_F/3 models use either the Alpine Controller Board (orange):
OR the Control Products Improved “E” Board (green):
PART NUMBERTYPE
2A1410-01 HOS-001A (Control Products - 10 Pin)
Features of All Three Controller Boards
(1) Maximum Water Supply Period - 6 minutes
Water Solenoid Valve opening, in the Defrost (Harvest) Cycle, is limited by
maximum period of the defrost timer. The Water Valve cannot remain open
longer than the maximum period. The Water Valve can close in less than the
maximum period if the defrost cycle is completed.
(2) Defrost Timer
The defrost cycle starts when the Float Switch opens and completes the
freeze cycle. But the Defrost Timer does not start counting until the Thermistor senses 48°F at the Evaporator outlet. The period from the end of the
freeze cycle up to the point of the Thermistor's sensing varies depending on
the ambient and water temperatures.
(3) High Temperature Safety - 127 ± 7°F
The temperature of the suction line in the refrigerant circuit is limited by the
High Temperature Safety.
During the defrost cycle the Evaporator temperature rises. The Thermistor
senses 48°F and starts the Defrost Timer. After the Defrost Timer counts
down to zero, the normal freeze cycle begins. If the Evaporator temperature
continues to rise, the Thermistor will sense the rise in temperature and at 127
± 7°F the Thermistor operates the High Temperature Safety.
17
This High Temperature Safety shuts down the circuit and the icemaker automatically stops. To reset the safety, turn the power off and back on again.
This High Temperature Safety protects the unit from excessive temperature.
(4) Low Water Safety
If the Pump Motor is operated without water, the mechanical seal can fail. To prevent this type of failure, the Controller Board checks the position of the Float Switch
at the end of the initial one minute water fill cycle and at the end of each defrost
cycle.
If the Float Switch is in the up position (electrical circuit closed), the Controller
Board changes to the ice making cycle. If the Float Switch is in the down position
(electrical circuit open), the Controller Board changes to a one minute water fill
cycle before starting the ice making cycle. This method allows for a Low Water
Safety shut down to protect the Water Pump from mechanical seal failure.
For water-cooled model, if the water is shut off, the unit is protected by the High
Pressure Switch.
(5) High Voltage Cut-out
The maximum allowable supply voltage of this icemaker is limited by the High
Voltage Cut-out.
If miswiring causes excessive voltage on the Controller Board, the High Voltage
Cut-out shuts down the circuit in 3 seconds and the icemaker automatically stops.
When the proper supply voltage is resumed, the icemaker automatically starts
running again.
18
Connector K1
Pins #1 through #10
#1, 9Magnetic Contactor
#2Hot Gas Valve
#3Line Valve
#4Pump Motor (icemaking)
#5Pump Motor (drain)
#6Water Valve
#7, 10 Power (line, Bin Control)
#8Open
The “E” board includes LED lights and audible alarm safeties. The red LED indicates proper control
voltage and will remain on unless a control voltage problem occurs. At startup a 5 second delay
occurs while the board conducts an internal timer check. A short beep occurs when the power
switch is turned ON or OFF.
The green LED’s 1-4 represent the corresponding relays and energize and sequence 5 seconds
from initial startup as follows:
Sequence StepLED’s onLength: Min.Max.Avg.
1 Minute Fill CycleLED460 sec.
Harvest CycleLED1, 4, & 22 min.20 min.3-5 min.
Freeze CycleLED15 min.60 min.30-35 min.
Reverse Pump OutLED1, 3, & 210 sec.20 sec.Factory set.
{LED 1 – Comp; LED 2 - HGV/CFM; LED 3 – PM; LED 4 - WV}
The built in safeties shut down the unit and have alarms as follows:
1 beep every 3 sec. = High Evaporator Temperature >127 ° F.
Check for defrost problem (stuck HGV or relay), hot water entering unit, stuck headmaster, or
shorted thermistor.
2 beeps every 3 sec. = Defrost Back Up Timer. Defrost >20 minutes.
Orange LED marked 20 MIN energizes.
Check for open thermistor, HGV not opening, TXV leaking by, low charge, or inefficient compressor.
3 beeps every 3 sec. = Freeze Back Up Timer. Freeze > 60 minutes.
Yellow LED marked 60 MIN energizes.
Check for F/S stuck closed (up), WV leaking by, HGV leaking by, TXV not feeding properly, low
charge, or inefficient compressor.
To manually reset the above safeties, depress white alarm reset button with the power supply ON.
6 beeps every 3 sec. = Low Voltage. Voltage is 92 Vac or less.
7 beeps every 3 sec. = High Voltage. Control voltage > 147Vac ±5%.
The red LED will de-energize if voltage protection operates.
The voltage safety automatically resets when voltage is corrected.
The Output Test switch “S3” provides a relay sequence test. With power OFF, place S3 on and
switch power to ICE. The correct lighting sequence should be none, 2, 3, 4, 1, & 4, normal sequence every 5 seconds. S3 should remain in the “OFF” position for normal operation.
The application switch located between relay X3 & X4 must be set to match the original board
application. Place this switch in the ALP position if there is no white wire supplied to the K1 connector. If there is a white wire, place the switch in the C position. If this switch is placed in the wrong
position either the compressor contactor will remain energized with the control switch OFF or the unit
will not start.
The dip switches should be adjusted per the adjustment chart published in the Tech Specs book. 7 &
8 must remain in the OFF position.
20
(Control Products HOSHIZAKI001 Board)
21
(Control Products HOS-001A Board)
22
[c] SEQUENCE
1st Cycle [KM-1300SAF/3, KM-1300SWF/3 and KM-1300SRF/3]
1. Unit energized and Control Switch to “ICE”
position. Water supply cycle starts.