Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
POWER UP, then depress
1.
✱
] and [#]
[
both at once, within 50 seconds of powering up.
OR
Initially, key:
2.
Installer Code (4 + 1 + 1 + 2)
plus
8 + 0 + 0.
OR
If different
3.
✱
(if
Installer Code
98 was used to exit previously, method 1 above must be used to enter the program mode again)
is programmed, key:
New Installer Code + 8 + 0 + 0.
Data Field Programming Procedures
TaskProcedure
Go to a Data Field
Entering Data
Press [∗] + [Field Number], followed by the required entry.
When the desired field number appears, simply make the required entry. When the last
entry for a field is entered, the keypad beeps three times and automatically displays the
next data field in sequence.
If the number of digits that you need to enter in a data field is less than the maximum
digits available (for example, the phone number fields *41, *42), enter the desired data,
then press [∗]. The entry is terminated and the next data field number appears.
Review a Data Field
Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Deleting an Entry
Press [∗] + [Field Number] + [∗]. (Applies only to fields ∗40–*43, *45, *94, and pager
programming fields)
80 Output Programming4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
✱
81 Zone List ProgrammingZone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
✱
82 Alpha ProgrammingZone alpha descriptors
(for example, ✱56). The alpha display keypad will display the first of a series of prompts
RF transmitters.
INITIALIZE DOWNLOAD and RESET DEFAULTS
✱
Initializes download ID and subscriber account number.
96
✱
Sets all data fields to original factory default values.
97
TO EXIT PROGRAMMING MODE:
✱
Exits programming mode and
98
prevents
re-entry by:
Installer Code + 8
+ 0 + 0. If
✱
is used to exit programming
98
mode, system must be powered down, and method 1 above used to enter the programming mode.
✱
Exits programming mode and
99
allows
re-entry by:
Installer Code
+ 8 + 0 + 0 or method 1 above.
Special Messages
= OPEN CIRCUIT (no communication between Keypad and Control).
OC
or
EE
ENTRY ERROR
After powering up,
This will revert to a “
delay by pressing
= ERROR (invalid field number entered; re-enter valid field number).
AC, dI
Ready
(disabled) or
Busy Standby
” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
and
NOT READY
will be displayed after approximately 4 seconds.
[#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. Correct the programming
and then completely de-power and re-power the control to clear this indication and remove the disable indication.
– 2 –
352*5$00,1*)250
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Entries shown in dashed boxes indicate partition entries for VISTA-20P only (not applicable for VISTA-15P).
Field Function Data Entries Programmable Values
SYSTEM SETUP (✱20–✱29)
∗
INSTALLER CODE
20
| | | [4112]
4 digits, 0–9
✱
QUICK ARM ENABLE
21
✱
RF JAM OPTION
22
✱
FORCED BYPASS
23
∗
RF HOUSE ID CODE
24
✱
CHIME BY ZONE
26
✱
27
X–10 HOUSE CODE
✱
ACCESS CODE FOR
28
4285/4286 PHONE MODULE
✱
LONG RANGE RADIO OUTPUT
29
ZONE SOUNDS AND TIMING (✱31 – ✱39)
✱
ONE AUDIBLE ALARM PER ZONE
31
✱
FIRE ALARM SOUNDER TIMEOUT
32
✱
ALARM SOUNDER TIMEOUT
33
✱
EXIT DELAY
34
✱
ENTRY DELAY #1 (zone type 01)
35
✱
ENTRY DELAY #2 (zone type 02)
36
AUDIBLE EXIT WARNING
∗37
✱
CONFIRMATION OF ARMING DING
38
✱
POWER UP IN PREVIOUS STATE
39
[0,0]
Part. 1 Part.2
[0]
[0,0]
Part. 1 Part. 2
| | |
Part. 1 Part. 2 Common
[0]
[0]
| [00]
(Partition 1 only)
[0]
[0]
[0]
[1]
| | [70,70]
Part. 1 Part. 2
| | [30,30]
Part. 1 Part. 2
| | [60,60]
Part. 1 Part. 2
[1,1]
Part. 1 Part. 2
[0,0]
Part. 1 Part. 2
[1]
0 = no; 1 = yes
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
0 = none UL: must be “0”
1 = bypass open zones
00 = disable all wireless keypad usage
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for "✱", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be “0”
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be “1” for fire install.
00–99 = seconds of exit delay time for each partition
Common zones use same delay as partition 1.
00–99 = seconds of entry delay #1 time for each
partition; UL: 45 seconds max.
Common zones use same delay as partition 1.
00–99 = entry delay #2 time for each partition;
UL: 60 seconds max.
Common zones use same delay as partition 1.
0 = no; 1 = yes
0 = no; 1 = yes (wired keypads and RF)
2 = yes, RF only
0 = no; 1 = yes UL: must be “1”
; 1 = yes
DIALER PROGRAMMING (✱40 – ✱42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the
maximum digits entered, exit the field by pressing [✶] and next desired field number.
PABX ACCESS CODE
∗40
PRIMARY PHONE No.
∗41
SECOND PHONE No.
∗42
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱41
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱42
| | | | |
Enter up to 6 digits. To clear entries from field, press ✱40✱ .
✱
.
✱
.
– 3 –
NOTE: Entry of a number other than one specified will give unpredictable results.
For fields *43- *46:
reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999. Exit field by pressing
digits are used. E.g., For Acct.
Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; [#+15 for F]. Enter
, enter: #+11| 2 | 3 | 4
B234
as the fourth digit if a 3-digit account number (for 3+1 dialer
[✱]
✱
(and press next field number) if only 3
✱
PARTITION 1 PRIMARY SUBS. ACCT. No.
43
✱
PARTITION 1 SECONDARY SUBS. ACCT. No.
44
✱
PARTITION 2 PRIMARY SUBS. ACCT. No.
45
✱
PARTITION 2 SECONDARY SUBS. ACCT. No.
46
✱
PHONE SYSTEM SELECT
47
✱
REPORT FORMAT
48
✱
SPLIT/DUAL REPORTING
49
✱
15 SEC DIALER DELAY (BURG)
50
✱
SECOA/RADIONICS SELECT
53
✱
DYNAMIC SIGNALING DELAY
54
✱
DYNAMIC SIGNALING PRIORITY
55
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (✱59 – ✱76, & ✱89):
For 3+1 or 4+1 Standard Format:
not
A 0 (
#+10) in the
For Expanded or 4+2 Format:
not
A 0 (
#+10) in the
For Ademco Contact ID® Reporting:
not
A 0 (
#+10) in the
first
second
first
Enter a code in the
box will disable a report. A 0 (
Enter codes in
box will eliminate the expanded message for that report. A 0 (
box disables the report.
Enter any digit (other than 0) in the
first
box: 1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
not
#+10) in the
both
boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
UL: see installation instructions for requirements
| | | [FFFF]
| | | [FFFF]
| | | [FFFF]
| | | [FFFF]
[1]
primary secondary
[0]
[0]
[0]
[0]
[0]
second
box will result in automatic advance to the next field.
first
box, to enable zone to report (entries in the
not
#+10) in
[70]
See box above for entries. To clear entries
from field, press *43
See box above for entries. To clear entries
from field, press *44*.
See box above for entries. To clear entries
from field, press *45*.
See box above for entries. To clear entries
from field, press *46*.
If Cent. Sta.
0=Pulse Dial; 1=Tone Dial;
if Cent. Sta.
2 = Pulse Dial ; 3 = Tone Dial
0 = disabled, 1 = first, 2 = second, 3 = third
4 = fourth, 5 = last, 6 = next to last, 7 = third to last
0 = no, 1 = partition 1 only
2 = partition 2 only, 3 = both partitions
0 = 15 seconds6 = 2-1/2 min#+12 = 8 min
1 = 30 seconds7 = 3 min#+13 = 10 min
2 = 45 seconds8 = 4 min#+14 = 12 min
3 = 60 seconds9 = 5 min#+15 = 15 min
4 = 90 seconds#+10 = 6 min
5 = 2 minutes#+11 = 7 min
(assign cross zones on zone list 4, with *81 Menu mode)
0 = no, 1 = yes
0 = 15 seconds6 = 2-1/2 min#+12 = 8 min
1 = 30 seconds7 = 3 min#+13 = 10 min
2 = 45 seconds8 = 4 min#+14 = 12 min
3 = 60 seconds9 = 5 min#+15 = 15 min
4 = 90 seconds#+10 = 6 min
5 = 2 minutes#+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm
zones when used in fire and/or UL burglar alarm installation
See box on previous page for report code entries.
0 = None; 1 = Alarm/Alarm Restore
2 = Trouble/Trouble Restore;
4 = Bypass/Bypass Restore;
8 = Open/Close.
Restore”, and “Open/Close”, enter 9 (1 + 8); To select
all, enter #15.
0 = None
4 = AAV UL: do not use AAV
8 = Exit Delay Restart
Multiple choice example: for AAV (4) + Exit Delay
restart (8) enter # + 12.
: 0 = disabled, 1-15 = 1 min - 15 min
Digit 1:
:
Digit 2
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble sound
2 = Same as “1”, plus programmed output device
STARTS. If either partition is armed, external sounder
activates also.
programmed to be STOPPED in field ✱80 or
STOPPED by Code + # + 8 + output number.
0 = Unlimited Reports; 1 = 1 report; 2 = 2 reports
UL: must be “0”
Enter up to 20 digits, 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. Do not fill unused
spaces. If fewer than 20 digits, exit field by pressing ✱ (and press 95, if entering next field). To clear
entries from field, press ✱94✱. UL: downloading may be performed only if a technician is at the site.
For each partition, select from the following options:
0 = no reports sent
1 = Open/closes all users
4 = All alarms and troubles
5 = All alarms / troubles, and open/closes for all users
12 = Alarms / troubles for zones entered in zone list 9
13 = Alarms / troubles for zones entered in zone list 9,
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
✱
CONFIGURABLE ZONE TYPE 91
184
✱
ZONE TYPE 91 REPORT CODES
185
IMPORTANT:
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
Use existing Contact ID®
Use existing Contact ID®
[0]
12345678910
Make the appropriate entry for each digit, 1-10, based on the charts provided on the
next page. Each digit’s entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
90 ALARM ID: XXX
TROUBLE ID: XXX
12345678910
Make the appropriate entry for each digit, 1-10, based on the charts provided on the
next page. Each digit’s entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
91 ALARM ID: XXX
TROUBLE ID: XXX
0 = 60 Hz; 1 = 50 Hz
Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [∗]
moves forward. Press [∗] when done to continue.
Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [∗]
moves forward. Press [∗] when done to continue.
KEYPAD OPTIONS *190-*196 (
NOTE:
Each keypad must be assigned a unique address. Keypads programmed with the same address will give
unpredictable results.
KEYPAD 2 ADDRESS 17
∗
190
KEYPAD 3 ADDRESS 18
∗
191
KEYPAD 4 ADDRESS 19
∗
192
KEYPAD 5 ADDRESS 20
∗
193
KEYPAD 6 ADDRESS 21
∗
194
KEYPAD 7 ADDRESS 22
∗
195
KEYPAD 8 ADDRESS 23
∗
196
EXIT TIME DISPLAY INTERVAL
∗
197
: Options for keypad address 16 are set by the factory and cannot be changed.)
NOTE
[0] [0]
Partition/Sound
Enable
VISTA-20P: enter partition
VISTA-15P: 1 = enable
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data
fields*182-*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the
downloader software.
Programming Configurable Zone Type options involves entering 10 digits in data field *182 for zone type 90 and
field *184 for zone type 91, where each digit represents the sum of the values of its various options as shown in
the tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
DIGIT 1
(See note 5 for RF zones)
DIGIT 2
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
(See note 5 for RF zones)
Shorted
Auto
RestoreVent Zone
0 = no
4 = yes
0 = no
8 = yes
Digit 1 = EOL + Open Digit 2 = Short + auto restore + vent zone
DIGIT 3
(See note 5 for RF zones)
DIGIT 4
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
(See note 5 for RF zones)
Shorted
Byp. when
disarmed
0 = no
4 = yes
Byp. when
armed
0 = no
8 = yes
Digit 3 = EOL + Open Digit 4 = Short + byp. disarmed + byp. armed
DIGIT 5
(See note 5 for RF zones)
DIGIT 6
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
(See note 5 for RF zones)
Shorted
Dial Delay
(see field *50)
0 = no
4 = use delay
Fault Delay
(see field *87)
0 = no
8 = use delay
see note 1
Digit 5 = EOL + Open Digit 6 = Short + dial delay + fault delay
DIGIT 7 DIGIT 8
Display FaultsPower Reset/
Verification
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
armed
alarms, trbles,
faults when
disarmed)
(show
0 = no
4 = power reset
after fault
(by code + OFF)
12 = verification
(see zone
type 16)
3 = never show
any alarms,
trbles, faults
Digit 7 = fault display + power
reset/verification
Use Entry
Delay 1/2
0 = no
1 = delay 1
2 = delay 2
Use Exit
Delay
0 = no
4 = use exit
delay
Respond as
Interior Type
0 = no
8 = yes
see note 2
Digit 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
DIGIT 9 DIGIT 10
Alarm SoundsUse Bell
Timeout
0 = none
1 = steady
0 = no
4 = yes
keypad
2 = steady bell
and keypad
see fields *32,
*33
3 = pulsing bell
and keypad
Digit 9 = alarm sounds + bell timeout + fire zone Digit 10 = trouble sounds + chime
Respond as
Fire Zone
0 = no
8 = yes
see zone type
09; see note 4
Trouble
Sounds
0 = none
1 = periodic
beep
2 = trouble
beeps
Chime when
Chime Mode On
0 = no
4 = yes
Entries for Fields *182 and *184
Digit Zone Type 90Zone Type 91
(field *182) (field *184)
1
2
3
4
5
6
7
8
9
10
To calculate each digit’s entry:
Simply add the values of the selected options
in each of the digit’s columns (one option per
column). For example, to program Digit 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
OPENSHORTEDINTACT
EOL
Zone Conditions Represented
in Digits 1-6
NOTES:
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
“respond as interior zone type” (Digit 8,
interior type = yes), and set zone
response to “fault” in digits 3-4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
3. Do not set fire zones to respond as a
“fault” (digits 1-6), otherwise faults will not
display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The “open” option in digits 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for offnormal RF zone conditions.
6. Zone-Doubling/Double-Balanced: A short
on either zone of a zone-doubled pair or
on a double-balanced zone causes a
tamper condition.
-018-V0
– 8 –
Reserved Zones
addressable
91 =
device report
enable/disable
default zone
type = [05].
Duress report
92 =
enable/disable
*56 ZONE PROGRAMMING WORKSHEET
Zone Zn Type Part.ReportInput Type Loop Rsp. Time Serial No.Location
Personal Emergency
Silent Alarm
Audible Alarm
Fire
Emergency Keys: A = [1] / [∗]B = [∗] / [#]C = [3] / [#]
OUTPUT RELAYS/POWERLINE CARRIER DEVICES WORKSHEET FOR
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗
79 RELAY/POWERLINE CARRIER DEVICE MAPPING (Must program before using *80)
OUTPUT TYPEOUTPUT TYPE
RelayX10RelayX10
Output
No.
0109
0210
0311
0412
0513
0614
0715
0816
Module
Addr.
Pos
(1-4)
Unit
No.
Description
Output
No.
17
18
Module
Addr.
On-Board Trigger 1
On-Board Trigger 2
Pos
(1-4)
∗79,
∗
80 and ∗81.
(09-16 apply to VISTA-20P only)
Unit
Description
No.
✱
81ZONE LISTS FOR OUTPUT DEVICES
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
Note:
Record desired zone numbers below, noting that a list may include
List No. Used For…Contains These Zones…
01
02
03
04
05
06
07
08
09
10
11
12
General Purpose (GP)
General Purpose
Chime-by-Zone or GP
Cross Zones
Night-Stay Zones or GP
General Purpose
General Purpose
General Purpose
Zones activating pager 1
Zones activating pager 2
Zones activating pager 3
Zones activating pager 4
– 10 –
any
or
of system's zone numbers.
all
✱
80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
✱
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number
(V20P=1-48)
(V15P=1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
Activation Type and DetailEvent (for zone list/activated by)Output
Zone List
1-8 = list
(ZL)
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
01-64
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 = partition 2
3 = common
78 = keyswitch red LED†††
79 = keyswitch green LED†††
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
Action
By Zone No.
0 = restore
1 = alrm/flt/trbl
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
†† Duration is set in program field *177.
††† Device action not used for these choices.
Code + # + 7 + NN Key Entry
Code + # + 8 + NN Key Entry
Output
Number
V20P=1-18
V15P=1-8,
17, 18
††
††
starts
stops
Device
Type
R = relay
T = trigger
X = X10
Device
Device
– 11 –
Zone Type Definitions
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
Type 02
Entry/Exit Burglary #2
Type 03
Perimeter Burglary
Type 04
Interior Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Fire
Type 10
Interior w/Delay
Type 12
Monitor Zone
Type 14
Carbon Monoxide
Type 16
Fire w/Verification
Type 20
Arm-Stay
Use this zone type if the zone is not used.
•
Assign to zones that are used for primary entry and exit.
•
Provides entry delay if the control is armed in the Away or Stay modes.
•
No entry delay is provided when the panel is armed in the Instant mode.
•
Entry delay #1 is programmable from 0 to 99 seconds for each partition.
•
Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable from 0 to 99 seconds (field ✱34).
•
Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
•
Provides a secondary entry delay, in same manner as entry delay #1.
•
Entry delay #2 is programmable from 0 to 99 seconds for each partition.
•
Exit delay is same as described for Type 01.
•
Assign to all sensors or contacts on exterior doors and windows.
•
Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, or Instant
modes.
•
Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
•
Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.
•
Active when the panel is armed in the Away mode.
•
Bypassed automatically when the panel is armed in the Stay or Instant modes.
•
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering
a sensitive area such as a stock room, drug supply room, etc.
•
Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
•
Provides an instant alarm if faulted when armed in the Away, Stay, or Instant (night) modes.
•
During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
•
Usually assigned to a zone containing an emergency button.
•
Sends a report to the central station but provides no keypad display or sounding.
•
Assign to a zone that has an emergency button.
•
Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external
alarm.
•
Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as
water or temperature sensors.
•
Sends a report to the central station and provides an alarm sound at the keypad.
provided.)
•
Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
•
This zone type is always active and cannot be bypassed.
Note:
•
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away
•
Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
•
Bypassed when the panel is armed in the Stay or Instant modes.
•
Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "
•
The “check” message will automatically disappear from the keypad. The zone restores dynamically;
•
Faults of this zone type are independent of the system, and can exist at the time of arming without
•
•
Assigned to any zone with a carbon monoxide detector.
•
The bell output will pulse when this zone type is alarmed.
•
Always active and cannot be bypassed.
•
Provides a fire alarm when zone is shorted, but only after alarm verified.
•
System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
•
Provides a trouble response when zone is open.
•
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.
Only hardwired zone 1 should be programmed as a fire zone, where 2-wire smoke detectors can
be connected. However, any wireless zone can be used as a fire zone.
mode.
delay zone was tripped first.
24 Hr. Non-Burg. -#XXX
system keypad will display a “check” message indicating the appropriate zone. Upon restoral of the zone,
the message, "
therefore a user code + off sequence is not needed to reset the zone.
interference.
Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
within 90 seconds triggers fire alarm.
UL: may not be used on zone 1.
RESTORE-24 Hr. Non-Burg. -#XXX
" (where XXX is the zone number) will be sent to the Central Station. The
" will be sent to the Central Station.
(No bell output is
ALARM-
– 12 –
Type 21
Arm-Away
Type 22
Disarm
Type 23*
No Alarm Response
Type 24
Silent Burglary
Type 77
Keyswitch
Types 90-93
Installer Defined
*
The system can still be armed when these zone types are in a faulted condition.
•
Arms the system in Away mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.
•
Disarms the system when the zone is activated.
•
User code for button must be assigned.
•
Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
•
Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
•
Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, or Instant, modes.
•
A report is sent to the central station.
•
Assign to zone wired to a keyswitch.
•
These zone types can be programmed for various custom responses. See data fields *182-*185.
UL: Zone types 90-93 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
Schedules
events 00-07 for both controls; VISTA-15P supports up to 8 schedules, VISTA-20P supports up to 32 schedules
(installer code + [#] + [6] [4];
master code can only access schedules 01-16 for VISTA-20P, 01-04 for VISTA-15P, and
01 = device on/off05 = forced AWAY arm10 = display custom words 8-10
02 = user access06 = auto disarm11 = peridoic test report
03 = latch key report07 = display “reminder”
04 = forced STAY arm
DaysDays
(yes/no)(yes/no)
– 13 –
(Word Space)
000
– A –
•001 AIR
• 002 ALARM
004 ALLEY
005 AMBUSH
• 006 AREA
• 007 APARTMENT
• 009 ATTIC
010 AUDIO
– B –
• 012 BABY
• 013 BACK
• 014 BAR
• 016 BASEMENT
• 017 BATHROOM
•018 BED
• 019 BEDROOM
020 BELL
•021 BLOWER
•022 BOILER
023 BOTTOM
025 BREAK
• 026 BUILDING
– C –
028 CABINET
• 029 CALL
030 CAMERA
031 CAR
033 CASH
034 CCTV
035 CEILING
036 CELLAR
• 037 CENTRAL
038 CIRCUIT
• 040 CLOSED
• 046 COMPUTER
047 CONTACT
– D –
• 048 DAUGHTERS
049 DELAYED
•050 DEN
051 DESK
• 052 DETECTOR
• 053 DINING
054 DISCRIMINATOR
055 DISPLAY
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
• 057 DOOR
• 059 DOWN
• 060 DOWNSTAIRS
061 DRAWER
• 062 DRIVEWAY
• 064 DUCT
– E –
• 065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
• 069 EQUIPMENT
• 071 EXIT
072 EXTERIOR
– F –
• 073 FACTORY
075 FAMILY
• 076 FATHERS
• 077 FENCE
•079 FIRE
• 080 FLOOR
081 FLOW
082 FOIL
• 083 FOYER
084 FREEZER
•085 FRONT
– G –
• 089 GARAGE
•090 GAS
091 GATE
•092 GLASS
093 GUEST
094 GUN
H –
–
• 095 HALL
• 096 HEAT
098 HOLDUP
099 HOUSE
100 INFRARED
•101 INSIDE
102 INTERIOR
103 INTRUSION
– J –
104 JEWELRY
– K –
• 105 KITCHEN
• 106 LAUNDRY
– L –
• 107 LEFT
108 LEVEL
• 109 LIBRARY
• 110 LIGHT
111 LINE
• 113 LIVING
• 114 LOADING
115 LOCK
116 LOOP
117 LOW
• 118 LOWER
– M –
• 119 MACHINE
121 MAIDS
122 MAIN
• 123 MASTER
• 125 MEDICAL
126 MEDICINE
128 MONEY
129 MONITOR
• 130 MOTHERS
• 131 MOTION
132 MOTOR
– N –
• 134 NORTH
135 NURSERY
– O –
• 136 OFFICE
• 138 OPEN
139 OPENING
• 140 OUTSIDE
142 OVERHEAD
– P –
143 PAINTING
• 144 PANIC
145 PASSIVE
• 146 PATIO
147 PERIMETER
• 148 PHONE
150 POINT
151 POLICE
152 POOL
• 153 POWER
• 156 REAR
•161 RIGHT
• 162 ROOM
• 167 SERVICE
• 168 SHED
•170 SHOP
•173 SIDE
•176 SMOKE
•178 SONS
•179 SOUTH
•182 STATION
• 185 STORAGE
• 199 TEMPERATURE
• 201 TOOL
•205 UP
• 206 UPPER
• 207 UPSTAIRS
• 208 UTILITY
– R –
155 RADIO
157 RECREATION
159 REFRIGERATION
160 RF
163 ROOF
– S –
164 SAFE
165 SCREEN
166 SENSOR
169 SHOCK
171 SHORT
174 SKYLIGHT
175 SLIDING
180 SPRINKLER
184 STORE
186 STORY
190 SUPERVISED
191 SUPERVISION
192 SWIMMING
193 SWITCH
– T –
194 TAMPER
196 TELCO
197 TELEPHONE
200 THERMOSTAT
202 TRANSMITTER
– U –
• 216 WEST
• 217 WINDOW
• 219 WING
• 225 ZONE
• 226 0
• 227 1
• 228 1ST
• 229 2
• 230 2ND
• 231 3
• 232 3RD
• 233 4
• 234 4TH
• 235 5
• 236 5TH
• 237 6
• 238 6TH
• 239 7
• 240 7TH
• 241 8
• 242 8TH
• 243 9
• 244 9TH
– V –
209 VALVE
210 VAULT
212 VOLTAGE
– W –
213 WALL
214 WAREHOUSE
220 WIRELESS
– X –
222 XMITTER
– Y –
223 YARD
– Z –
224 ZONE (No.)
245 Custom Word #1
246 Custom Word #2
247 Custom Word #3
248 Custom Word #4
249 Custom Word #5
250 Custom Word #6
251 Custom Word #7
252 Custom Word #8
253 Custom Word #9
254 Custom Word #10
Note:
32 (space)
33!
34"
35#
36$
37%
38&
39'
40(
Bulleted (•) words in
boldface type
are those that are also available for use by the 4285/4286 Phone Module. If
using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide
annunciation of those words.
CHARACTER (ASCII) CHART (For Adding Custom Words)
41)
42*
43+
44,
45–
46.
47/
480
491
502
513
524
535
546
557
568
579
58:
59;
60<
61=
62>
63?
64@
65A
66B
67C
68D
69E
70F
71G
72H
73I
74J
75K
76L
77M
78N
79O
80P
81Q
82R
83S
84T
85U
86V
87W
88X
89Y
90 Z
– 14 –
5800 Series Transmitter Input Loop Identification
• All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
of the inputs requires its own programming zone
• Transmitter inputs entered as:
"RF" (Supervised RF) Type
signals, as well as fault, restore and low battery signals.
The transmitter must remain within the receiver's range.
“UR" (Unsupervised RF) Type
the "RF" Type does, but the control does not supervise
the check-in signals. The transmitter may, therefore, be
carried off-premises.
"BR" (Unsupervised Button RF) Type
signals. They do not send restore or check-in signals.
They will indicate a low battery condition when tested or
activated normally. The transmitter may be carried offpremises.
: For information on any transmitter not shown
Note
above, refer to the instructions accompanying that
transmitter for details regarding loop numbers, etc
UL NOTE:The 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TEMP, 5819,
5819WHS & BRS, 5827BD, and 5850
transmitters are not intended for use
in UL installations
send periodic check-in
send all the signals that
only send fault
(e.g., a 5804's four inputs require four programming zones).
LOOP 3
LOOP 2
LOOP 1
LOOP 4
YOU MUST
ENROLL THIS
BUTTON
5801
ENROLL AS "UR" OR "RF"
YOU MUST
ENROLL THIS
BUTTON
LOOP 4
5804
ENROLL
AS "BR"
.
ENROLL AS "RF"
5808
ENROLL AS "RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 3
LOOP
1
5809
LOOP
1
5802MN
ENROLL AS "UR" OR "RF"
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5804BD
ENROLL AS "BR"
5816
ENROLL AS "RF"
ENROLL THIS
(REED)
(TERMINALS)
LOOP
LOOP 2
YOU MUST
BUTTON
LOOP 4
LOOP 1
SET
HOUSE
CODE
LOOP
2
LOOP 1
1
LOOP
2
(REED)
ALTERNATE
POSITION
FOR LOOP2
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
5819
ENROLL AS "RF"
5827
SET HOUSE CODE
5850 (GBD)
ENROLL AS "RF"
LOOP 2
(REED)
LOOP 1
(TERMINALS)
5816MN
LOOP 1
(TERMINALS)
(Green)
(Red)
(Yellow)
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
5819S (WHS & BRS)
ENROLL AS "RF"
5827BD
SET HOUSE CODE
5890
ENROLL AS "RF"
5817
Each
LOOP
1
(PRIMARY)
2
(AUX. CENTER)
3
(AUX. RIGHT)
LOOP 1
(INTERNAL
SHOCK
SENSOR)
LOOP
1
(MOTION)
Table of Device Addresses
Address Report††DeviceProgrammed by…
00100RF Receiver*56 zone programming: input device type entry
03103Long Range Radioautomatic if output to long range radio field *29 enabled
041044286 Voice Moduleautomatic if phone module access code field *28 enabled
07107module 1 zones 09 - 16
Zone Expanders (4219/4229):*56 zone programming: input device type entry, then:
08108module 2 zones 17 - 24
†
09
10
11
†
†
109module 3 zones 25 - 32
110module 4 zones 33 - 40
111module 5 zones 41 - 48
28n/a5800TM Moduleautomatic
† These module addresses apply to VISTA-20P only.
††
Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable
addressable device reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification
touchpad display options.
•
automatic if zone no. 9-16 entered as AW type or relay assigned
•
automatic if zone no. 17-24 entered as AW type or relay assigned
•
automatic if zone no. 25-32 entered as AW type or relay assigned
•
automatic if zone no. 33-40 entered as AW type or relay assigned
•
automatic if zone no. 41-48 entered as AW type or relay assigned
•
entered at device address prompt
•
entered at device address prompt
•
entered at device address prompt
•
entered at device address prompt
•
always enabled for partition 1, all sounds enabled.
24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS
CHARGING VOLTAGE
13.8VDC. MAXIMUM
CHARGING CURRENT
650mA.
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
CLASS 2 PLUG-IN TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO No. 1321).
(USE No. 1321CN IN CANADA)
USE 4300 / 1321X10 TRANSFORMER
INTERFACE IN PLACE OF 1321 OR
1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
INSTRUCTIONS FOR CONNECTIONS)
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
BATTERY-MARCH PARK, QUINCY,MA
02269).
PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION,
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
BATTERY
12V, 4AH
BATTERY FUSE
FOR REPLACEMENT,
3A
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
BLACK
+
RED
FLYING LEADS
FOR BATTERY
CONNECTION
+
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
SOUNDER.
8-PIN CONNECTOR
USED FOR 4300/1321X10
TRANSFORMER
CONNECTIONS AND FOR
ON-BOARD TRIGGERS
SEE INSTRUCTIONS.
1234 5 6
GND
+12 AUX
(TRIG. 1)
OUTPUT 17
OUTPUT 18
12378
}
+
) RETURN
-
)
+
BLACK: KEYPAD GROUND (
RED: KEYPAD PWR (
REMOTE
KEYPADS
AND OTHER
ADDRESSABLE
DEVICES
(e.g. 5800TM,
4285/4286, LRR,
4219, 4229,
4204, 5881)
REMOTE KEYPADS
CAN USE 6150 OR 6160
KEYPADS. LOCAL
PROGRAMMING
MUST BE DONE WITH A
6139/6160, BUT NEED NOT
REMAIN IN THE SYSTEM
(SET TO ADDRESS 16).
TO 110VAC
UNSWITCHED
OUTLET (24HR)
+
ALARM OUTPUT
10.5–13.8VDC, 2A MAX.
(600mA MAX. FOR UL
USAGE, INCLUDING
AUX POWER) STEADY
FOR BURGLARY/PANIC,
TEMPORAL PULSE
SOUNDING FOR FIRE.
CAN USE ADEMCO No. 702
SIREN, OR 12V BELL).
SEE INSTRUCTIONS.
FOR COMPLETE
INFORMATION, SEE
INSTRUCTIONS K5305-1
ASSEMBLED IN MEXICO
INSTALLATIONS)
ALL OUTPUTS
ARE POWER
LIMITED.
NOTE:
KEYPAD (S)
CURRENT (IN
BOTH
PARTITIONS)
AND ALL
OTHER DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
DRAIN
CALCULATIONS.
AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
(500mA MAX.
FOR UL
(USE SA4120XM-1
78
(TRIG. 2)
▲
GREEN: DATA IN FROM KEYPAD
SYNC
COM
DATA
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
▲
YELLOW: KEYPAD DATA OUT
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
CABLE)
TO
TRANS.
BLK
RED
GRN
YEL
10
9654
LO
HI
ZONE 1
2000
OHMS
EOLR
131214
TAMPER
2k
CONTACTS
TAMPER
2k
CONTACTS
2k
ZONE 3
TYPICAL WIRING FOR
DOUBLE BALANCED ZONE
(VISTA-20P ONLY)
OPTIONAL
FOR UP TO 40 ADDITIONAL ZONES
( FROM EITHER OR BOTH GROUPS)
11
LO
HI
ZONE 2
2000
OHMS
EOLR
2k
2k
2k
ZONE 4
VISTA-20P/VISTA-15P
SUMMARY OF CONNECTIONS
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO No. 4229
WIRED EXPANSION/RELAY MODULE
BLK
(8 ADD'L EOLR WIRED ZONES PLUS 2
RED
GRN
YEL
BLK
RED
GRN
YEL
12
HI
OHMS
EOLR
2000
OUTPUT RELAYS)
ADEMCO No. 4204 RELAY MODULE
*5882 IN CANADA
13
LO
ZONE 3
•
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
•
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
•
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
1011
-OR-
(4 OUTPUT RELAYS)
AND/OR
ADEMCO 5881* Type
RF RECEIVER
WIRELESS ZONES
5881L: UP TO 8
5881M: UP TO 16
5881H: UP TO 64
14
15
LO
HI
HI
ZONE 4
2000
OHMS
EOLR
ZONE 2
3k
ZONE 10
6.2k
TYPICAL WIRING FOR
ZONE DOUBLING
(VISTA-20P ONLY)
2000
OHMS
EOLR
ZONE
PAI RS
2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
8 / 16
16
LO
ZONE 5
SET UNIT’S
DIP SWITCH
FOR DEVICE
ADDRESSES
7 - 15
SEE
INSTRUCTIONS.
SET
RECEIVER’S
DIP SWITCH
FOR DEVICE
ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
17
18
19
HI
HI
LO
2000
OHMS
EOLR
USED IN A CANADIAN INSTALLATION
MUST BE LISTED FOR USE IN CANADA
LO
ZONE 7
ZONE 6
2000
OHMS
EOLR
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.
ALL DEVICES AND ACCESSORIES
4-WIRE
SMOKE DETECTOR
CONNECTIONS
AUX PWR
OUTPUT
TERMINALS
TO ZONES 2-8
TO ZONES 2-8
20
HI
LO
ZONE 8
2000
OHMS
EOLR
RELAY
PROGRAM RELAY
AS ZONE TYPE 54
HEAT
DETECTOR
(FIRE ZONE RESET)
_
BLK
+
_
VIOLET
2000
OHMS
EOLR
+
+
5
_
4
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
TERM. ( )
+
_
TERM. ( )
2122232425
RING
TIP
TIP
(GRAY)
(BROWN)
}
HANDSET
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
CONNECT CORD)
*CA38A IN CANADA
DOC LOAD NO.: 3
VISTA-20P ONLY
FOR CONNECTION OF OPTIONAL 4285 OR 4286 VIP
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
WARNING:
DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
RING
(GREEN)
(RED)
}
INCOMING
PHONE LINE
INSTRUCTIONS
FOR PROPER
GROUNDING
TO PREVENT RISK OF SHOCK,
V20P_V15P-SOC-V0
RED
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
EARTH
GROUND
SEE
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.