Honeywell VISTA-12A, VISTA-12E Installation And Setup Manual

ADEMCO VISTA-12A
ADEMCO VISTA-12E
Security Systems
K10022-1V1 10/05 Rev. A
ii
Table Of Contents
•••••••••••••••••••••••••••••••••
Features and Installation Highlights ..............................................................................................1-1
Capabilities ........................................................................................................................................ 1-1
Functions............................................................................................................................................ 1-1
Compatible Devices............................................................................................................................1-2
Important Installation Highlights (Installer Please Read) .............................................................1-2
Mounting and Wiring the Control....................................................................................................2-1
Cabinet and Lock ...............................................................................................................................2-1
Mounting the PC Board..................................................................................................................... 2-2
Wiring to Keypads .............................................................................................................................2-3
Sounder (Siren) Connections............................................................................................................. 2-5
Wiring the AC Transformer .............................................................................................................. 2-5
Backup Battery .................................................................................................................................. 2-6
Earth Ground..................................................................................................................................... 2-6
Basic Wired Zones.............................................................................................................................. 2-8
Smoke Detectors ................................................................................................................................ 2-9
4219/4229 Expansion Zones .............................................................................................................. 2-10
6164 Keypad Expansion Zones..........................................................................................................2-11
Installing the RF Receiver.................................................................................................................2-12
Installing a 5800TM Module............................................................................................................. 2-13
Installing the Transmitters............................................................................................................... 2-13
Installing a Keyswitch.......................................................................................................................2-14
Connecting Relay Modules ................................................................................................................ 2-15
Powerline Carrier Devices................................................................................................................. 2-16
Trigger Module and On-Board Triggers ...........................................................................................2-17
Phone Line Connections .................................................................................................................... 2-18
Alternative Communications Media (ACM) Connections ................................................................ 2-18
Audio Alarm Verification Connections (AAV, “Listen-In”) .............................................................. 2-19
Programming Overview ..................................................................................................................... 3-1
About Programming...........................................................................................................................3-1
Zones and Partitions.......................................................................................................................... 3-2
Keypads .............................................................................................................................................. 3-3
Wireless Receiver Transmitters, and Wireless Keys (keyfobs)........................................................3-3
Pager Programming........................................................................................................................... 3-4
Function Keys .................................................................................................................................... 3-4
Output Devices................................................................................................................................... 3-4
Zone Type Definitions........................................................................................................................ 3-5
Mechanics of Programming............................................................................................................... 3-8
Data Field Programming.................................................................................................................... 4-1
About Data Field Programming........................................................................................................ 4-1
Programming Data Fields ................................................................................................................. 4-1
System Setup Fields .......................................................................................................................... 4-1
Zone Sounds & Timing ...................................................................................................................... 4-3
Dialer Programming (∗40 – ∗55) .......................................................................................................4-4
iii
System Status Report Codes ............................................................................................................. 4-7
Miscellaneous System Fields.............................................................................................................4-9
Pager Programming Fields................................................................................................................4-13
Miscellaneous System Fields.............................................................................................................4-15
AUI Enable......................................................................................................................................... 4-19
Keypad Programming Fields............................................................................................................. 4-19
Menu Mode Programming..................................................................................................................5-1
About Zone Programming (56 and 58 Menu Modes) .................................................................... 5-1
56 Zone Programming Procedure.................................................................................................... 5-1
Completing Zone Programming ........................................................................................................ 5-5
58 Expert Programming Mode Procedures ..................................................................................... 5-6
Wireless Key Programming Templates ............................................................................................5-8
About Output Device Programming (*79/*80 Menu Mode) ............................................................. 5-12
*79 Menu Mode: Output Device Mapping ........................................................................................5-12
*80 Menu Mode: Defining Output Functions ...................................................................................5-14
About Zone Lists (81 Menu Mode)...................................................................................................5-17
Zone List Programming.....................................................................................................................5-18
About Function Key Programming (57 Menu Mode)...................................................................... 5-18
Programming Function Keys ............................................................................................................5-19
About Descriptor Programming (*82 Menu Mode)........................................................................... 5-20
Configurable Zone Type Programming (*83 Menu Mode) ............................................................... 5-22
Programming Installer and User Schedules ....................................................................................5-23
System Communication and Operation.......................................................................................... 6-1
Panel Communication with Central Station ....................................................................................6-1
Report Code Formats......................................................................................................................... 6-1
Robofon 8 Format............................................................................................................................... 6-4
ADEMCO Contact ID®...................................................................................................................... 6-5
Security Codes....................................................................................................................................6-6
Keypad Functions .............................................................................................................................. 6-7
Panic Keys.......................................................................................................................................... 6-8
Follow-Me Feature............................................................................................................................. 6-9
Setting/Adjusting the Real-Time Clock ............................................................................................ 6-10
Various System Trouble Displays..................................................................................................... 6-11
Testing the System............................................................................................................................... 7-1
About Test Procedures....................................................................................................................... 7-1
System Test........................................................................................................................................7-1
Go/No Go Test Mode .......................................................................................................................... 7-2
Dialer Communication Test .............................................................................................................. 7-3
Automatic Standby Battery Tests..................................................................................................... 7-3
Specifications & Accessories............................................................................................................. 8-1
SECURITY CONTROL...................................................................................................................... 8-1
COMPATIBLE DEVICES .................................................................................................................8-2
5800 Series Transmitter Input Loop Identification .........................................................................8-3
Limitations and Warranty..................................................................................................................9-1
Index ....................................................................................................................................................... 10-1
iv
SECTION 1
Features and Installation Highlights
•••••••••••••••••••••••••••••••••
This manual describes the installation of both the VISTA-12A and VISTA-12E. These units are identical except where noted.
Capabilities
Functions
Supports 2 independent partitions, which can protect two independent areas, as if each area had its own control.
Supports 1 common area partition that allows either of the other two independent partitions to arm, while leaving a common area (ex. lobby or foyer) disarmed for access into the remaining disarmed partition.
Supports up to 22 protection zones plus 16 keyfob zones (zones 49-64) for total of 38 zones:
-- 6 basic wired zones (zones 1-6) with optional zone-doubling/double-balanced zone feature
-- Up to 8 additional wired zones (zones 17-24) using an 8-zone 4219/4229 module.
-- Supports up to 16 wireless transmitter zones (5800 series; zones 9-24).
-- Supports up to 4 installer-configurable zone types
Up to 16 User Level Security Codes, each with separate authority levels and partition access
Downloading: Via an IBM compatible computer, Compass downloading software, and an ADEMCO CIA/CIA-EU modem.
Single-button arming feature: Can use dedicated keys to arm the system AWAY or STAY
Up to 8 Schedules, to control output devices, to determine when users have access, and/or to
auto-arm/disarm (or allow disarm) the system
Up to 2 Keypad macros, which can be activated by wired/wireless keypads
Paging feature allows certain system conditions to be reported to up to 2 pager phone
numbers; can use a dedicated key on keypads to send a signal to a pager
User programmable telephone number for audio “beeps” reporting of alarms to the user (follow-me feature).
Built-in Telephone Line Monitoring option can monitor the telephone line voltage and can cause a local display, or a display and trouble/alarm sound.
Event Logging records up to 254 selected events in a history log; control and readout from the log is done via ADEMCO Compass Downloader software or using an installer/master code at an alpha display keypad for local display.
Installer-customized zone descriptors for all zones (useful only when using alpha display keypads).
Optional siren supervision detects external sounder wiring short or open; causes a trouble condition, keypad display, and sends a report to the central monitoring station, if enabled.
Optional RF jam detection for wireless systems detects a condition that may impede proper RF reception (i.e., jamming or other RF interference); causes keypad display, sends a report to the central monitoring station (if trouble reporting is enabled), and can optionally send a tamper alarm if detected during the armed mode.
Individual user code selection for open/close reporting to central monitoring station (set when adding a user code, attribute 6).
1-1
Installation and Setup Guide
Compatible Devices
Supports up to 8 Addressable Keypads: 6148/6150 Fixed-Word Display Keypads, 6164 Alpha Keypad, 6128RF/6128RFH/6150RF/6160RF Keypad/Transceivers, 6160V Voice Keypad
Supports up to two (2) Touch Screen (AUI) Devices (Symphony, 6270), which are in addition to the standard eight (8) addressable keypads.
Supports a 4219 or 4229 addressable basic wired zone expander module
Supports 5881/5883 series receiver and 5800 series transmitters
Outputs up to 4 relays, two on-board triggers, and/or Powerline Carrier Devices (X-10 type)
-- Use any combination of 4204, 4229, 6164 relays and/or Powerline Carrier Devices.
-- Output functions (up to 12)
Alarm power output provides a 12VDC, 2 AMP output that can drive compatible sounders with a steady output for burglary/panic, or temporal pulse (3 pulses – pause – 3 pulses – pause – 3 pulses.) for fire. Uses current limiting circuitry for protection.
Auxiliary Power Output: 12VDC, 700mA maximum, including output triggers.
Backup Battery: Rechargeable (sealed lead-acid type) 12VDC, 6AH minimum.
Audio Alarm Verification (using AAV module, such as ADEMCO UVS); can be used in
conjunction with an output trigger to permit voice dialog between an operator at the central station and a person at the premises.
Alternative Communication Media: Primary telephone number messages can be reported via ECP connection to Ethernet TCP-IP Internet/Intranet Network Modules, or other network interfaces (e.g., EUREKA)
AC Power Supply:
VISTA-12A: Plug-in 230VAC power pack, XF1 Model No. 60844CK, Ap11V/99090/E148-36
VISTA-12E: 220VAC wired-in transformer, 16.5VAC 25VA
Important Installation Highlights (Installer Please Read)
This system uses addressable keypads and a Zone Expander Module (see table of addresses in
Programming Overview section).
Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.
Zone Expander Module must be set for specific address (08), based on the zone numbers used (see table of addresses in 4219/4229 Expansion Zones section).
4204 Relay Module must be set for specific address (13; see Connecting Relay Modules section).
6164 Keypads must be set for two addresses: a keypad address and a zone expander address (if
using the keypad’s expansion zones).
This control will not power-up unless AC mains is connected (will not power-up on battery alone). However, once the system is powered up, it will operate on battery power in the event of AC mains loss.
Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions (see Output Device Programming section).
This system supports programmable function keys. Use *57 Menu mode to define the function keys (see Function Key Programming section).
This system provides various paging features. Refer to the Programming Overview section for a summary on pager programming.
1-2
Mounting and Wiring the Control
SECTION 2
Mounting and Wiring the Control
•••••••••••••••••••••••••••••••••
This section describes the procedures for mounting and wiring this control and its peripheral devices. In the following subsections, procedures are listed in the left column, while notes and pertinent explanations are provided in the right column.
Cabinet and Lock
1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes.
2. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.
3. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until it is held securely by its snap tabs.
Notes
The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge.
CHECK
POSITION
LOCKED
UNLOCKED
CABINET DOOR
BOTTOM
PUSH
SNAP
TAB
ADEMCO
SNAP
TAB
ADEMCO
STEP 2STEP 1
PUSH
ON LOCK
UNTIL IT IS SEATED SECURELY
Figure 1. Installing the Cabinet Lock
cab_lock_snap-001-V0
2-1
Installation and Setup Guide
Mounting the PC Board
NOTE: The door of the metal cabinet may be removed to make it easier to install the PC board. Remove the door as follows:
1. With the cabinet laying on a flat surface, swing open the door to its full-open position.
2. Slide the door out of its retaining slots in the cabinet and store in a safe place.
3. Remove standoff (part number K0380) from the hardware bag and insert it into the square hole in the back of the cabinet so that it will align behind the lower left mounting hole in the PC board.
1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 21 22 23 25
4. Insert top of circuit board into slots at top of cabinet. Make sure that circuit board rests in slots as indicated in the diagram shown below.
5. Swing base of circuit board onto the raised cabinet tab and standoff.
6. Secure the sides of the PC board to the enclosure using the 2 screws provided.
Notes
Before installing the cabinet's contents, remove
the metal cabinet knockouts required for wiring entry. Do not remove the knockouts after the circuit board has been installed.
2-2
Figure 2. Mounting the PC Board
V12D-001-V0
Wiring to Keypads
1. Connect keypads to the control’s keypad terminals as shown on the Summary of Connections diagram.
Determine wire size using the Wiring Run
Chart below.
If power supervision is required, refer to the
Aux Power Supervision Connections paragraph at right.
2. Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right.
3. Program the keypad addresses, partition assignments and sound options in data fields *190-*196.
NOTE: Each keypad must be assigned a
unique address, starting at address 16. Keypads programmed with the same address will give unpredictable results.
Supplementary Power (optional)
1. Connect as shown. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control.
SUPPLEMENTARY
POWER SUPPLY
+
CONNECTIONS
DIRECTLY TO
TERMINALS AS
TO KEYPAD RED POWER WIRE (V+)
TO KEYPAD BLK GROUND WIRE (V-)
TO KEYPAD YEL DATA WIRE (<)
TO KEYPAD GRN DATA WIRE (>)
Figure 3. Using a Supplementary Power Supply
IMPORTANT:
MAKE THESE
SCREW
SHOWN.
CONTROL TERMINAL STRIP
AUX. DATA
AUX.
– 456 7
DATA
IN
OUT
+
TO KEYPAD BLK GROUND WIRE (V-)
TO KEYPAD RED POWER WIRE (V+)
TO KEYPAD GRN DATA WIRE (>)
TO KEYPAD YEL DATA WIRE (<)
pwr_sup_conn-008-V0
Mounting and Wiring the Control
Notes
Typical Fixed-Word Display: 6128RF/6148/6150/6150RF/6150V
Typical Alpha Display: 6160/6160V/6164
The system supports up to 8 keypads, which
can be assigned to partitions in any combination (see program fields *190-*196).
For single 4-wire runs, determine the current drain of all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.
Use supplementary power if the control’s aux. power load for all devices exceeds 700mA. Suggested power supply: AD12612
Aux Power Supervision Connections
To supervise aux power:
1. Use the Trigger Module terminals for ground and +12V connections (instead of main board terminals 4 and 5). See Trigger Module and On-Board Triggers section (page 2-17) for instructions on mounting the Trigger Module.
2. Connect the SUPV terminal to a zone (+) terminal.
3. Program that zone as a configurable zone type programmed as a 24-hour zone and with the desired report code (CID code 312 is recommended).
TOUCH SCREEN KEYPAD (AUI) NOTES:
•••• Use of up to two AUI devices (e.g., 6270, Symphony)
is independent from standard keypads and does not affect the number of standard keypads the system can support.
•••• AUI devices must be set for either address 1 or
address 2, depending on which unit is enabled in field *189.
•••• To ensure proper AUI device operation, connect
only to controls having microprocessor version 3.0 or higher, and use AUI devices with the following rev levels: 6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version 1.1.175 or higher.
2-3
Installation and Setup Guide
Keypad Addresses
Keypad Address Keypad Address
no. 1 16** no. 5 20 no. 2 17 no. 6 21 no. 3 18 no. 7 22 no. 4 19 no. 8 23
** The first keypad is address 16, which is always enabled and set for partition 1 with all sounds on.
Keypads powered from supplies that do not have a backup battery will not function if AC mains power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.
Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
TOTAL CURRENT DRAIN OF ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Wire Size
0.6mm O.D. 152m 76m 24m 15m 13m
0.8mm O.D. 228.6m 116m 40m 24m 20m 1mm O.D. 396m 198m 67m 40m 35m
1.2mm O.D. 457m 305m 100m 70m 52m
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, or TeleCommand Phone Module.
Maximum wire lengths for any device that is wired directly to the control can also be determined from the Wiring Run
Chart, based on the current drain of that device alone
The length of all wire runs for all partitions combined must not exceed 457m when unshielded quad conductor cable is
used (228m if shielded/screened cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.
50mA or less 100mA 300mA 500mA 600mA
.
2-4
V48so nder
001
V0
Sounder (Siren) Connections
1. Make sounder connections to alarm output terminals 3 (+) and 4 (–).
For supervised output, continue with steps 2 and
3.
2. Cut the red Siren Supervision Jumper located above terminals 2 and 3 on the control board.
3. Connect a 2k ohm resistor across the terminals of the last sounder.
TERMINALS
CUT RED JUMPER ON CONTROL BOARD TO ENABLE SIREN (SOUNDER) SUPERVISION.
ALARM
OUTPUT
TERMINALS ON
CONTROL BOARD
_
4
+
3
2
IF SIREN SUPERVISION IS ENABLED (RED JUMPER ON CONTROL BOARD IS CUT) CONNECT A 2000 OHM RESISTOR ACROSS THE EXTERNAL SOUNDER AS SHOWN BY THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR AT THE ALARM OUTPUT TERMINALS THEMSELVES!
Figure 4. Sounder Wiring (Supervised)
Notes
2-5 The 12VDC sounder output activates when an
alarm occurs.
Total current drain from this output cannot
exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to activate).
You must install a battery, since the battery
supplies this current.
Do NOT perform steps 2 and 3 if using a self-
activated siren.
EXTERNAL ALARM
SOUNDER
_
+
OBSERVE POLARITY
2000 OHM EOL RESISTOR
Wiring Table
Distance from control Wire Gauge
Up to 15m 0.8mm O.D. 15-30m 1.0mm O.D. 30-76m 1.2mm O.D.
Mounting and Wiring the Control
Wiring the AC Transformer
Transformer:
Connect the Transformer to terminals 1 and 2 on the control board. See wiring table at bottom of page for wire size to use.
Use wired-in or plug-in 110 (e.g., 1321)/220VAC transformer, with 16.5VAC, 25VA output.
VISTA-12A: XF1 Model 60844CK, Ap11 V/99090/E148-36
Using Powerline Carrier (X-10) Devices
If using Powerline Carrier (X-10) devices, a separate powerline modulator must be used, which is connected to the supplied Trigger Module via an SA4120XM-1 cable. See your local distributor for available modulators and connecting cable.
Notes
Use caution when wiring the transformer to the control to guard against blowing the
-
-
transformer fuse (the fuse is non-replaceable).
Wiring to the AC transformer must not exceed 76m using 1.2mm O.D. wire. The voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message will be displayed.
Do not connect to AC mains power while making any wiring connections to the control. As a safety precaution, always power down the control when making such connections.
2-5
Installation and Setup Guide
Backup Battery
1. Place the 12-volt backup battery in the cabinet.
2. After all connections to the control are completed and AC mains power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed.
Battery Saver Feature: The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored.
Earth Ground
Metal Cold Water Pipe or Earth Ground Rod:
Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe/rod to which the ground lead is electrically connected and secured.
Notes
IMPORTANT: The panel will not power up initially on battery power only. You must plug the transformer in first, and then connect the battery.
Operating on Battery Power Alone: To operate the control on battery power only, connect a jumper between the negative (–) battery terminal and control PCB terminal 4 (– aux power).
Notes
This product has been designed and tested to ensure its resistance to damage from generally expected levels of lightning and electrical discharge, and does not normally require an earth ground.
If an earth ground is desired for additional protection in areas of severe electrical activity, terminal 25 on the control board, or the cabinet, may be used as the ground connection point. The examples of good earth grounds listed at the left are available at some installations.
2-6
Mounting and Wiring the Control
AUXILIARY DEVICE CURRENT DRAIN WORKSHEET
DEVICE CURRENT # UNITS TOTAL CURRENT
6128RF Keypad/Transceiver 90mA standby/120mA alarm 6150RF Keypad/Transceiver 80mA standby/105mA alarm 6148 Fixed-Word Keypad 30mA standby/55mA alarm 6150 Fixed-Word Keypad 40mA standby/90mA alarm 6160 Alpha Keypad 40mA standby/150mA alarm 6150V Fixed-Word Display Voice Keypad 6160V Alpha Display Voice Keypad 6164 Keypad w/4-Zone Expander and Relay 5881 RF Receiver 35mA 5883 RF Transceiver 80mA 4219 Zone Expander 35mA 4204 Relay Unit
4229 Zone Expander/Relay Unit TeleCommand 55mA (standby)
* *
*If using wired devices such as PIRs or Dual Tecs, refer to the specifications for that particular unit's
current drain.
Figures are for relays OFF/relays ON.
60mA standby/160mA alarm
60mA standby/190mA alarm
115mA standby/190mA alarm
15/180mA‡ 35/100mA‡
119mA (local phone) 85mA (remote phone)
TOTAL =
(Current available from Aux. terminals = 700mA max.)
2-7
Installation and Setup Guide
Basic Wired Zones
Normally Open Zones/Normally Open EOLR
Zones
1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.
2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.
Normally Closed Zones/Normally Closed EOLR
Zones
1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.
2. Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt..
Double-Balanced: Connections as shown (resistors provided for one device in selected models); maximum of 8 sensors on each double­balanced zone.
IMPORTANT: Double-balanced zones provide unique tamper signaling on the same 2 wires used for alarm signaling, and should be used as burglary or emergency zones only. Do not use double-balanced zones as fire zones.
Zone Doubling: Connections as shown (resistors provided).
Notes
EOLR: If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone.
Zone 1 is intended only for EOLR usage.
Zone Doubling:
This feature provides two unique zone identifications for normally closed sensors connected to each basic wired zone (but does not increase the total number of zones supported by the control). Do not use zone doubling for fire zones. If enabled (Zone Programming mode, “Hardwire Type” prompt, option “3”), basic wired zones are automatically paired as follows:
Zone Paired with
zone
1 9 2 10 3 11 4 12 5 13 6 14
NOTE: A short across the EOL (i.e., at terminal) on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition (displayed at keypad as CHECK).
12 13
14
10 11
TAMPER
2k
CONTACTS
2k
ZONE 2
TAMPER
CONTACTS
2k
2k
ZONE 10
2k
ZONE 3
Double Balanced Zones Zone Doubling
2k
ZONE 4
zone-002-V0
2-8
Figure 5. Configuring Zones
3k
6.2k
zone-004-V0
Smoke Detectors
4-Wire Smoke Detectors
Connect 4-wire smoke detectors (up to 16,
depending on detector current drain) to any zone from 2-8 as shown on the next page. This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger 17 to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.
Figure 6. 4-Wire Smoke Detector Connections
5
+
AUX PWR
OUTPUT
TERMINALS
TO ZONE TERM. ( )
TO ZONE TERM. ( )
4-Wire Smoke Detector Using Relay for Power Reset
TO OUTPUT 17
PROGRAM OUTPUT 17
FOR "OUT NORM
LOW" = YES IN 79 MENU
MODE AND AS ZONE
TYPE 54 IN
80 MENU MODE
TO ZONE TERM. ( )
TO ZONE TERM. ( )
4-Wire Smoke Detector Using Output 17 for Power Reset
PROGRAM
(FIRE ZONE
_
4
CONTACT OPENS
MOMENTARILY UPON
FIRE ALARM RESET
+
_
+
( )
AUX PWR
_
( )
+
_
RELAY
AS ZONE
TYPE 54
RESET)
5
DETECTOR
DETECTOR
RELAY
N.C.
+
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
HEAT
+
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
HEAT
Mounting and Wiring the Control
Notes
•••• Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds for a second alarm trigger. If the smoke detector does not trigger again, the control will disregard the first trigger, and no alarm signal will occur. This feature eliminates false alarms from smoke detectors due to electrical or physical transients.
Maximum current for trigger 17 output for 4- wire smoke detectors is 300mA.
_
BLK
_
2000
OHMS
EOLR
BLK
_
2000
OHMS
EOLR
N.O.
VIOLET
_
VIOLET
N.O.
+
RED
+
EOL POWER SUPERVISION RELAY MODULE A77-716B. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.
RED
EOL POWER SUPERVISION RELAY MODULE A77-716B. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.
4_wiresmk-007-V0
4_wiresmk-008-V0
2-9
Installation and Setup Guide
4219/4229 Expansion Zones
1. Connect each module to the control’s keypad terminals.
If power supervision is required, use the Trigger
Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3).
2. Assign the module a device address of 08 using its DIP switches. The device address determines the zone numbers being used, as shown below.
Expander Module Addresses
Zones… Device Address…
17-24 08
3. Connect sensors to the module’s loops.
4. If using relays with the 4229, connect the desired field wiring to the unit's relay contact terminals.
RELAY
CONNECTOR
VIO
BLK
GRY
WHT
GND
NONCC
RLY
2
RELAYS OFF
YEL
NONCC
RLY
ORG
1
BRN
RELAY
NO C NC
REED
(TAMPER)
SWITCH
ZONES
2
TAMPER JUMPER POSITION
4229 IN CABINET (NOT TAMPER)
4229 REMOTE (TAMPER PROTECTED)
DIP SWITCH
FOR SETTING ADDRESS AND ZONE "A" RESPONSE
RELAY
1
2
1
3
B
A
4 6
5
C
D
7
Notes
Supports up to 8 expansion zones (NO or NC) using 4219/4229 Zone Expander Modules as follows:
Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229 modules. (End-of line resistors used on the control terminals are 2000 ohms.)
Expansion zones have normal response time (400–500 msec), except zone connected to each module’s loop “A,” which can be set for fast response (10–15 msec).
4229
EITHER OR BOTH CAN BE USED
4-PIN CONSOLE PLUG
TB1
8
9
11
10
E
GH
F
TB2
GRN
BLK
RED
YEL
DATA OUT (>) TO CONTROL
(–) GROUND
(+) 12VDC
DATA IN (<) FROM CONTROL
4
3
4 3
2
2
1
1
12
TERMINATE EACH PROGRAMMED ZONE WITH 1000 OHM (1K) END-OF-LINE RESISTOR (EACH ZONE'S MAX. LOOP RESISTANCE 300 OHMS + EOL)
CONTROL PANEL
TERMINALS ON
(TERM 6)
(TERM 4)
(TERM 5)
(TERM 7)
Figure 7. Wiring Connections, 4219 & 4229 (4229 shown)
2-10
4229-002-V0
D
U
6164 Keypad Expansion Zones
1. Connect each keypad to the control’s keypad terminals.
If power supervision is required, use the
Trigger Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3).
2. Using the keypad’s program mode, assign the keypad a unique keypad address (16-23), and assign a device address of 08 that provides expansion zones 17-20.
3. Connect sensors to the keypad’s zone terminals.
4. If using the keypad relay, connect the desired field wiring to the keypad's relay contact terminals.
See 6164 Keypad Instructions for other
mounting, wiring, and programming information.
Notes
Each 6164 keypad supports up to 4 wired expansion EOLR or double-balanced zones and one relay output.
Use 2000 ohm end-of-line resistors at the end of loops connected to the 6164 keypads.
Mounting and Wiring the Control
Enter 6164 keypad program mode by pressing and holding down both the [1] and [3] keys within 60 seconds of power up.
Enable the keypad addresses using data fields *191-*196 as required.
Program keypad zones using *56 Menu mode. Keypad zones 1-4 correspond to the respective groups of zones shown in the chart at left, where keypad zone 1 is the lowest zone number in each group.
DOUBLE BALANCED
2K
2K
N.O.
C.
N.C.
2K
TAMPER
CONTACTS
TAMPER
CONTACTS
Z1
Z2
OPTIONAL
(Z1
(Z3
&
Z2)
Z4)
CONVENTIONAL EOLR
2K
[Y] DATA IN
N.O.
N.C.
Y +
Z4
Z3
&
[+] +12VDC
[-] GROUN
[G] DATA O
G
2-11
Installation and Setup Guide
Installing the RF Receiver
Use one of the following receivers:
RF Receiver Number of Zones
5881ENL up to 8 (including keyfob buttons) 5881ENM up to 16 (including keyfob buttons)
1. Set Device Address to “00” as described in its instructions (set all switches to the right, “off” position).
2. Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 67m.
3. Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the other end of the harness into the receiver. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc.
If power
Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3).
supervisio n is required, use the Trigger
Notes
The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if communication between the panel and receiver is interrupted, or if no valid RF signals from at least one supervised transmitter are received within 12 hours.
Only one receiver can be installed in a system.
If the receiver is mounted remotely:
Place the RF receiver in a high, centrally located area for best reception.
Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or block transmissions.
Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged lighting of the LED in the receiver; random flicker is OK).
Do not locate RF receiver closer than 3m from any keypads to avoid interference from the microprocessors in those units.
Figure 8. 5881EN RF Receiver (cover removed)
2-12
WIRELESS ZONE NUMBERS
transmitter zones 9-24 button or transmitter zones 49-64
Mounting and Wiring the Control
Installing a 5800TM Module
1. Mount the 5800TM next to the RF receiver (between one and two feet from the receiver’s antennas) using its accompanying mounting bracket. Do not install within the control cabinet.
2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on the Summary of Connections diagram and set to address 28.
Notes
Use this module only in 345Hz RF systems and if you are using one or more wireless bi-directional keypads or keyfob; 5800TM is not necessary if using a Transceiver (e.g., 5883).
The 5800TM must be set to address 28 (cut red-W1 jumper).
The 5800TM can be used in partition 1 only.
For additional information regarding the 5800TM, refer to the 5800TM’s
Installing the Transmitters
1. To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test (see the Testing the System section).
2. Install transmitters in accordance with the
instructions provided with each.
3. Set 5827, 5827BD, 5804BD wireless keypads to
the programmed House ID (field *24), using its DIP switches (5827) or follow the instructions provided with the device.
instructions.
Notes
Refer to the table of compatible devices at the back of this manual.
Supervised transmitters† send check-in signals to the receiver at 70-90 minute intervals. If at least one check-in message is not received from each transmitter within a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed.
Hand-held transmitters (e.g., 5802, 5802CP, 5804,
5804BD, 5827, 5827BD) do not send check-in signals.
Transmitter Battery Life
• See Wireless Transmitter paragraph in the Limitations of This Alarm System statement located at the end of this manual for information on transmitter battery life.
• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable batteries, and no battery installation is required. At the end of their life, the complete unit must be replaced (and a new serial number enrolled by the control).
• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically tested for battery life.
• The 5802MN, 5802MN2, and 5804 Button Transmitters have replaceable batteries.
Do not install batteries in wireless transmitters until you are ready to enroll during system programming. After enrolling, batteries need not be removed.
2-13
Installation and Setup Guide
Installing a Keyswitch
1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s terminals (zones 2-8). Remove the 2000 ohm EOL resistor if connected across the selected zone.
2. Using a standard keypad cable as shown: Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).
Connect the Red and Green LED wires to the
appropriate output 17/output 18 trigger connector pins.
3. Connect a 2000 ohm EOL resistor across the momentary switch.
4. You can wire an optional closed-circuit tamper switch (model 112) in series with the zone. If the switch plate is then removed from the wall, the tamper will open, disabling keyswitch operation until the system is next disarmed from the keypad.
If the tamper is opened when the system is
armed, an alarm will occur.
Notes
Use 4146 keyswitch or any normally open keyswitch.
Use only one keyswitch per partition.
If using a keyswitch in more than one partition,
you must use relays (not the on-board triggers) for the Red/Green LED functions (step 2).
When using a keyswitch, the zone it is connected to is no longer available for use as a protective zone.
Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.
Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see Output Device Programming section).
8-PIN TRIGGER CONNECTOR
1345678
KEY
(RED)
(YELLOW)
OUTPUT 17
(GREEN)
+12 AUX.
OUTPUT 18
11
TYPICAL ZONE
ON CONTROL
BOARD
10
4-WIRE CABLE
YELLOW
WHITE
BLACK
BROWN
RED
BLUE
(ARMED)
RED
(READY)
GREEN
4146 KEYSWITCH
820
ohms
TAMPER
SWITCH (N. C.)
BROWN
LOCK
SWITCH (N. O.)
BLUE
EOLR
(use appropriate value)
820
ohms
Figure 9. Keyswitch Wiring Connections
00-trigcon-004-V2
2-14
Connecting Relay Modules
1. Mount either remotely or in the control panel.
2. Connect to control’s keypad terminals using the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs.
If power supervision is required, use the
Trigger Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3).
3. Set the module’s device address according to the table at right.
4. Connect the desired field wiring to the unit's relay contact terminals.
Notes
Use 4204/4229 modules or 6164 keypad.
Supervision: 4204/4229 modules and 6164
keypad are supervised against removal. The module’s device address is displayed as follows if a module is disconnected from the control’s terminals, or if the module cover is removed and the tamper jumper is installed:
Alpha: CHECK xx Wire Expansion FAULT xx Wire Expansion TAMPER xx Wire Expansion ALARM xx Wire Expansion
Fixed-Glass: lxx (or 91 if field *199 set for 2-digit
display)
where “xx is the module’s address.
If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed in their respective partitions.
Mounting and Wiring the Control
Relay Module Addresses 4204/6164
Address 4229/6164
††
Address
2 13 (zn 17-24) 08
† Use these addresses if using only relays
with the 6164 and not its zones.
†† Use these addresses if using zone
expansion and relays with the 6164; supports only the first four zones in parenthesis. NOTE: You can not use a 4229 and 6164 in the same system.
††† Not available if zone doubling used.
Figure 10. 4204 Connections to Control
(4229 Module connections and 6164 optional keypad connections are shown in the Expansion Zones section on pages 2-10 and 2­11, respectively)
2-15
Installation and Setup Guide
Powerline Carrier Devices
1. Install up to 4 powerline carrier devices (if no relays are used) according to the instructions included with each.
2. Connect the Powerline Interface Modulator to the Trigger Module connector using SA4120XM-1 cable as shown below.
3. Use Programming Mode to enter the device
house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.
(USE SA4120XM-1CABLE)
Notes
When using Powerline Carrier devices, you must use a Powerline Carrier Device Modulator. It supplies signals from the control panel through the premises AC mains wiring to the Powerline Carrier devices (which are plugged into AC outlets). You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads.
NOT USED
SUPV
TRIG 1
123 4 56
78
TRIGGER MODULE
Trigger Module Powerline Interface Connections
TRIG 2
( ) VTRIG
+
( ) AUX
+
( ) GND
-
DATA (BLU)
COM (VIO) SYNC BLK)
TO X-10 TRANS.
V48A-V48E-004-V0
2-16
Trigger Module and On-Board Triggers
IMPORTANT: Make all wiring connections to
the Trigger Module before mounting the module to the PC board.
1. Connect field wiring to the desired trigger terminal on the trigger module (TRIG 1 = output 17; TRIG 2 = output 18) and the VTRIG +12V terminal.
For supervised trigger operation, refer to the
following:
Trigger Voltage/Aux Power Supervision
To supervise trigger voltage and/or aux
power:
A. For Aux Power: Use the Trigger Module
terminals for ground and +12V connections (instead of main board terminals 4 and 5).
For Trigger Voltage: Connect trigger
wiring as described in step 1 above.
B. Connect the SUPV terminal on the
Trigger Module to a zone (+) terminal.
C. Program that zone as a configurable zone
type programmed as a 24-hour zone and with the desired report code (CID code
2. If using a Powerline Interface Modulator and
3. Install the Trigger Module by aligning its 8-
312 is recommended).
powerline carrier devices, use the SA4120XM-1 cable (part of 4120TR Trigger Cable). See previous Powerline Carrier Device section.
pin header over the main PC board’s 8-pin connector (orient the Trigger Module as shown on the Summary of Connections diagram), then press down firmly until the Trigger Module’s standoffs are seated on the main PC board.
Mounting and Wiring the Control
Notes
There are two on-board triggers that can be used to activate output devices.
These outputs are normally high, and go low upon programmed condition.
The outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.
Program these triggers using *80/*81 Menu modes as you would for any other relay output.
When using these outputs, note:
pin 1 = output number 17 (trigger 1): 15 ohms to ground when closed
(output low), open when off (output high, normal default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module that draws less than
300mA. pin 5 = output number 18 (trigger 2): 15 ohms to ground when closed
(output low); open when off (output
high, normal default); or can
support 12V relay module that
draws less than 300mA.
NOTE: Do not exceed 700mA combined
current for both triggers and aux
power. Doing so can damage PC
board components and will void the
system’s warranty.
2-17
Installation and Setup Guide
Figure 11. Trigger Module
Phone Line Connections
VISTA-12E
Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram. Wire colors represent the colors of the cable to the RJ31X jack.
VISTA-12A
Plug the phone line plug into the modular phone connector mounted on the PC board.
Alternative Communications Media (ACM) Connections
Connect the data in/data out terminals and voltage
input terminals of the ACM to the control's keypad connection points.
Set the ACM’s address to “03” following the
instructions provided with the ACM.
ABLE)
V48A-V48E-001-V0
Notes
If you are using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.
CAUTION: To reduce the risk of fire, use only
0.6mm O.D. or larger telecommunication line
cord for phone line connections.
Notes
Use compatible ACMs (e.g., 7845i, AI4164RS, or AI4164ETH).
2-18
Audio Alarm Verification Connections (AAV, “Listen-In”)
Refer to the connection diagram below. Connections use one of the on-board triggers.
Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250
AUXILIARY AUDIO LEVEL ADJUSTMENT
TRIM POT
UVCM MODULE
NOTE:
REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.
SWITCH
SWITCH
BANK 2
BANK 1
1 = ON
1 = OFF 2 = OFF 3 = OFF 4 = OFF 5 = OFF 6 = OFF 7 = OFF 8 = ON
2 = ON 3 = OFF 4 = ON 5 = ON 6 = ON 7 = ON 8 = ON
ON ON
SWITCH BANK 2
FALLING VOICE TRIG
SWITCH BANK 1
12345678 12345678
GND
+12VDC IN
CONTROL
29 30 31 32 33 34
1234567891011
Mounting and Wiring the Control
Notes
Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode (select zone type “60”).
For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7, and program the zone as zone type 81 (*56 Menu mode).
E.g., Using output 18 for the trigger,
program an output function in *80 Menu mode as:
ZT = 60, P = 0, Action = 1, Device = 18
4
GND
5
+12VDC
5
OUTPUT 18
TRIGGER CONNECTOR
ZONE
TERMINALS
EOL
21
RING
TIP
OPTIONAL MONITORING ZONE CONNECTION (USE ZONE TYPE 81)
23
22
24
RED (R)
GREEN (T)
GREY (R)
BROWN (T)
25
PREMISES
HANDSET
EARTH
GROUND
RJ31X
TO
INCOMING
PHONE LINE
aav_uvcm-003-V0
Figure 12. Connection of AAV Unit
2-19
Installation and Setup Guide
2-20
SECTION 3
Programming Overview
•••••••••••••••••••••••••••••••••
About Programming
You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s office/home, using an IBM compatible personal computer, a CIA/CIA-EU modem, and Compass downloading software.
The following is a list of the various Programming modes used to program this system:
Programming Mode… Used to …
Data Field Programming Program basic data fields used for setting the various system
options. Most of the data fields in this system have been programmed for specific default values. However, some fields must be programmed for each particular installation to establish its specific alarm and reporting features.
56 Zone Programming Assign zone characteristics, report codes, alpha descriptors, and
serial numbers for RF transmitters.
57 Function Key Programming Program each of the four function keys to perform one of several
system functions.
58 Zone Programming Assign zone attributes similar to 56 mode, but provides a faster
(Expert Mode) programming procedure and is intended for those more exper­ ienced in programming controls of this type.
79 Output Device Mapping Assign device addresses used by 4229/4204 Relay modules or
6164 keypad and map specific relays and device outputs, and assign unit codes for Powerline Carrier devices
80 Output Definitions Define up to 12 output definitions which can control the output
relays mapped using *79 Output Device Mapping mode.
81 Zone List Programming Create Zone Lists for relay/powerline carrier zones, chime zones,
night-stay, exit route zones, final exit door zone, and pager zones.
82 Alpha Programming Create alpha descriptors for easy zone identification. Scheduling Mode (code + [#] +64) Create schedules to automate various system functions or
determine user access.
3-1
Installation and Setup Guide
Zones and Partitions
Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or *58 Expert Programming mode. Refer to those sections for detailed procedures. The system can control three independent areas of protection (known as partitions) for use by independent users, if desired. Partitioning involves simply assigning zones to one of the three partitions during zone programming:
The user’s partition number can be displayed on keypads by enabling data field *198.
The system, by default, automatically distributes users among the three partitions.
The master user can change the user number distributions.
Zones can also be assigned to a common area partition if partition 3 is so designated, which is
an area shared by users of the other two partitions (such as a lobby in a building).
Common area partition allows either of the independent partitions to arm, while leaving the common area partition disarmed for access into the other partition.
The following describes the functioning of the common area partition, if used:
-- The common area sounds and reports alarms only when both the other partitions are armed. If only one partition is armed, the system ignores faults in the common area.
-- Either partition may arm its system if the common area is faulted, but once armed, the other partition will not be able to arm unless the common area zones are first bypassed or their faults are corrected.
-- Faults in the common area are displayed on common area keypads, and will also appear on another partition’s keypad when that partition is armed.
Either partition can clear and restore the common area after an alarm.
3-2
Programming Overview
Keypads
Keypads are identified by predefined addresses (starting at address 16) as follows:
Address Keypad Program Field
16 17 18 19 20 21 22 23
keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8
always enabled for partition 1, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
To enable keypads:
1. Set desired address at keypad (refer to keypad’s instructions for setting the address).
2. Use data field program mode to enable keypad addresses, assign a partition, enable sound options in fields *190-*196 as shown in the table above.
3. If desired, use data field *198 to turn on the display of the partition number.
4. Set the following keypad-related data fields as required by the installation: *21 Quick Arm Enable ∗180 Zone Bypass Limit *23 Forced Bypass 186 Display Options 25 Arming Prevention Override 188 Keypad Sabotage Options *84 Auto STAY Arm
197 Exit Time Display Interval
*86 Exit Options NOTE: Do not use this option if Telecommand is
installed to permit remote end-user control of the system.
NOTE. First keypad is address 16
Wireless Receiver Transmitters, and Wireless Keys (keyfobs)
Receiver: Set the receiver’s address to “00” using its DIP switches, then set the following options:
*22 RF Jam Option *24 RF House ID Code (if using DIP switch equipped wireless keypads) for each partition 25 Arming Prevention Override *67 Transmitter Low Battery Report Code *75 Transmitter Low Battery Restore Report Code
173 RF Reporting Options 178 RF Supervision/RF Jam Options
Use *56 Menu mode to program wireless zones 9-24 and wireless button zones 49-64.
Transmitters: Use *56 or *58 Zone Programming Menu modes to program zone information and enroll
transmitters (zones 9-24, buttons 49-64).
Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone Programming
Menu mode to program zone information and enroll each button of the wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before it becomes active. See Adding/Deleting Security Codes section for procedure.
3-3
Installation and Setup Guide
Pager Programming
The system can send various reports to up to 2 pagers. To program pager reporting, do the following:
1. Enter the appropriate information in the following data fields: *160, *163 Pager Phone Numbers (for pagers 1and 2 respectively) *161, *164, Pager Prefix Characters (for pagers 1 and 2 respectively)
*162, *165, Pager Reporting Options by Partition† (for pagers 1 and 2 respectively)
2. Enable Pager Delay, if desired, in field *166 (delays alarm reporting for ALL pagers).
3. Enable appropriate user open/close pager reports using the user attribute command (master code + [8] + user no. + [#] [5] + [1]). Users that perform actions in their assigned
partition will, if enabled, attempt to report to all pagers enabled for open/close reporting in that partition.
4. If using child-not-home pager report, define the report schedule using Scheduling mode
(master code + [#] [6] [4] then select event type “03”).
5. If using a function key to manually send a message to a pager, see Function Keys paragraph
below.
6. If reporting zone alarms and troubles to a pager, use *81 Zone List menu mode to assign the
zones associated with each pager (zone lists 9-11).
Function Keys
To assign functions to the function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency
zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.
If using a function key to activate a relay action (*57 Menu mode key function 07), use *79 Menu mode
to map the output, and use *80 Menu mode to define the output’s action; select system operation type “66.”
If using a function key for a user macro, use *57 menu mode to activate the desired key, then define the
actual macro functions using the user code + [#] + [6] [6] command.
Output Devices
To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for scheduled automatic activation, simply map the device using *79 Menu mode.
To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map the device, then use *80 Menu mode to define the automated device action.
If the device action is based on more than one zone, use *81 Zone List menu mode to assign the zones.
3-4
Loading...
+ 82 hidden pages