The purpose of this document is to provide a quick and easy way to program your entire system. A
recommended programming procedure is included, followed by a list of program fields with the corresponding
program group they belong to (system-wide, partition-specific, scheduling, etc.). Two program forms are
included. One contains all the programming fields, and the other contains the partition-specific fields. If you are
setting up a single-partition system, the partition-specific fields become system-wide fields.
Following the program forms are system layout worksheets. We recommend that you use these sheets to plan
your system before programming is performed. If you need further information about specific programming
options, see the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide.
Make sure that one two-line alpha keypad is connected to the control and is set to device address "00."
Single-Partition System
The system default is for a single-partition system. Use the VISTA-50P/VISTA-50PUL SINGLE PARTITION
PROGRAMMING FORM when programming for single-partition usage. Follow the steps outlined in
RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.
Multiple-Partition System
You must enter the number of partitions you are using in data field 2*00 to set the system for multiple
partitions. Use the VISTA-50P/VISTA-50PUL SINGLE PARTITION and the PARTITION-SPECIFIC
PROGRAM FORMS when programming the system for multiple partitions. Follow the steps outlined in
RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.
SUMMARY OF PROGRAMMING COMMANDS
• To enter program mode, enter installer code + [8] + [0] + [0]
• To set standard defaults, press ✱97
• To change to next page of program fields, press ✱94
• To return to previous set of fields, press ✱99
• To erase account and phone number field entries, press [✱] + field number + [✱]
• To assign zone descriptors, press #93 + follow menu prompts
• To add custom words, press #93 + follow menu prompts
• To enter Installer's Message, press #93 + follow menu prompts
• To exit program mode, enter ✱99 OR ✱98: ✱99 allows re-access to programming mode by installer code.
✱98 prevents re-access to programming mode by installer code.
Standard default (✱97) values are shown in brackets [ ], otherwise default = 0.
The following is a step-by-step procedure recommended for programming your VISTA-50P/VISTA-50PUL system.
1. Set the keypads (and other peripheral devices) to the appropriate addresses.
2. Set factory defaults by pressing
This will automatically enable keypad addresses 00-03, so be sure at least one keypad is set to one of these
addresses.
3. Program system-wide (global) data fields.
Using the programming form as a guide, enter program mode and program all system-wide programming
fields. These options affect the entire system, regardless of partitions. They include control options,
downloader and dialer options, RF options, event logging options, etc. Refer to the Program Field Index for a
listing of the program fields and their function.
Note that field 2
✱00 (number of partitions) must be programmed before continuing.
4. Program partition-specific fields.
When the system-wide fields have been programmed, program all partition-specific programming fields by
first pressing
specific field number
✱91 to select a partition (while still in data field program mode). Then enter the first partition-
✱09. When you are finished, the next partition-specific field is automatically displayed.
Partition-specific fields can have different values for each partition. To program the fields for the next partition,
press
✱91, enter the desired partition number, then enter field ✱09. Refer to the PROGRAMMING section in
the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed instructions.
5. Use #93 Menu Mode for device programming.
Refer to Device Programming in this guide to assign keypad ID numbers and default partitions for each
keypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RF
receivers, relay modules, the VIP module, the ECP Long Range Radio, and the VISTA Gateway Module.
6. Use #93 Menu Mode for zone programming.
Refer to Zone Programming in this guide to program zone response types, assign right loop zones and
wireless zones, assign zones to partitions, and to program alarm report codes.
7. Use #93 Menu Mode for programming outputs.
Refer to Output Programming in this guide to program desired output operation.
8. Program Communication options.
Refer to System Communication section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup
Guide for detailed instructions. Then use #93 menu mode to program report codes.
9. Use #93 Menu Mode for programming alpha descriptors.
Refer to Alpha Programming in this guide to enter zone and partition descriptors and a custom installer’s
message.
10.Use #93 Menu Mode for relay voice descriptors and custom word substitutes.
Refer to Relay Voice Descriptors in this guide for further instructions for programming relay descriptors to be
annunciated by the VIP module, as well as the Custom Index section for custom word substitutes.
11. Use #80 Mode for programming schedules.
Refer to the Scheduling Menu Prompts in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup
Guide to program open/close schedules, temporary and holiday schedules, limitation of access schedules,
and time-driven events.
12. Define user access codes.
Refer to User Access Codes in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide to
program authority level, O/C reporting option, partition assignments, and RF key assignments for each user.
13. Exit Programming Mode.
Exit programming mode by pressing either
being done from fields 1
✱00 and above.
To prevent re-access to programming mode using the Installer’s code, use
programming mode is by depressing both the [
up.
Exiting by using
✱99 always allows reentry into programming mode using the Installer code. Either way of
exiting allows access via downloading. Note that if local programming lockout is set via downloading,
programming mode cannot be entered at the keypad.
✱97.
✱98 or ✱99. Additional entries of ✱99 are required if the exit is
✱98. The only way to re-access
✱] and [#] keys at the same time within 30 seconds of power-
– 3 –
Program Field Index
On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the
fields on the programming form.
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ].
*00 INSTALLER CODE | | |
Enter 4 digits, 0-9 [4140]
*02 *05 RESPONSE TYPES FOR ZONES
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
*09 ENTRY DELAY #1 [02] |
00, 02-15 times 15 secondsMaximum "03" for UL.
*10 EXIT DELAY #1 [03] |
00, 03-15 times 15 secondsMaximum "04" for UL installations.
*11 ENTRY DELAY #2 [06] |
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for UL installations.
*12EXIT DELAY #2 [08] |
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for UL installations.
*13 ALARM SOUNDER DURATION [04] |
01-15 times 2 minutes. Must be minimum 16 minutes for UL
installations.
*14ZONE 9 RESPONSE TIME [0]
Enter 1 for fast response time 10ms
Enter 0 for normal response time 350ms.
Must be 0 for UL installations.
*15KEYSWITCH ASSIGNMENT [0]
Enter partition in which keyswitch used,
1-8; 0=disable
*16CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
Must be "1" for UL Installations.
*17AC LOSS KEYPAD SOUNDING [0]
1=yes; 0=no
*19 RANDOMIZE AC LOSS REPORT [0]
1=10-40 min; 0=normal report (about 2 min. after AC loss).
*20 VIP MODULE PHONE CODE | |
Enter 01 - 09 for the first digit; enter [00], [11]
11 for “*” or 12 for “#” for the second digit.
Must be set to "0" for UL installations.
*21 PREVENT FIRE TIMEOUT [0]
1=No timeout; 0=Timeout.
*22 KEYPAD PANIC ENABLES [001]
1=enable; 0=disable 995 996 999
*23MULTIPLE ALARMS [1]
1=yes; 0=no
*24IGNORE EXPANSION ZONE TAMPER [0]
1=Ignore; 0=Enable tamper for RF and RPMs.
Must be "0" for UL installations if using these devices.
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0]
1=yes (no report sent if any other report was recently sent);
0=no (send report at programmed interval, field *27)
Must be 0 for UL installations.
*27TEST REPORT INTERVAL [024] | | |
Enter interval in hours, 001-999; 0000=no report;
Max. 024 for UL installations.
*28 POWER UP IN PREVIOUS STATE [1]
1=yes; 0=no; "1" for UL installations.
*29QUICK ARM [1]
1=yes; 0=no
*30 TOUCHTONE OR ROTARY DIAL [0]
1=TouchTone; 0=rotary
*31 PABX ACCESS CODE | | | |
00-09; B-F (11-15)
*32PRIM. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*33 PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*34 SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*35DOWNLOAD PHONE NO.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
1=yes; 0=no If used with Spilt Reporting "1" option (1*34),
alarms and alarm restores go to both primary & secondary
numbers, while all other reports go to secondary only. If used
with Split Reporting "2" option, alarms and alarm restores go to
both, open/close and test messages go to secondary only,
while all other reports go to primary.
Default = 00 for all reports
*80 1st Digit *81 2nd Digit
Close
Open
Low Battery
Low Battery Restore
AC Loss
AC Restore
Test
Power Up
Cancel
Program Tamper
Enter 00-09; B-F (11-15).
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*83FIRST TEST REPORT TIME | | |
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-
59; 00 in all boxes = instant (Day 01= Monday)
*84 SWINGER SUPPRESSION [01] |
01-15 alarms
Must be "00" (disabled) for UL.
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
995
996
999
Duress
*87ENTRY WARNING [1]
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [0]
1=16 seconds; 0=no delay
Must be "0" for UL installations.
*89 RESTORE REPORT TIMING [0]
0=Instant; 1=After bell timeout if zone is restored; 2=when
system is disarmed. Must be "0" for UL installations.
*90 SEC. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Programming Fields (press *94)
1*01 1*09 ASSIGN RESPONSE TYPE FOR ZONES.
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
1*17 LOBBY PARTITION [0]
Enter the "common lobby" partition (1-8)
1*18 AFFECTS LOBBY [0]
Enter 1 if this partition affects the common lobby; enter 0 if it
does not.
Must be "0" for UL installations.
1*19 ARMS LOBBY [0]
Enter 1 if arming this partition attempts to arm lobby; enter 0
if it does not.
Must be "0" for UL installations.
1*20 EXIT ERROR LOGIC ENABLE [0]
0=No; 1=Bypass E/E and Interior zones faulted after exit
delay.
Must be "0" for UL installations.
1*21 EXIT DELAY RESET [0]
0=No; 1=Resets Exit Delay to programmed value after zone
is closed and then faulted prior to end of exit delay.
Must be "0" for UL installations.
FIELDS 1✳22-1✳25: Allow four sets of two zones each to be
linked so that both must fault within a five minute period to
cause an alarm. Default for these fields = [000], [000].
1*22 CROSS-ZONING PAIR ONE
1*23 CROSS-ZONING PAIR TWO
1*24 CROSS-ZONING PAIR THREE
1*25 CROSS-ZONING PAIR FOUR
MISCELLANEOUS WIRELESS OPTIONS
Fields 1*28 - 1*31 are not applicable for UL installations.
| |
| |
| |
| |
1*28 RF TX LOW BATTERY SOUND [0]
1=immediate; 0=when disarmed
1*29 RF TX LOW BATTERY REPORTING [0]
1=enable; 0=disable
1*30 RF RCVR CHECK-IN INTERVAL [06] |
02-15 times 2 hours; 00 disables supervision
1*31 RF XMITTER CHECK-IN INTERVAL [12] |
02-15 times 2 hours; 00 disables transmitter supervision
1*33 TOUCHTONE W/ROTARY BACKUP [0]
1=enable; 0=disable
1*34 COMM. SPLIT REPORTING [0]
0=no; 1=alarms and alarm restores primary, others secondary;
2=open/close, test secondary, others primary. See
comments if using with dual reporting.
1*35 1*38 ALARM REPORT CODES & ID DIGITS FOR
Skip these fields. Use #93 Menu Mode, Zone
ZONES 65-80.
Programming to program the report codes.
1*39 SUPERVISORY AND RESTORE CODES FOR
ZONES 65-80.
Enter 00-09; B-F (11-15).
Default = [00 00 00 00 00]
|
Alarm Rst
|
Trbl
|
Trbl Rst
|
Byp
– 7 –
7
51 for
|
Byp Rst
1*40 1*41NON-ALARM DIALER CODES
Default = 00 for all reports
1*40 1st Digit 1*41 2nd Digit
Armed STAY
Enter 00-09; B-F (11-15).
|
|
1*58 5800 RF BUTTON FORCE ARM [0]
Enter "1" to enable. If a zone is faulted after pressing button,
keypad will beep once. Pressing the button again within 4
sec. bypasses the zone. Enter "0" to disable.
Must be "0" for UL installations.
Time/Date Set or Event Log Reset
Event Log 50% & 90% Full
Event Log Overflow
Exit Error (Zone)
Exit Error (User)
Recent Close
|
|
|
|
|
|
|
|
|
|
|
|
1*42 CALL WAITING DEFEAT [0]
1=Yes; 0=No
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable When disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.
1*44 WIRELESS KEYPAD TAMPER [0]
DETECTION
1=enable; 0=disable.
Must be "0" for UL installations.
1*45 EXIT DELAY SOUNDING [0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
1*46 AUXILIARY OUTPUT MODE [0]
Enter 0 for ground start output.
Enter 1 for open/close trigger (is produced only if all partitions
are armed.
Enter 2 for keypad-like sounding. Applies to the partition
enabled in field *15.
Enter 3 if AAV module is being used.
NOTE: Only one of the above options may be active within
the system.
1*47 CHIME ON EXTERNAL SIREN [0]
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT [0]
0=disable; enter partition in which RF keypad used, 1-8.
Must be "0" for UL installations.
1*49 SUPPRESS TX SUPERVISION SOUND [1]
1=disable; 0=enable.
Must be "0" for UL installations.
1*52 SEND CANCEL IF ALARM + OFF [1]
1=no restriction; 0=within bell timeout period only
1*53 DOWNLOAD CALLBACK [0]
1=callback not required; 0=callback required.
Must be "0" for UL installations.
1*57 5800 RF BUTTON GLOBAL ARM [0]
1=enable; 0=disable
1*60 ZONE 5 AUDIO ALARM VERIFICATION [0]
Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is
not.
Must be "0" for UL installations.
1*69 PRINTER TYPE [0]
Enter 0 if you are using a parallel printer connected to the
VA8201 Alpha Pager Module.
Enter 1 if you are using a serial printer.
1*70EVENT LOG TYPES
[1 0 0 0 1]
1=enable; 0=disable
Alarm
Chk
Byp
O/C
Syst
1*71 12/24 HOUR TIME STAMP FORMAT [0]
0=12 hour; 1=24 hour
1*72 EVENT LOG PRINTER ON-LINE [0]
0=disable; 1=enable
1*73 PRINTER BAUD RATE [0] 1=300; 0=1200
1*74 RELAY TIMEOUT XXX MINUTES [000] | |
Enter the relay timeout, 000-127 in multiples of 2 minutes,
desired for #80 Menu Mode time-driven event relay
command numbers "04/09" and #93 Menu Mode Output
Programming output command "56."
1*75 RELAY TIMEOUT YYY SECONDS [000] | |
Enter the relay timeout, 000-127 seconds, desired for #80
Menu Mode time driven event relay command numbers
"05/10" and #93 Menu Mode Output Programming command
"57."
1*76ACCESS CONTROL RELAY [00] |
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-16; 00=none.
Must be "00" for UL.
3rd Page Programming Fields (press *94)
2*00
NUMBER OF PARTITIONS [1]
Enter 1-8
2*01 DAYLIGHT SAVING TIME [04, 10] | |
START/END MONTH Start End
00-12; if no daylight saving time, enter 00,00
2*02 DAYLIGHT SAVING TIME [1, 5] |
START/END WEEKEND Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last;
6=next to last; 7=3rd from last [1,5]
2*05 AUTO-ARM DELAY [15] |
Enter the time between the end of the arming window and
the start of auto-arming warning period, in values of 1-14
times 4 minutes 00=instant; [15=no auto arm at all]. When
this delay expires, the Auto-Arm Warning Period begins.
– 8 –
2*06AUTO-ARM WARNING PERIOD[15] |
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay.
2*07 AUTO-DISARM DELAY [15] |
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm.
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]
0=disable; 1=enable
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable
If enabled, only openings and closings occurring outside the
scheduled opening/closing windows will trigger dialer
reports. Opening reports will also be suppressed during the
closing window, in order to prevent false reports when the
user arms the system and then reenters the premises to
retrieve a forgotten item.
2*10 ALLOW DISARMING ONLY DURING [0]
ARMING/DISARMING WINDOWS
0=disable; 1=enable
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.
2*11 ALLOW DISARM OUTSIDE WINDOW [0]
IF ALARM OCCURS
Used only if field 2*10 (partition-specific field) is set to "1." If
this field is enabled ("1") the system can be disarmed outside
the disarm window if an alarm has occurred. If "0," disarming
can only be done during the disarm window. If field 2*10 is
set to "0" for a partition, this field has no effect for that
partition.
2*13 2*14SCHEDULING RELATED REPORT CODES
Default = 00 for all reports
2*13 1st Digit 2*14 2nd Digit
Enter 00-09; B-F (11-15).
2*18 ENABLE GOTO FOR THIS PARTITION [0]
1=Allow log-on from other partitions; 0=disable
2*19 USE PARTITION DESCRIPTORS [0]
0=disable; 1=enable
2*20 ENABLE J7 TRIGGERS FOR PARTITION [1]
0=disable for displayed partition; 1=enable for displayed
partition
2*21 ENABLE SUPERVISION PULSES FOR LRR
TRIGGER OUTPUTS [000]
Used for supervised connection to 7920SE. F B P
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary; P= Silent Panic/Duress.
Must be 1 for UL. Installations.
SUMMARY OF PROGRAMMING COMMANDS
• To enter program mode, enter installer code + [8] + [0] +
[0]
• To set standard defaults, press *97
• To change to next page of program fields, press *94
• To return to previous set of fields, press *99
• To erase account and phone number field entries,
press [*] + field number + [*]
• To assign zone descriptors, press #93 + follow menu
prompts
• To add custom words, press #93 + follow menu prompts
• To enter Installer's Message, press #93 + follow menu
prompts
• To exit program mode, enter *99 OR *98: *99 allows re-
access to programming mode by installer code. *98
prevents re-access to programming mode by installer
code.
| |
Early Opening
Early Closing
Late Opening
Late Closing
No Opening (late to open)
No Closing (late to close)
Auto-Arm Failure
Access Schedule Changed
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 9 –
Partition-Specific Fields
(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press *91 to select a partition.
2. Enter a partition-specific field number (ex. *09).
3. Make the required entry.
4. Repeat steps 1-3 for each partition in the system.
PARTITION #____ PROGRAM FIELDS
1st Page Fields
*09 ENTRY DELAY #1 [02] |
00, 02-15 times 15 seconds.
Maximum 03 for UL Listed installations.
*10 EXIT DELAY #1 [03] |
00, 03-15 times 15 seconds.
Maximum 04 for UL Listed installations.
*11 ENTRY DELAY #2 [06] |
00, 02-15 times 15 seconds.
Maximum 03 for UL installations.
*12EXIT DELAY #2 [08] |
00, 03-15 times 15 seconds.
Maximum 04 for UL installations.
*13 ALARM SOUNDER DURATION [04] |
01-15 times 2 minutes.
Must be minimum 16 minutes for UL installations.
*16CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
Must be "1" for UL installations.
*22KEYPAD PANIC ENABLES [001]
1=enable; 0=disable 995 996 999
*23MULTIPLE ALARMS [1]
1=yes; 0=no.
Must be 1 for UL installations.
*29QUICK ARM [1]
1=yes; 0=no
*32PRIM. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*38 PREVENT ZONE XX BYPASS [00] |
01-86; 000 if all zones (except fire zones) can be bypassed
*39 ENABLE OPEN/CLOSE REPORT [0]
FOR INSTALLER CODE
1=enable; 0=disable
*84 SWINGER SUPPRESSION [01] |
01-15 alarms;
Must be "00" (disabled) for UL installations..
*85ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
995
996
999
Duress
*87ENTRY WARNING [1]
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [0]
1=16 seconds; 0=no delay.
Must be "0" for UL installations. Must be “1” for SIA
*90 SEC. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Programming Fields (press *94)
1*18 AFFECTS LOBBY [0]
Enter 1 if this partition affects the common lobby; enter 0 if it
1*19
Enter 1 if arming this partition attempts to arm lobby; enter 0
1*20
Must be "0" for UL installations.
1*21
0=No; 1=Resets Exit Delay to programmed value after zone
Must be "0" for UL installations.
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable. When disabled, display lights when
1*45 EXIT DELAY SOUNDING [0]
1=enable; 0=disable. Produces quick beeping during exit
1*47 CHIME ON EXTERNAL SIREN [0]
1=enable; 0=disable
1*52 SEND CANCEL IF ALARM + OFF [1]
1=no restriction; 0=within Bell Timeout period only
1*76ACCESS CONTROL RELAY FOR PART.[00] |
Relay will be pulsed for 2 seconds whenever code + [0] is
Must be "00" for UL installations.
installations.
does not.
ARMS LOBBY [0]
if it does not
EXIT ERROR LOGIC ENABLE [0]
0=No; 1=Bypass E/E and Interior zones faulted after exit
delay.
EXIT DELAY RESET [0]
is closed and then faulted prior to end of exit delay.
any key is pressed, and turns off after period of keypad
inactivity.
delay if enabled.
pressed. Enter 00-16; 00=none.
– 10 –
3rd Page Programming Fields (press *94)
2*05AUTO-ARM DELAY [15] |
Enter the time between the end of the arming window and
the start of auto-arming warning period, in values of 1-14
times 4 minutes 00=instant; [15=no auto arm at all]. When
this delay expires, the Auto-Arm Warning Period begins.
2*06 AUTO-ARM WARNING PERIOD [15] |
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps
every 15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay .
2*07 AUTO-DISARM DELAY [15] |
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]
0=disable; 1=enable
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable If enabled, only openings and closings
occurring outside the scheduled opening/closing windows
will trigger dialer reports. Opening reports will also be
suppressed during the closing window, in order to prevent
false reports when the user arms the system and then reenters the premises to retrieve a forgotten item.
2*10 ALLOW DISARMING ONLY DURING [0]
ARMING/DISARMING WINDOWS
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.
0=disable; 1=enable
2*18 ENABLE GOTO FOR THIS PARTITION [0]
1=Allow log-on from other partitions; 0=disable
2*20 ENABLE J7 TRIGGERS BY PARTITION [1]
0=disable for displayed partition; 1=enable for displayed
partition
SUMMARY OF PROGRAMMING COMMANDS
• To enter program mode, enter installer code + [8] + [0] +
[0]
• To set standard defaults, press *97
• To change to next page of program fields, press *94
• To return to previous set of fields, press *99
• To erase account and phone number field entries,
press [*] + field number + [*]
• To assign zone descriptors, press #93 + follow menu
prompts
• To add custom words, press #93 + follow menu prompts
• To enter Installer's Message, press #93 + follow menu
prompts
• To exit program mode, enter *99 OR *98: *99 allows re-
access to programming mode by installer code. *98
prevents re-access to programming mode by installer
code.
– 11 –
Programming With #93 Menu Mode
NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should
be programmed via Device programming.
After programming all system related programming fields in the usual way, press #93 while still in programming mode to
display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu
selection. Pressing 0 will display the next choice in sequence.
#93 MENU MODE KEY COMMANDS
The following is a list of commands used while in the menu mode.
Menu selections are as follows:
PROMPT
ZONE PROG?
1 = YES 0 = NO 0
EXPERT MODE?
1 = YES 0 = NO 0
ALPHA PROG?
1 = YES 0 = NO 0
DEVICE PROG?
1 = YES 0 = NO 0
RELAY PGM?
1 = YES 0 = NO 0
RLY VOICE DESCR?
1 = YES 0 = NO 0
CUSTOM INDEX ?
1 = YES 0 = NO 0
#93 Enters Menu mode
[4] Serves as ENTER key. Press to have keypad accept entry.
[#] Backs up to previous screen.
0 Press to answer NO
1 Press to answer YES
01-09 All data entries are either 1-digit or 2-digit entries.
00 Exits menu mode, back into field programming mode, when entered at the first question for each category.
EXPLANATION
For programming the following:
• Zone Number
• Zone Response Type
• Partition Number for Zone
• Dialer report code for zone
• Input Device Type for zone (whether RF, polling loop, etc.)
• Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.
Same as Zone Programming except:
• Done with a minimum number of keystrokes.
• Can program wireless keys using pre-defined templates.
For entering alpha descriptors for the following:
• Zone Descriptors
• Installer's Message
• Custom Words
• Partition Descriptors
• Relay Descriptors
For defining the following device characteristics for addressable devices, including keypads, RF receivers
(5881), output relay modules (4204), and 4285/4286 VIP Module:
• Device Address
• Device Type
• Keypad Options (incl. partition assignment)
• RF House ID
For defining output relay functions.
For entering voice descriptors for relays to be used with the 4285/4286 VIP Module.
For creating custom word substitutes for VIP Module annunciation.
– 12 –
Zone Programming
ou are ready to enroll them. After enrolling
If using 5800 Series transmitters, do not the install batteries until y
the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.
PROMPT
ZONE PROG?
1 = YES 0 = NO 0
SET TO CONFIRM?
1 = YES 0 = NO 0
ENTER ZONE NO.
00 = QUIT 10
Zone 10 entered ↑
10 ZT P RC In L
00 1 10 00 1
10 ZONE TYPE
PERIMETER 03
Zone number 10 and Zone
Type 03 entry shown
† These are special zone
types used with 5800
Series Wireless
Pushbutton Units that
result in arming the system
in the STAY or AWAY
mode, or disarming the
system, depending on the
selection made.
10 Partition
1
10 REPORT CODE
1st 03 2nd 12 3C
EXPLANATION
Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [✱] to display the next
screen. Press # to display a previous screen.
This prompt appears once upon entering Zone Programming Mode.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been
entered later.
Enter the 2-digit zone number to be programmed, as follows:
Protection Zones = 01–86
System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97 and 98 (bell supervision)
Keypad Panic Zones = 95, 96, 99
Press [✱] to continue.
This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P =
Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the
sensor is connected.
Some devices can support more than one zone by means of individual loops (for example, 5801, 5804,
5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a
zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another
zone number, if desired.
Press [✱] to continue.
Each zone must be assigned a zone type, which defines the way in which the system responds to faults in
that zone. Refer to the Zone Type Definitions section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if
necessary). Available zone types are listed below.
00 = Assign for Unused Zones 08 = 24 Hr. Auxiliary
01 = Entry/Exit #1, Burglary 09 = Fire Without Verification
02 = Entry/Exit #2, Burglary 10 = Interior Delay, Burglary
03 = Perimeter, Burglary 20 = Arm–STAY†
04 = Interior Follower, Burglary 21 = Arm AWAY†
05 = Trouble Day/Alarm Night 22 = Disarm†
06 = 24 Hr. Silent Alarm 23 = No Alarm Response
07 = 24 Hr. Audible Alarm (e.g., relay activation)
Press [✱] to continue.
Enter the partition number (1–8) you are assigning this zone to.
Press [✱] to continue.
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."
(Refer to the System Communication section in the Installation and Setup Guide for more information about
report codes and reporting formats.)
Press [✱] to continue.
– 13 –
PROMPT
10 INPUT TYPE
RF Xmitter 3
Input types 4 & 5 are
valid for certain 5800
Series transmitters only
(e.g., 5801, 5802, 5802CP
& 5803).
10 INPUT S/N: L
AXXX-XXXX 1
10 INPUT S/N: L
A022-4064 1
10 INPUT S/N: L
A022-4064 1
EXPLANATION
Enter the input device type as follows:
00 = not used
01 = hardwired
03 = supervised RF transmitter (RF type)
04 = unsupervised RF transmitter (UR type)
05 = RF button-type transmitter (BR type)
06 = serial number polling loop device (SL type)
07 = DIP switch-type polling loop device
08 = right loop of DIP switch type device
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which
allow hardwired devices to be monitored by the polling loop.
If you are programming hardwired or DIP switch polling loop devices, the summary display appears after
completing this entry.
Press [✱] to continue.
For Serial Number entry and Loop Number entry, do one of the following:
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and
release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad.
Then press the [✱] key, the cursor moves to the “L” position. You can edit the loop number, if necessary.
When the loop number is acceptable, press [✱].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several
input loops).
Press [✱] to accept.
The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number
displayed.
Enter the loop number (refer to 5800 Series Transmitters Loop Designations below).
To Delete an Existing Serial Number, enter “0“ in the loop number field. The serial number will change to
“0”s.
If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to
the display.
Press [✱] to accept.
The system will then check for a duplicate serial/loop number combination.
If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display
the serial number along with a “?” for the loop number, allowing you to re-enter the correct loop number.
If the serial/loop number combination is not a duplicate in the system, a display appears showing the serial
number and loop number entry.
Press [✱] to continue.
– 14 –
5800 Series Transmitters Loop Designations
LOOP 3
LOOP 2
LOOP 1
LOOP 4
YOU MUST
ENROLL THIS
BUTTON
5801
ENROLL AS "UR" OR "RF"
5802MN
ENROLL AS "UR" OR "RF"
LOOP
1
ALTERNATE
POSITION
FOR LOOP 2
LOOP 2
(REED)
LOOP 1
(TERMINALS)
5816MN
ENROLL AS "RF"
LOOP 1
(PRIMARY)
LOOP 2
(AUX. CENTER)
LOOP 3
(AUX. RIGHT)
5817
ENROLL AS "RF"
YOU MUST
ENROLL THIS
BUTTON
LOOP 4
ENROLL AS "RF"
ENROLL AS "RF"
5809
5808
5804
ENROLL
AS "BR"
LOOP
1
LOOP
1
LOOP 3
LOOP 2
LOOP 1
LOOP 3
•
•
•
•
•
•
•
•
•
•
•
•
•
•••
•
•
•
5804BD
ENROLL AS "BR"
5816
ENROLL AS "RF"
LOOP 2
YOU MUST
ENROLL THIS
BUTTON
LOOP 4
LOOP 1
SET
HOUSE
CODE
LOOP 2
(REED)
LOOP 1
(TERMINALS)
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
SET HOUSE CODE
ENROLL AS "RF"
5819
5827
5850 (GBD)
(TERMINALS)
(Green)
(Red)
(Yellow)
LOOP 1
(TERMINALS)
LOOP 2
(REED)
LOOP 3
5819S (WHS & BRS)
ENROLL AS "RF"
5827BD
SET HOUSE CODE
ENROLL AS "RF"
5890
LOOP 1
(INTERNAL
SHOCK
SENSOR)
LOOP 1
(MOTION)
5800_trans_loop-V0
Note: For information on any transmitter not shown above, refer to the instructions accompanying that transmitter for
details regarding loop numbers, etc.
U
PROMPT
L
The 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, 5827BD,
and 5850 transmitters are not intended for use in UL installations.
XMIT TO CONFIRM
PRESS ✱TO SKIP
Entd A022-4063 1
Rcvd A022-4064
10 ZT P RC In L
03 1 3C RF 1s
EXPLANATION
Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system
enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate
the loop input or button that corresponds to this zone. At any time during this step, you may press the [✱] key
on the keypad to save the serial and loop number combination without confirming.
If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears. If the loop number does not match, it is also displayed.
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display does not appear), press the [#] key twice and then enter or transmit the correct serial number.
If the serial number transmitted does match the serial number entered, the system beeps 3 times and a
summary display appears, showing that zone’s programming. Note that an “s” indicates that a transmitter’s
serial number has been enrolled.
Press [✱] to accept the zone information.
– 15 –
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.