· Housing (300) with terminal connection (IP 65), “blue” cable
entry and terminals.
· Also available with resistor combination for line break and
short-circuit monitoring (with isolating amplifier Ex 041).
Important:
All pressure switches with the ZF 5… additional functions listed here can only be operated in combination with a suitable
isolating amplifier (see pages 60 – 61).
Additional functions
for EEx-i equipment ZF 5…
DWAM…-576
Pressure switches
Mechanical pressure switches
Additional functions for EEx-i equipment Connection diagram Isolating amplifier
Gold-plated contacts, single-pole ZF 513 Ex 011
switching. Switching differential fixed (not adjustable).
Switching capacity: max. 24 VDC,
100 mA, min. 5 VDC, 2 mA.
Versions with resistor combination for line break and short-circuit monitoring in control current circuit, see DBS series, pages 54 – 56:
Normally closed contact with resistor combination ZF 576 Ex 041
for maximum pressure monitoring,
gold-plated contacts,
plastic-coated housing
(chemical version).
Normally closed contact with reclosing lockout ZF 577 Ex 041
and resistor combination,
for maximum pressure monitoring
Plastic-coated housing
(chemical version).
Normally closed contact with resistor combination ZF 574 Ex 041
for minimum pressure monitoring,
gold-plated contacts,
plastic-coated housing
(chemical version).
Normally closed contact with reclosing lockout ZF 575 Ex 041
and resistor combination,
for minimum pressure monitoring
Plastic-coated housing
(chemical version).
Other additional functions Plug connection Terminal connection
200 series 300 series
Adjustment according to customer’s instruction: one switching point ZF 1970* ZF 1970*
two switching points or defined switching differential ZF 1972* ZF 1972*
Adjustment and lead sealing according to customer’s instruction:
one switching point ZF 1971* –
two switching points or defined switching differential ZF 1973* –
Labelling of units according to customer’s instruction with sticker ZF 1978 ZF 1978
Special packing for oil and grease-free storage ZF 1979 ZF 1979
Documents: Additional documents, e.g. data sheets, operating instructions, TÜV, DVGW or PTB certificates.
Test certificates according to EN 10 204
Factory certificate 2.2 based on non-specific specimen test WZ 2.2 WZ 2.2
Acceptance test certificate 3.1 based on specific test AZ 3.1 AZ 3.1
Acceptance test certificate for ZFV separating diaphragms AZ 3.1 –V AZ 3.1 –V
*Switching point adjustment: Please specify switching point and direction of action (rising or falling pressure).
29
I
o
I
i
U
o
U
i
P
i
Non-Ex area Ex area
For ZF513, ZF576, ZF574:
Ui= 15 V DC, Ii= 60 mA,
P
i
= 0.9 W, Ci< 1 nF, Li< 100 µH