Honeywell VISTA-20PCN, VISTA-20P, VISTA-15P, VISTA-15PCN Programming Manual

9,67$39,67$3&1 9,67$39,67$3&1
3URJUDPPLQJ*XLGH
T
3
W
2
F
F
O
1
S S
A
P
Y
B
6
T
T
D
E
M
R
A
Y
D
A
E
R
5
M
4
M
I
H
C
9
D
O
C
8
T N A
T
S N I
7
#
0
Y
D A E
R
A
R
M
E
D
R
E
A
D
OFF
ON
Y
1
O
F
F
2
A
W
A
Y
3
S
T
A
Y
4
M
A
X
5
T
E
S
T
6
B
Y
P
A
S
S
7
IN
ST
A
N
T
8
C
O
D
E
9
C
H
I
M
E
R
E
A
D
Y
0
#
®
K5305-1PR 7/01
TO ENTER PROGRAMMING MODE:
Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
POWER UP, then depress
1.
] and [#]
[
both at once, within 50 seconds of powering up. OR Initially, key:
2.
Installer Code (4 + 1 + 1 + 2)
plus
8 + 0 + 0.
OR If different
3.
(if
Installer Code
98 was used to exit previously, method 1 above must be used to enter the program mode again)
is programmed, key:
New Installer Code + 8 + 0 + 0.
Data Field Programming Procedures
Task Procedure Go to a Data Field
Entering Data
Press [∗] + [Field Number], followed by the required entry. When the desired field number appears, simply make the required entry. When the last
entry for a field is entered, the keypad beeps three times and automatically displays the next data field in sequence. If the number of digits that you need to enter in a data field is less than the maximum digits available (for example, the phone number fields *41, *42), enter the desired data,
then press [∗]. The entry is terminated and the next data field number appears.
Review a Data Field
Press [#] + [Field Number]. Data will be displayed for that field number. No changes will be accepted in this mode.
Deleting an Entry
Press [∗] + [Field Number] + [∗]. (Applies only to fields ∗40–*43, *45, *94, and pager programming fields)
Interactive Mode Programming (∗56, *57, ∗58, ∗80, ∗81, ∗82)
Press
[✱] + [Interactive Mode No.]
requesting entries.
Interactive Mode Used to Program
56 Zone Programming Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
57 Function Key Programming Unlabeled keypad keys (known as ABCD keys) for special functions
58 Zone Programming Same options as *56 mode, but with fewer prompts. Intended for those familiar with
(Expert mode) this type of programming, otherwise *56 mode is recommended.
79 Output Device Mapping Assign module addresses and map individual relays/powerline carrier devices
✱ ✱
80 Output Programming 4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
81 Zone List Programming Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
82 Alpha Programming Zone alpha descriptors
(for example, ✱56). The alpha display keypad will display the first of a series of prompts
RF transmitters.
INITIALIZE DOWNLOAD and RESET DEFAULTS
Initializes download ID and subscriber account number.
96
Sets all data fields to original factory default values.
97
TO EXIT PROGRAMMING MODE:
Exits programming mode and
98
prevents
re-entry by:
Installer Code + 8
+ 0 + 0. If
is used to exit programming
98
mode, system must be powered down, and method 1 above used to enter the programming mode.
Exits programming mode and
99
allows
re-entry by:
Installer Code
+ 8 + 0 + 0 or method 1 above.
Special Messages
= OPEN CIRCUIT (no communication between Keypad and Control).
OC
or
EE
ENTRY ERROR
After powering up, This will revert to a “ delay by pressing
= ERROR (invalid field number entered; re-enter valid field number).
AC, dI
Ready
(disabled) or
Busy Standby
” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
and
NOT READY
will be displayed after approximately 4 seconds.
[#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. Correct the programming and then completely de-power and re-power the control to clear this indication and remove the disable indication.
– 2 –
352*5$00,1*)250
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults. Entries shown in dashed boxes indicate partition entries for VISTA-20P only (not applicable for VISTA-15P).
Field Function Data Entries Programmable Values
SYSTEM SETUP (✱20–✱29)
INSTALLER CODE
20
| | | [4112]
4 digits, 0–9
QUICK ARM ENABLE
21
RF JAM OPTION
22
FORCED BYPASS
23
RF HOUSE ID CODE
24
CHIME BY ZONE
26
27
X–10 HOUSE CODE
ACCESS CODE FOR
28
4285/4286 PHONE MODULE
LONG RANGE RADIO OUTPUT
29
ZONE SOUNDS AND TIMING (✱31 – ✱39)
ONE AUDIBLE ALARM PER ZONE
31
FIRE ALARM SOUNDER TIMEOUT
32
ALARM SOUNDER TIMEOUT
33
EXIT DELAY
34
ENTRY DELAY #1 (zone type 01)
35
ENTRY DELAY #2 (zone type 02)
36
AUDIBLE EXIT WARNING
37
CONFIRMATION OF ARMING DING
38
POWER UP IN PREVIOUS STATE
39
[0,0]
Part. 1 Part.2
[0]
[0,0]
Part. 1 Part. 2
| | |
Part. 1 Part. 2 Common
[0]
[0]
| [00]
(Partition 1 only)
[0]
[0]
[0]
[1]
| | [70,70]
Part. 1 Part. 2
| | [30,30]
Part. 1 Part. 2
| | [60,60]
Part. 1 Part. 2
[1,1]
Part. 1 Part. 2
[0,0]
Part. 1 Part. 2
[1]
0 = no; 1 = yes
0 = no RF Jam detection; 1 = send RF Jam report UL: must be 1 if wireless devices are used
0 = none UL: must be “0” 1 = bypass open zones
00 = disable all wireless keypad usage 01–31 = using 5827, 5827BD or 5804BD keypad [00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3, using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G, 7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N, #14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11 for "✱", or # + 12 for "#". UL: must be “00” for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be “0”
0 = sounder stops at timeout; 1 = no sounder timeout UL: must be “1” for fire install.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min; UL: minimum “1” (4 min.)
00–99 = seconds of exit delay time for each partition Common zones use same delay as partition 1.
00–99 = seconds of entry delay #1 time for each partition; UL: 45 seconds max. Common zones use same delay as partition 1.
00–99 = entry delay #2 time for each partition; UL: 60 seconds max. Common zones use same delay as partition 1.
0 = no; 1 = yes
0 = no; 1 = yes (wired keypads and RF) 2 = yes, RF only
0 = no; 1 = yes UL: must be “1”
; 1 = yes
DIALER PROGRAMMING (✱40 – ✱42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum digits entered, exit the field by pressing [✶] and next desired field number.
PABX ACCESS CODE
40
PRIMARY PHONE No.
41
SECOND PHONE No.
42
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱41
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱42
| | | | |
Enter up to 6 digits. To clear entries from field, press ✱40✱ .
.
.
– 3 –
NOTE: Entry of a number other than one specified will give unpredictable results.
For fields *43- *46:
reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999. Exit field by pressing digits are used. E.g., For Acct.
Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; [#+15 for F]. Enter
, enter: #+11| 2 | 3 | 4
B234
as the fourth digit if a 3-digit account number (for 3+1 dialer
[✱]
(and press next field number) if only 3
PARTITION 1 PRIMARY SUBS. ACCT. No.
43
PARTITION 1 SECONDARY SUBS. ACCT. No.
44
PARTITION 2 PRIMARY SUBS. ACCT. No.
45
PARTITION 2 SECONDARY SUBS. ACCT. No.
46
PHONE SYSTEM SELECT
47
REPORT FORMAT
48
SPLIT/DUAL REPORTING
49
15 SEC DIALER DELAY (BURG)
50
SECOA/RADIONICS SELECT
53
DYNAMIC SIGNALING DELAY
54
DYNAMIC SIGNALING PRIORITY
55
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (✱59 – ✱76, & ✱89):
For 3+1 or 4+1 Standard Format:
not
A 0 (
#+10) in the
For Expanded or 4+2 Format:
not
A 0 (
#+10) in the
For Ademco Contact ID® Reporting:
not
A 0 (
#+10) in the
first
second
first
Enter a code in the
box will disable a report. A 0 (
Enter codes in
box will eliminate the expanded message for that report. A 0 (
box disables the report.
Enter any digit (other than 0) in the
first
box: 1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
not
#+10) in the
both
boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
UL: see installation instructions for requirements
| | | [FFFF]
| | | [FFFF]
| | | [FFFF]
| | | [FFFF]
[1]
primary secondary
[0]
[0]
[0]
[0]
[0]
second
box will result in automatic advance to the next field.
first
box, to enable zone to report (entries in the
not
#+10) in
[70]
See box above for entries. To clear entries from field, press *43
See box above for entries. To clear entries from field, press *44*.
See box above for entries. To clear entries from field, press *45*.
See box above for entries. To clear entries from field, press *46*.
If Cent. Sta. 0=Pulse Dial; 1=Tone Dial; if Cent. Sta. 2 = Pulse Dial ; 3 = Tone Dial
0 = 3+1, 4+1 ADEMCO L/S STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 6 = 4+2 ADEMCO EXPRESS 7 = ADEMCO CONTACT ID® REPORTING 8 = 3+1, 4+1 ADEMCO L/S EXPANDED 9 = 3+1, 4+1 RADIONICS EXPANDED
0 = Disable (Backup report only)
Primary Phone No.
Phone No.
1 = Alarms, Restore, Cancel Others 2 = All except Open/Close, Test Open/Close,
3 = Alarms, Restore, Cancel All 4 = All except Open/Close, Test All 5 = All All
0 = no UL: must be “0”
0 = Radionics (0-9, B-F) 1 = SESCOA (0-9 only reporting) Select “0” for all other formats.
Delay selectable from 0 to 225 secs in 15-sec increments. 0 = no delay (both signals sent), 1 = 15 secs, 2 = 30 secs, etc. UL: must be “0”
0 = Primary Dialer first; 1 = Long Range Radio first.
both
boxes will disable the report.
second
*.
IS NOT
on a WATS line:
IS on
a WATS line:
; 1 = yes
boxes are ignored).
Second
Test
SYSTEM STATUS REPORT CODES (✱59–
EXIT ERROR REPORT CODE
59
TROUBLE REPORT CODE
60
BYPASS REPORT CODE
61
AC LOSS REPORT CODE
62
LOW BAT REPORT CODE
63
TEST REPORT CODE
64
OPEN REPORT CODE
65
ARM AWAY/STAY RPT CODE
66
68)
[0] See box above.
| [00] See box above.
| [00] See box above.
| [00] See box above.
| [00] See box above.
| [00] See box above. Use Scheduling mode to set periodic test reports.
[0,0,0] See box above.
Part. 1 Part. 2 Common
Away Stay Away Stay Away Stay
Part. 1 Part. 2 Common
– 4 –
[0,0,0,0,0,0]
See box above.
RF XMTR LOW BAT REPORT CODE
67
CANCEL REPORT CODE
68
RESTORE REPORT CODES (✱70 – ✱76)
ALARM RESTORE RPT CODE
70
TROUBLE RESTORE RPT CODE
71
BYPASS RESTORE RPT CODE
72
AC RESTORE RPT CODE
73
LOW BAT RESTORE RPT CODE
74
RF XMTR LO BAT RST RPT CODE
75
TEST RESTORE RPT CODE
76
| [00] See box on previous page.
UL: must be enabled if wireless devices are used
| [00] See box on previous page.
[0] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
UL: must be enabled if wireless devices are used
| [00] See box on previous page.
OUTPUT AND SYSTEM SETUP (✱77 – ✱93)
*
DAYLIGHT SAVINGS TIME
77
START\END MONTH
*
DAYLIGHT SAVINGS TIME
78
START\END WEEKEND
AUTO STAY ARM
84
CROSS ZONE TIMER
85
This option not for use in UL installations.
CANCEL VERIFY
86
MISC. FAULT DELAY TIME
87
(used with Configurable Zone Types “digit 6”)
EVENT LOG FULL REPORT CODE
89
EVENT LOG ENABLES
90
OPTION SELECTION
91
PHONE LINE MONITOR ENABLE
92
UL: see Inst. Instructions for requirements
No. OF REPORTS IN ARMED PERIOD
93
PER ZONE (Swinger Suppression)
| [4][10]
| [1][5]
[0]
[0]
[0]
[0]
| [00]
[3]
System messages are
NOTE:
logged when any non-zero selection is made.
[8]
[0,0]
[0]
0 = Disabled 1-12 = January-September (1 = Jan, 2 = Feb, etc) #+10 = October; #+11 = November; #+12 = December
0 = disabled, 1 = first, 2 = second, 3 = third 4 = fourth, 5 = last, 6 = next to last, 7 = third to last
0 = no, 1 = partition 1 only 2 = partition 2 only, 3 = both partitions
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min (assign cross zones on zone list 4, with *81 Menu mode)
0 = no, 1 = yes
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm zones when used in fire and/or UL burglar alarm installation
See box on previous page for report code entries.
0 = None; 1 = Alarm/Alarm Restore 2 = Trouble/Trouble Restore; 4 = Bypass/Bypass Restore; 8 = Open/Close. Restore”, and “Open/Close”, enter 9 (1 + 8); To select all, enter #15.
0 = None 4 = AAV UL: do not use AAV 8 = Exit Delay Restart Multiple choice example: for AAV (4) + Exit Delay restart (8) enter # + 12.
: 0 = disabled, 1-15 = 1 min - 15 min
Digit 1:
:
Digit 2
0 = Keypad display when line is faulted 1 = Keypad display plus keypad trouble sound 2 = Same as “1”, plus programmed output device STARTS. If either partition is armed, external sounder activates also. programmed to be STOPPED in field ✱80 or STOPPED by Code + # + 8 + output number.
0 = Unlimited Reports; 1 = 1 report; 2 = 2 reports UL: must be “0”
Example:
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14 = 14 min; #+15 = 15 min)
NOTE:
To select “Alarm/Alarm
Output Device must either be
– 5 –
DOWNLOAD INFORMATION (✱94, ✱95)
DOWNLOAD PHONE No.
94
RING COUNT FOR DOWNLOADING
95
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits, 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. Do not fill unused spaces. If fewer than 20 digits, exit field by pressing ✱ (and press 95, if entering next field). To clear entries from field, press ✱94✱. UL: downloading may be performed only if a technician is at the site.
PAGER OPTIONS 160-172
PAGER 1 PHONE No.
160
PAGER 1 CHARACTERS
161
PAGER 1 REPORTING OPTIONS
162
PAGER 2 PHONE No.
163
| | | | | | | | | | | | | | | | | | | Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
| | | | | | | | | | | | | | | | | | | Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
[15]
Do not enter “0” if using
NOTE:
4285/4286 Phone Module.
| | | | | | | | | | | | | | | Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
Part. 1 Part. 2 common [0,0,0]
0 = Disable Station Initiated Download; 1–14 = number of rings (1–9, # +10 =10, # +11 =11, # +12 =12, # +13 =13, # +14 =14); 15 = answering machine defeat (# +15 =15).
For each partition, select from the following options: 0 = no reports sent 1 = Open/closes all users 4 = All alarms and troubles 5 = All alarms / troubles, and open/closes for all users 12 = Alarms / troubles for zones entered in zone list 9 13 = Alarms / troubles for zones entered in zone list 9,
and open\closes for all users
PAGER 2 CHARACTERS
164
PAGER 2 REPORTING OPTIONS
165
PAGER 3 PHONE No. | | | | | | | | | | | | | | | | | | |
166
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 3 CHARACTERS | | | | | | | | | | | | | | |
167
PAGER 3 REPORTING OPTIONS
168
PAGER 4 PHONE No. | | | | | | | | | | | | | | | | | | |
169
PAGER 4 CHARACTERS | | | | | | | | | | | | | | |
170
PAGER 4 REPORTING OPTIONS
171
PAGER DELAY OPTION FOR ALARMS
172
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
| | | | | | | | | | | | | | | Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
[0,0,0]
Part. 1 Part. 2 common
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
0,0,0] Part. 1 Part. 2 common
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
[0,0,0] Part. 1 Part. 2 common
[3]
See field *162 for reporting options. Select for each partition (use zone list 10 if using options 12 or 13).
See field *162 for reporting options. Select for each partition (use zone list 11 if using options 12 or 13).
See field *162 for reporting options. Select for each partition (use zone list 12 if using options 12 or 13).
0 = none, 1 = 1 minute, 2 = 2 minutes, 3 = 3 minutes This delay is for ALL pagers in the system.
The delay does not reset for new alarms
NOTE:
occurring while an existing pager delay is in progress.
REPORTING OPTIONS
CLEAN ME REPORTING OPTIONS
174
(for ESL smoke detectors)
DEVICE DURATION 1, 2
177
(used in *80 Menu mode-Device Actions 5/6)
[0]
[0] [0]
1 2
0 = disable; 1 = Clean Me signal reports;
Note:
If Clean Me is enabled, you must enter “3” in
field ✱56 programming for zone 1 response time. 0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min
1 = 30 seconds 7 = 3 min #+12 = 8 min 2 = 45 seconds 8 = 4 min #+13 = 10 min 3 = 60 seconds 9 = 5 min #+14 = 12 min 4 = 90 seconds #+10 = 6 min #+15 = 15 min 5 = 2 minutes
– 6 –
SYSTEM OPTIONS *180-*181
50/60 HERTZ AC OPERATION
181
CONFIGURABLE ZONE TYPE 90
182
ZONE TYPE 90 REPORT CODES
183
IMPORTANT:
codes, if appropriate, or define unique codes in CID code range 750-789. See important note in installation instructions.
CONFIGURABLE ZONE TYPE 91
184
ZONE TYPE 91 REPORT CODES
185
IMPORTANT:
codes, if appropriate, or define unique codes in CID code range 750-789. See important note in installation instructions.
Use existing Contact ID®
Use existing Contact ID®
[0]
12345678910 Make the appropriate entry for each digit, 1-10, based on the charts provided on the next page. Each digit’s entry is the sum of the values of its selected options (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15). UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
90 ALARM ID: XXX TROUBLE ID: XXX
12345678910 Make the appropriate entry for each digit, 1-10, based on the charts provided on the next page. Each digit’s entry is the sum of the values of its selected options (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15). UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
91 ALARM ID: XXX TROUBLE ID: XXX
0 = 60 Hz; 1 = 50 Hz
Enter the desired 3-digit Contact ID® report codes for alarms and troubles occurring on zones assigned to this zone type. Enter the codes sequentially (all 6 digits). When entering digits, [#] moves cursor back, [∗] moves forward. Press [∗] when done to continue.
Enter the desired 3-digit Contact ID® report codes for alarms and troubles occurring on zones assigned to this zone type. Enter the codes sequentially (all 6 digits). When entering digits, [#] moves cursor back, [∗] moves forward. Press [∗] when done to continue.
KEYPAD OPTIONS *190-*196 (
NOTE:
Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results.
KEYPAD 2 ADDRESS 17
190
KEYPAD 3 ADDRESS 18
191
KEYPAD 4 ADDRESS 19
192
KEYPAD 5 ADDRESS 20
193
KEYPAD 6 ADDRESS 21
194
KEYPAD 7 ADDRESS 22
195
KEYPAD 8 ADDRESS 23
196
EXIT TIME DISPLAY INTERVAL
197
: Options for keypad address 16 are set by the factory and cannot be changed.)
NOTE
[0] [0]
Partition/ Sound Enable VISTA-20P: enter partition VISTA-15P: 1 = enable
[0] [0]
Part./Enable
[0] [0]
Part. /Enable
[0] [0]
Part. /Enable
[0] [0]
Part. /Enable
[0] [0]
Part. /Enable
[0] [0]
Part. /Enable
[0]
0 = disable
Sound
Sound
Sound
Sound
Sound
Sound
Partition: 0 = keypad disabled; 1-3 = part. no. (3 = com) Sound: 0 = no suppression
1 = suppress arm/disarm and E/E beeps 2 = Suppress chime beeps only 3 = suppress arm/disarm, E/E, and chime
beeps
See field ∗190 for entries. † VISTA-20P: enter partition VISTA-15P: 1 = enable; 0 = disable
See field ∗190 for entries. † VISTA-20P: enter partition VISTA-15P: 1 = enable; 0 = disable
See field ∗190 for entries. † VISTA-20P: enter partition VISTA-15P: 1 = enable; 0 = disable
See field ∗190 for entries. † VISTA-20P: enter partition VISTA-15P: 1 = enable; 0 = disable
See field ∗190 for entries. † VISTA-20P: enter partition VISTA-15P: 1 = enable; 0 = disable
See field ∗190 for entries. † VISTA-20P: enter partition VISTA-15P: 1 = enable; 0 = disable
0 = no display; 1-5 = seconds between display refresh
DISPLAY PARTITION NUMBER
198
(for Alpha Display Keypads) ECP FAIL DISPLAY
199
[0]
[0]
0 = no; 1 = yes (partition no. appears on Alpha Display)
0 = 3-digit display (“1” + device address) 1 = 2-digit fixed-display as “91”
– 7 –
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves entering 10 digits in data field *182 for zone type 90 and field *184 for zone type 91, where each digit represents the sum of the values of its various options as shown in the tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
DIGIT 1
(See note 5 for RF zones)
DIGIT 2
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault
(See note 5 for RF zones)
Shorted
Auto
Restore Vent Zone
0 = no 4 = yes
0 = no 8 = yes
Digit 1 = EOL + Open Digit 2 = Short + auto restore + vent zone
DIGIT 3
(See note 5 for RF zones)
DIGIT 4
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault
(See note 5 for RF zones)
Shorted
Byp. when
disarmed
0 = no 4 = yes
Byp. when
armed
0 = no 8 = yes
Digit 3 = EOL + Open Digit 4 = Short + byp. disarmed + byp. armed
DIGIT 5
(See note 5 for RF zones)
DIGIT 6
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault
(See note 5 for RF zones)
Shorted
Dial Delay
(see field *50)
0 = no 4 = use delay
Fault Delay
(see field *87)
0 = no 8 = use delay
see note 1
Digit 5 = EOL + Open Digit 6 = Short + dial delay + fault delay
DIGIT 7 DIGIT 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed & disarmed
1 = don’t show
alarms when armed
alarms, trbles, faults when disarmed)
(show
0 = no 4 = power reset
after fault
(by code + OFF)
12 = verification
(see zone type 16)
3 = never show
any alarms,
trbles, faults Digit 7 = fault display + power reset/verification
Use Entry
Delay 1/2
0 = no 1 = delay 1 2 = delay 2
Use Exit
Delay
0 = no 4 = use exit
delay
Respond as
Interior Type
0 = no 8 = yes
see note 2
Digit 8 = entry delay 1/entry delay 2 + exit delay + interior zone type
DIGIT 9 DIGIT 10
Alarm Sounds Use Bell
Timeout
0 = none 1 = steady
0 = no 4 = yes
keypad 2 = steady bell
and keypad
see fields *32, *33
3 = pulsing bell
and keypad Digit 9 = alarm sounds + bell timeout + fire zone Digit 10 = trouble sounds + chime
Respond as
Fire Zone
0 = no 8 = yes
see zone type 09; see note 4
Trouble Sounds
0 = none 1 = periodic
beep
2 = trouble
beeps
Chime when
Chime Mode On
0 = no 4 = yes
Entries for Fields *182 and *184
Digit Zone Type 90 Zone Type 91
(field *182) (field *184)
1 2 3 4 5 6 7 8 9 10
To calculate each digit’s entry:
Simply add the values of the selected options in each of the digit’s columns (one option per column). For example, to program Digit 2 for “alarm response to short,” “auto restore on,” but not a “vent zone,” enter 5 (“1” for alarm short + “4” for auto restore yes + “0” for vent zone no).
OPEN SHORTEDINTACT
EOL
Zone Conditions Represented
in Digits 1-6
NOTES:
1. Do not use the “fault delay” option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur.
2. To create an interior type zone, select “respond as interior zone type” (Digit 8, interior type = yes), and set zone response to “fault” in digits 3-4 to ensure fault displays; do not set as “normal,” “alarm,” or “trouble.”
3. Do not set fire zones to respond as a “fault” (digits 1-6), otherwise faults will not display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or unpredictable results may occur.
5. RF Zones: The “open” option in digits 1, 3, and 5 is not applicable for RF zones. Use the “intact EOL” option for normal RF zone conditions and “shorted” for off­normal RF zone conditions.
6. Zone-Doubling/Double-Balanced: A short on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition.
-018-V0
– 8 –
Reserved Zones
addressable
91 =
device report enable/disable default zone type = [05].
Duress report
92 =
enable/disable
*56 ZONE PROGRAMMING WORKSHEET
Zone Zn Type Part. Report Input Type Loop Rsp. Time Serial No. Location
1 2 3 4 5 6 7 8
[09] [1] [HW] [1] [01] [1] [HW] [1] [03] [1] [HW] [1] [03] [1] [HW] [1] [03] [1] [HW] [1] [03] [1] [HW] [1] [03] [1] [HW] [1] [03] [1] [HW] [1]
(VISTA-15P supports up to 32 zones: 1-6, 9-34) [default shown in brackets]
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 95 96 99
NOTES:
64); Response Time: 0 (10msec), 1 (350msec), 2 (700msec), 3 (1.2 sec)
[00] N/A N/A N/A N/A [00] N/A N/A N/A N/A keypad [3] / [#] [06] N/A N/A N/A N/A
Zone Type: see chart on page 12; Input Type: HW (1-zones 1-8), AW (2-zones 9-48), RF (3-zones 1-48), UR (4-zones 1-48), BR (5-zones 49-
[1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR] [1] [BR]
keypad [1] / [∗]
keypad [∗] / [#]
– 9 –
*57 FUNCTION KEY PROGRAMMING
Option Function A B C D Comments
01 Paging 02 Time Display 03 Arm AWAY 04 Arm STAY 05 Arm NIGHT-STAY 06 Step Arming 07 Device Activation Device: 08 Comm. Test 09 Macro Key 1 10 Macro Key 2 11 Macro Key 3 12 Macro Key 4 00 Emergency Keys:
Personal Emergency Silent Alarm Audible Alarm Fire Emergency Keys: A = [1] / [∗]B = [∗] / [#] C = [3] / [#]
OUTPUT RELAYS/POWERLINE CARRIER DEVICES WORKSHEET FOR
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
79 RELAY/POWERLINE CARRIER DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE OUTPUT TYPE
Relay X10 Relay X10 Output No. 01 09
02 10 03 11 04 12 05 13 06 14 07 15 08 16
Module Addr.
Pos
(1-4)
Unit No.
Description
Output No.
17 18
Module Addr.
On-Board Trigger 1 On-Board Trigger 2
Pos
(1-4)
∗79,
80 and ∗81.
(09-16 apply to VISTA-20P only)
Unit
Description
No.
81 ZONE LISTS FOR OUTPUT DEVICES
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence.
Note:
Record desired zone numbers below, noting that a list may include
List No. Used For… Contains These Zones…
01 02 03 04 05 06 07 08 09 10 11 12
General Purpose (GP) General Purpose Chime-by-Zone or GP Cross Zones Night-Stay Zones or GP General Purpose General Purpose General Purpose Zones activating pager 1 Zones activating pager 2 Zones activating pager 3 Zones activating pager 4
– 10 –
any
or
of system's zone numbers.
all
80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number (V20P=1-48) (V15P=1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary 01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch 02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide 90-93 = Configurable 03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 04 = Interior Follower 09 = Fire 23 = No Alarm Response
Choices for System Operation are:
20 = Arming–Stay 38 = Chime 52 = Kissoff 21 = Arming–Away 39 = Any Fire Alarm 54 = Fire Zone Reset 22 = Disarming (Code + OFF) 40 = Bypassing 58 = Duress 31 = End of Exit Time 41 = **AC Power Failure 60 = AAV Trigger 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key† 33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure 36 = **At Bell Timeout*** 68 = TELCO Line Fault
Activated by 0=delete 1=zn list 2=zn type 3=zn no.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Activation Type and Detail Event (for zone list/activated by)Output
Zone List
1-8 = list
(ZL)
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN) 00=none 01-64
Partition
Number
(P)
(if using ZT trig)
0 = any 1 = partition 1 2 = partition 2 3 = common
78 = keyswitch red LED††† 79 = keyswitch green LED†††
By Zone List
0 = restore 1 = alarm 2 = fault 3 = trouble
Action
By Zone No.
0 = restore 1 = alrm/flt/trbl
** Use 0 (any) for Partition No. (P) entry. *** Or at Disarming, whichever occurs earlier. † Use *57 Menu mode to assign the function key. †† Duration is set in program field *177. ††† Device action not used for these choices.
0 = off 1 = close 2 secs 2 = stay closed 3 = pulse 4 = toggle 5 = duration 1 6 = duration 2
In normal operation mode:
Note:
Code + # + 7 + NN Key Entry Code + # + 8 + NN Key Entry
Output
Number
V20P=1-18
V15P=1-8, 17, 18
†† ††
starts
stops
Device
Type
R = relay T = trigger X = X10
Device
Device
– 11 –
Zone Type Definitions
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
Type 02
Entry/Exit Burglary #2
Type 03
Perimeter Burglary
Type 04
Interior Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Fire
Type 10
Interior w/Delay
Type 12
Monitor Zone
Type 14
Carbon Monoxide
Type 16
Fire w/Verification
Type 20
Arm-Stay
Use this zone type if the zone is not used.
Assign to zones that are used for primary entry and exit.
Provides entry delay if the control is armed in the Away or Stay modes.
No entry delay is provided when the panel is armed in the Instant mode.
Entry delay #1 is programmable from 0 to 99 seconds for each partition.
Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable from 0 to 99 seconds (field ✱34).
Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
Provides a secondary entry delay, in same manner as entry delay #1.
Entry delay #2 is programmable from 0 to 99 seconds for each partition.
Exit delay is same as described for Type 01.
Assign to all sensors or contacts on exterior doors and windows.
Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, or Instant
modes.
Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.
Active when the panel is armed in the Away mode.
Bypassed automatically when the panel is armed in the Stay or Instant modes.
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering
a sensitive area such as a stock room, drug supply room, etc.
Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
Provides an instant alarm if faulted when armed in the Away, Stay, or Instant (night) modes.
During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
Usually assigned to a zone containing an emergency button.
Sends a report to the central station but provides no keypad display or sounding.
Assign to a zone that has an emergency button.
Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external
alarm.
Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as
water or temperature sensors.
Sends a report to the central station and provides an alarm sound at the keypad.
provided.)
Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
This zone type is always active and cannot be bypassed.
Note:
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away
Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
Bypassed when the panel is armed in the Stay or Instant modes.
Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "
The “check” message will automatically disappear from the keypad. The zone restores dynamically;
Faults of this zone type are independent of the system, and can exist at the time of arming without
Assigned to any zone with a carbon monoxide detector.
The bell output will pulse when this zone type is alarmed.
Always active and cannot be bypassed.
Provides a fire alarm when zone is shorted, but only after alarm verified.
System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
Provides a trouble response when zone is open.
Arms the system in Stay mode when the zone is activated.
Pushbutton units send the user number to the central station when arming or disarming.
User code for button must be assigned.
Only hardwired zone 1 should be programmed as a fire zone, where 2-wire smoke detectors can be connected. However, any wireless zone can be used as a fire zone.
mode.
delay zone was tripped first.
24 Hr. Non-Burg. -#XXX
system keypad will display a “check” message indicating the appropriate zone. Upon restoral of the zone, the message, "
therefore a user code + off sequence is not needed to reset the zone.
interference. Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
within 90 seconds triggers fire alarm.
UL: may not be used on zone 1.
RESTORE-24 Hr. Non-Burg. -#XXX
" (where XXX is the zone number) will be sent to the Central Station. The
" will be sent to the Central Station.
(No bell output is
ALARM-
– 12 –
Type 21
Arm-Away
Type 22
Disarm
Type 23*
No Alarm Response
Type 24
Silent Burglary
Type 77
Keyswitch
Types 90-93
Installer Defined
*
The system can still be armed when these zone types are in a faulted condition.
Arms the system in Away mode when the zone is activated.
Pushbutton units send the user number to the central station when arming or disarming.
User code for button must be assigned.
Disarms the system when the zone is activated.
User code for button must be assigned.
Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, or Instant, modes.
A report is sent to the central station.
Assign to zone wired to a keyswitch.
These zone types can be programmed for various custom responses. See data fields *182-*185. UL: Zone types 90-93 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
Schedules
events 00-07 for both controls; VISTA-15P supports up to 8 schedules, VISTA-20P supports up to 32 schedules
(installer code + [#] + [6] [4];
master code can only access schedules 01-16 for VISTA-20P, 01-04 for VISTA-15P, and
)
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events:
enter 01-18 enter 1-8 enter 1, 2, or 3
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Events: Master/Installer Installer Only
01 = device on/off 05 = forced AWAY arm 10 = display custom words 8-10 02 = user access 06 = auto disarm 11 = peridoic test report 03 = latch key report 07 = display “reminder” 04 = forced STAY arm
Days Days
(yes/no) (yes/no)
– 13 –
(Word Space)
000
– A –
•001 AIR
• 002 ALARM
004 ALLEY 005 AMBUSH
• 006 AREA
• 007 APARTMENT
• 009 ATTIC
010 AUDIO
– B –
• 012 BABY
• 013 BACK
• 014 BAR
• 016 BASEMENT
• 017 BATHROOM
•018 BED
• 019 BEDROOM
020 BELL
•021 BLOWER
•022 BOILER
023 BOTTOM 025 BREAK
• 026 BUILDING – C –
028 CABINET
• 029 CALL
030 CAMERA 031 CAR 033 CASH 034 CCTV 035 CEILING 036 CELLAR
• 037 CENTRAL
038 CIRCUIT
• 040 CLOSED
• 046 COMPUTER
047 CONTACT
– D –
• 048 DAUGHTERS
049 DELAYED
•050 DEN
051 DESK
• 052 DETECTOR
• 053 DINING
054 DISCRIMINATOR 055 DISPLAY
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
• 057 DOOR
• 059 DOWN
• 060 DOWNSTAIRS
061 DRAWER
• 062 DRIVEWAY
• 064 DUCT – E –
• 065 EAST
066 ELECTRIC 067 EMERGENCY 068 ENTRY
• 069 EQUIPMENT
• 071 EXIT
072 EXTERIOR
– F –
• 073 FACTORY
075 FAMILY
• 076 FATHERS
• 077 FENCE
•079 FIRE
• 080 FLOOR
081 FLOW 082 FOIL
• 083 FOYER
084 FREEZER
•085 FRONT – G –
• 089 GARAGE
•090 GAS
091 GATE
•092 GLASS
093 GUEST 094 GUN
H –
• 095 HALL
• 096 HEAT
098 HOLDUP 099 HOUSE 100 INFRARED
•101 INSIDE
102 INTERIOR 103 INTRUSION
– J –
104 JEWELRY
– K –
• 105 KITCHEN
• 106 LAUNDRY
– L –
• 107 LEFT
108 LEVEL
• 109 LIBRARY
• 110 LIGHT
111 LINE
• 113 LIVING
• 114 LOADING
115 LOCK 116 LOOP 117 LOW
• 118 LOWER – M –
• 119 MACHINE
121 MAIDS 122 MAIN
• 123 MASTER
• 125 MEDICAL
126 MEDICINE 128 MONEY 129 MONITOR
• 130 MOTHERS
• 131 MOTION
132 MOTOR
– N –
• 134 NORTH
135 NURSERY
– O –
• 136 OFFICE
• 138 OPEN
139 OPENING
• 140 OUTSIDE
142 OVERHEAD
– P –
143 PAINTING
• 144 PANIC
145 PASSIVE
• 146 PATIO
147 PERIMETER
• 148 PHONE
150 POINT 151 POLICE 152 POOL
• 153 POWER
• 156 REAR
•161 RIGHT
• 162 ROOM
• 167 SERVICE
• 168 SHED
•170 SHOP
•173 SIDE
•176 SMOKE
•178 SONS
•179 SOUTH
•182 STATION
• 185 STORAGE
• 199 TEMPERATURE
• 201 TOOL
•205 UP
• 206 UPPER
• 207 UPSTAIRS
• 208 UTILITY
– R –
155 RADIO
157 RECREATION 159 REFRIGERATION 160 RF
163 ROOF
– S –
164 SAFE 165 SCREEN 166 SENSOR
169 SHOCK
171 SHORT
174 SKYLIGHT 175 SLIDING
180 SPRINKLER
184 STORE
186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 193 SWITCH
– T –
194 TAMPER 196 TELCO 197 TELEPHONE
200 THERMOSTAT
202 TRANSMITTER
– U –
• 216 WEST
• 217 WINDOW
• 219 WING
• 225 ZONE
• 226 0
• 227 1
• 228 1ST
• 229 2
• 230 2ND
• 231 3
• 232 3RD
• 233 4
• 234 4TH
• 235 5
• 236 5TH
• 237 6
• 238 6TH
• 239 7
• 240 7TH
• 241 8
• 242 8TH
• 243 9
• 244 9TH
– V –
209 VALVE 210 VAULT 212 VOLTAGE
– W –
213 WALL 214 WAREHOUSE
220 WIRELESS
– X –
222 XMITTER
– Y –
223 YARD
– Z –
224 ZONE (No.)
245 Custom Word #1 246 Custom Word #2 247 Custom Word #3 248 Custom Word #4 249 Custom Word #5 250 Custom Word #6 251 Custom Word #7 252 Custom Word #8 253 Custom Word #9 254 Custom Word #10
Note:
32 (space) 33 ! 34 " 35 # 36 $ 37 % 38 & 39 ' 40 (
Bulleted (•) words in
boldface type
are those that are also available for use by the 4285/4286 Phone Module. If using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
CHARACTER (ASCII) CHART (For Adding Custom Words)
41 ) 42 * 43 + 44 , 45 – 46 . 47 / 48 0 49 1
50 2 51 3 52 4 53 5 54 6 55 7 56 8 57 9 58 :
59 ; 60 <
61 = 62 > 63 ? 64 @ 65 A 66 B 67 C
68 D 69 E 70 F 71 G 72 H 73 I 74 J 75 K 76 L
77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V
87 W 88 X 89 Y 90 Z
– 14 –
5800 Series Transmitter Input Loop Identification
• All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
of the inputs requires its own programming zone
• Transmitter inputs entered as:
"RF" (Supervised RF) Type
signals, as well as fault, restore and low battery signals. The transmitter must remain within the receiver's range.
“UR" (Unsupervised RF) Type
the "RF" Type does, but the control does not supervise the check-in signals. The transmitter may, therefore, be carried off-premises.
"BR" (Unsupervised Button RF) Type
signals. They do not send restore or check-in signals. They will indicate a low battery condition when tested or activated normally. The transmitter may be carried off­premises.
: For information on any transmitter not shown
Note
above, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc
UL NOTE:The 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, 5827BD, and 5850 transmitters are not intended for use in UL installations
send periodic check-in
send all the signals that
only send fault
(e.g., a 5804's four inputs require four programming zones).
LOOP 3
LOOP 2
LOOP 1
LOOP 4 YOU MUST ENROLL THIS BUTTON
5801
ENROLL AS "UR" OR "RF"
YOU MUST ENROLL THIS BUTTON
LOOP 4
5804
ENROLL
AS "BR"
.
ENROLL AS "RF"
5808
ENROLL AS "RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 3
LOOP
1
5809
LOOP
1
5802MN
ENROLL AS "UR" OR "RF"
5804BD
ENROLL AS "BR"
5816
ENROLL AS "RF"
ENROLL THIS
(REED)
(TERMINALS)
LOOP
LOOP 2
YOU MUST
BUTTON
LOOP 4
LOOP 1
SET
HOUSE
CODE
LOOP
2
LOOP 1
1
LOOP
2
(REED)
ALTERNATE
POSITION
FOR LOOP2
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
5819
ENROLL AS "RF"
5827
SET HOUSE CODE
5850 (GBD)
ENROLL AS "RF"
LOOP 2 (REED)
LOOP 1
(TERMINALS)
5816MN
LOOP 1
(TERMINALS)
(Green)
(Red) (Yellow)
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
5819S (WHS & BRS)
ENROLL AS "RF"
5827BD
SET HOUSE CODE
5890
ENROLL AS "RF"
5817
Each
LOOP
1
(PRIMARY)
2
(AUX. CENTER)
3
(AUX. RIGHT)
LOOP 1
(INTERNAL
SHOCK
SENSOR)
LOOP
1
(MOTION)
Table of Device Addresses
Address Report††Device Programmed by…
00 100 RF Receiver *56 zone programming: input device type entry 03 103 Long Range Radio automatic if output to long range radio field *29 enabled 04 104 4286 Voice Module automatic if phone module access code field *28 enabled
07 107 module 1 zones 09 - 16
Zone Expanders (4219/4229): *56 zone programming: input device type entry, then:
08 108 module 2 zones 17 - 24
09 10 11
† †
109 module 3 zones 25 - 32 110 module 4 zones 33 - 40 111 module 5 zones 41 - 48
Relay Modules (4204): *79 output device programming: device address prompt: 12 112 module 1 13 113 module 2
14 15
114 module 3 115 module 4
Keypads: data filed programming as listed below: 16 n/a keypad 1 17 n/a keypad 2 18 n/a keypad 3 19 n/a keypad 4 20 n/a keypad 5 21 n/a keypad 6 22 n/a keypad 7 23 n/a keypad 8
28 n/a 5800TM Module automatic † These module addresses apply to VISTA-20P only.
††
Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification touchpad display options.
automatic if zone no. 9-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay assigned
automatic if zone no. 25-32 entered as AW type or relay assigned
automatic if zone no. 33-40 entered as AW type or relay assigned
automatic if zone no. 41-48 entered as AW type or relay assigned
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
always enabled for partition 1, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
– 15 –
¬.35l
K5305-1PR 7/01
Copyright © 2001 Pittway Corporation
A DIVISION OF PITTWAY CORPORATION
165 Eileen Way, Syosset, NY 11791
24-HR BATTERY STANDBY REQUIRED FOR FIRE INSTALLATIONS. USE 12V, 17.2AH BATTERY FOR 600mA AUX POWER. SEE INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY BURGLARY STANDBY USE AT LEAST 4 HRS
CHARGING VOLTAGE
13.8VDC. MAXIMUM CHARGING CURRENT 650mA.
SEALED LEAD-ACID TYPE. BATTERY NORMALLY NEED NOT BE REPLACED FOR AT LEAST 3 YRS.
TO DETERMINE TOTAL STANDBY LOAD ON BATTERY, ADD 100mA TO TOTAL OF AUX. POWER OUTPUT AND REMOTE KEYPAD CURRENTS.
USE UL LISTED LIMITED ENERGY CABLE FOR ALL CONNECTIONS
CLASS 2 PLUG-IN TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO No. 1321).
(USE No. 1321CN IN CANADA)
USE 4300 / 1321X10 TRANSFORMER INTERFACE IN PLACE OF 1321 OR 1321CN WHEN POWER LINE CARRIER DEVICES ARE BEING USED. (SEE INSTRUCTIONS FOR CONNECTIONS)
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL FIRE PROTECTION ASSOCIATION, BATTERY-MARCH PARK, QUINCY,MA
02269). PRINTED INFORMATION DESCRIBING PROPER INSTALLATION, OPERATION,TESTING, MAINTENANCE, EVACUATION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT.
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER.
BATTERY
12V, 4AH
BATTERY FUSE
FOR REPLACEMENT,
3A
USE SAME VALUE (e.g. ADEMCO No. 90-12)
BLACK
+
RED
FLYING LEADS FOR BATTERY CONNECTION
+
RED JUMPER
CUT FOR BELL SUPERVISION. ALSO, CONNECT 2000 OHM RESISTOR DIRECTLY ACROSS SOUNDER.
8-PIN CONNECTOR
USED FOR 4300/1321X10
TRANSFORMER
CONNECTIONS AND FOR
ON-BOARD TRIGGERS
SEE INSTRUCTIONS.
1234 5 6
GND
+12 AUX
(TRIG. 1)
OUTPUT 17
OUTPUT 18
123 78
}
+
) RETURN
-
)
+
BLACK: KEYPAD GROUND (
RED: KEYPAD PWR (
REMOTE
KEYPADS
AND OTHER
ADDRESSABLE
DEVICES
(e.g. 5800TM,
4285/4286, LRR,
4219, 4229, 4204, 5881)
REMOTE KEYPADS
CAN USE 6150 OR 6160 KEYPADS. LOCAL PROGRAMMING MUST BE DONE WITH A 6139/6160, BUT NEED NOT REMAIN IN THE SYSTEM (SET TO ADDRESS 16).
TO 110VAC
UNSWITCHED
OUTLET (24HR)
+
ALARM OUTPUT
10.5–13.8VDC, 2A MAX. (600mA MAX. FOR UL
USAGE, INCLUDING
AUX POWER) STEADY
FOR BURGLARY/PANIC,
TEMPORAL PULSE
SOUNDING FOR FIRE.
CAN USE ADEMCO No. 702
SIREN, OR 12V BELL).
SEE INSTRUCTIONS.
FOR COMPLETE
INFORMATION, SEE
INSTRUCTIONS K5305-1
ASSEMBLED IN MEXICO
INSTALLATIONS)
ALL OUTPUTS ARE POWER
LIMITED.
NOTE:
KEYPAD (S) CURRENT (IN BOTH PARTITIONS) AND ALL OTHER DEVICES DRAWING POWER FROM TERMS 4 & 5 MUST BE INCLUDED IN AUX CURRENT DRAIN CALCULATIONS.
AUX. POWER
OUTPUT
10.5-13.8VDC 600mA MAX. (500mA MAX.
FOR UL
(USE SA4120XM-1
78
(TRIG. 2)
GREEN: DATA IN FROM KEYPAD
SYNC
COM DATA
TO TERM 4 TO TERM 5 TO TERM 6 TO TERM 7
YELLOW: KEYPAD DATA OUT
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
CABLE)
TO TRANS.
BLK RED GRN YEL
10
9654
LO
HI
ZONE 1
2000 OHMS EOLR
1312 14
TAMPER
2k
CONTACTS
TAMPER
2k
CONTACTS
2k
ZONE 3
TYPICAL WIRING FOR
DOUBLE BALANCED ZONE
(VISTA-20P ONLY)
OPTIONAL
FOR UP TO 40 ADDITIONAL ZONES
( FROM EITHER OR BOTH GROUPS)
11
LO
HI
ZONE 2
2000 OHMS EOLR
2k
2k
2k
ZONE 4
VISTA-20P/VISTA-15P
SUMMARY OF CONNECTIONS
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
BLK
(8 ADD'L EOLR WIRED ZONES PLUS 2 RED GRN YEL
BLK RED GRN YEL
12
HI
OHMS EOLR
2000
OUTPUT RELAYS)
ADEMCO No. 4204 RELAY MODULE
*5882 IN CANADA
13
LO
ZONE 3
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16; DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
10 11
-OR-
(4 OUTPUT RELAYS)
AND/OR
ADEMCO 5881* Type
RF RECEIVER
WIRELESS ZONES
5881L: UP TO 8 5881M: UP TO 16 5881H: UP TO 64
14
15
LO
HI
HI
ZONE 4
2000 OHMS EOLR
ZONE 2
3k
ZONE 10
6.2k
TYPICAL WIRING FOR
ZONE DOUBLING (VISTA-20P ONLY)
2000 OHMS EOLR
ZONE PAI RS
2 / 10 3 / 11 4 / 12 5 / 13 6 / 14 7 / 15 8 / 16
16
LO
ZONE 5
SET UNIT’S DIP SWITCH FOR DEVICE ADDRESSES 7 - 15 SEE INSTRUCTIONS.
SET RECEIVER’S DIP SWITCH FOR DEVICE ADDRESS OF “0”. SEE INSTRUCTIONS.
17
18
19
HI
HI
LO
2000 OHMS EOLR
USED IN A CANADIAN INSTALLATION
MUST BE LISTED FOR USE IN CANADA
LO
ZONE 7
ZONE 6
2000
OHMS
EOLR
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.
ALL DEVICES AND ACCESSORIES
4-WIRE SMOKE DETECTOR CONNECTIONS
AUX PWR
OUTPUT
TERMINALS
TO ZONES 2-8
TO ZONES 2-8
20
HI
LO
ZONE 8
2000 OHMS EOLR
RELAY
PROGRAM RELAY AS ZONE TYPE 54
HEAT
DETECTOR
(FIRE ZONE RESET)
_
BLK
+
_
VIOLET
2000 OHMS EOLR
+
+
5
_
4
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
TERM. ( )
+
_
TERM. ( )
21 22 23 24 25
RING
TIP
TIP
(GRAY)
(BROWN)
}
HANDSET
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
CONNECT CORD)
*CA38A IN CANADA
DOC LOAD NO.: 3
VISTA-20P ONLY
FOR CONNECTION OF OPTIONAL 4285 OR 4286 VIP MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
WARNING:
DISCONNECT TELEPHONE LINE AT TELCO JACK BEFORE SERVICING THIS UNIT.
COMPLIES WITH FCC RULES, PART 68. FCC REGISTRATION NO. 5GBUSA-44003-AL-E RINGER EQUIVALENCE: 0.1B.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
RING
(GREEN)
(RED)
}
INCOMING
PHONE LINE
INSTRUCTIONS
FOR PROPER GROUNDING
TO PREVENT RISK OF SHOCK,
V20P_V15P-SOC-V0
RED
EOL
POWER
SUPERVISION
RELAY MODULE A77-716B
EARTH
GROUND
SEE
Loading...