Honeywell V8043F, V4043, V8043A, V8043B, V8043E User Manual

V8043A,E,F 5000 Series
APPLICATION
These valves consist of a motorized actuator and valve assembly for controlling
the flow of hot water to a heat exchanger such as a radiator, convector, finned baseboard radiator, or infloor radiant coil for space temperature control. The V8043 5000 series valves provide two-position, straight through control of supply water at up to 300 psi operating pressure.
Quick Fit actuator provides easy snap on and
off connection to the valve assembly.
SPECIFICATION
ZONE V ALVES
Patent Pending
Actuator Electrical Rating:
24Vac 60 Hz, 0.30 A Current Draw, 5 W, 7.2 VA maximum
Electrical Connection:
18” leads or screw terminal board
Auxiliary Switch Rating:
120V, 4.4A running, 26.4A Inrush (60 Hz); 50 VA Pilot duty at 24 V.
Fluid Temperature:
Standard models (class F motor): 200° F (93° C) Max.
Ambient Temperature:
125° F (52° C) Max.
Humidity Limits:
95% Relative Humidity, Non-condensing
Shipping and Storage Temperature:
-40° F to 150° F (-40° C to 65° C).
Atmosphere:
Non-corrosive, non explosive.
Maximum Soldering Temperature:
500° F (260° C). Rubber ball plug must be moved away from the seat for soldering.
Maximum System Pressure Rating:
300 psi (2000 kPa), PN20.
Flow Characteristics:
Quick opening for on-off application. Slow return for water hammer resist.
Maximum Close-off Rating (@ Flow Capacity Rating) :
20 psi (@ 3.5 Cv) 8 psi (@ 8 Cv)
Actuator Materials:
Case:galvanized steel. Cover : zinc plated steel. Sector gear: Brass
Valve Material:
Body of forged brass; drive shaft stem of stainless steel; ball plug of Buna-N rubber; o-ring seals of EPDM rubber.
Service Medium:
Suitable for glycol/water mix up to 50:50 use in closed hydronic systems. Not for
use with oxygenated water, potable water or steam.
Use this valve in hydronic systems which do not contain dissolved oxygen in the
system water. The dissolved oxygen, which is found in systems that have a frequent source of make-up water, causes the rubber plug inside the valve to deteriorate and eventually fail.
Approvals:
CSA C/US Certified to Canadian Standards Association and Underwriter's Laboratories Standards.
MODELS
V8043 (Straight through, Normally Closed)
V8043A: Leadwires V8043E: Leadwires and End Switch V8043F: Terminal Board and End Switch
2004.09 Printed in Canada
1
Form No. 95C-10932
1
HEIGHT NEEDED TO REMOVE COVER.
2
DIMENSIONS FOR 1/2 IN. COPPER TUBING. DIMENSIONS FOR 3/4 IN COPPER TUBING.
3
DIMENSIONS FOR 1 IN. COPPER TUBING.
4
4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL
5
BOARD ENCLOSURE. V4034B AND V8043B VAL VES THAT ARE
6
NORMALLY OPEN IN THE DE-ENERGIZED POSITION HAVE NO MANUAL LEVER.
REFER TO MOUNTING INSTRUCTIONS.
7
OPENING FOR 1/2 IN. CONDUIT ON MANUAL
8
LEVER SIDE FOR V4043, V8043.
Fig. 1 - Mounting Dimensions in in. (mm in Brackets)
M10175.A4
V4043, V8043 SWEAT COPPER CONNECTION MODELS
3-1/2 (89)
1-3/4
(44)
A B
1-5/16
(33)
1-3/8 (35)
1-11/16
(43)
7/8 DIA. (22)
8
1-1/2
(38)
15/32 (12)
AUTO
2-3/8
(60)
MAN OPEN
5-1/4 (133)
1
3/8 (10)
IN
1-3/4
(44)
2-5/8 (66)
2-3/4 (70)
3-3/8
(86)
6
5
OUT
7
2
3
4
CAUTION
1. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
2. Normally it is not necessary to remove the actuator from the valve body during installation. If the valve must be disassembled, be certain that it is reassembled with the water flow in the direction of the arrow. Reversal of the actuator results in damage to the gear train.
3.
On 24V systems, never jumper the
valve coil terminals even tempor arily. This can burn out the heat anticipator in the thermostat.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Location
Install the valve in an area with adequate clearance to:
- Move the manual opening lever on the side of the actuator
- Remove the actuator cover
- Wire the actuator
Replace the actuator motor
-
The valve location should be in an area where the temperature does not exceed the maximum valve operating ambient temperature and fluid temperatuare.
Manual Lever
The V8043 normally closed valves can be opened manually by moving the manual lever slowly and firmly to the MAN. OPEN position and pushing up to the stop. The stop permits the valve to be locked in the open position. The valve returns to automatic position when it is energized.
2
R
L1 (HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
END SWITCH
TO CIRCULATOR OR ANOTHER VALVE
TH
TR
24V TRANSFORMER
THERMOSTAT (TYPICALLY T87F)
TH TR
M5952
MOUNTING
The valve can be mounted in any position on a vertical line. See Fig. 2. If the valve is mounted horizontally; the actuator must be even with or above the center line of the piping. Make sure to leave enough room above the actuator to remove the cover for servicing.
thermostat or controller connected to the valve so that the valve runs through its cycle. Make sure the valve runs smoothly and positively from closed to open to closed again. (See Operation and Checkout Sections.)
Mount the valve directly in the tube or pipe after the coil.
Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body.
HORIZONTIAL PIPING
VERTICAL PIPING
Fig. 2 - Mounting Positions
M10162
Sweat Copper Models
1. Use new, properly reamed pipe, free from dents or corrosion.
2. Place the valve on the pipe. Set the manual opening lever to MAN. OPEN position before applying heat. This protects the plug inside the valve by removing it from the seat.
3. Sweat the joints, keeping the outer surface free from solder. DO NOT use silver solder because of the high melting temperature required.
TO INSTALL A COMPLETE VALVE (V8043):
1. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
2. Install valve into pipe on the return side of the coil. (See Mounting Section.)
3. Make wiring connections to valve. (Refer to Wiring section for proper instructions.)
4. Inspect the valve installation to ensure that all connections and adjustments have been correctly made.
Adjust the
TO REMOVE THE ACTUATOR FROM THE VALVE BODY (See Fig. 3)
NOTE!
It is not necessary to drain the hydronic system if the valve body assembly remains in the pipe line.
1. Switch power supply OFF. Disconnect electrical leads carefully, noting the position and colour of each lead.
2. Place the manual lever in the MAN. OPEN position.
3. Remove actuator by fully depressing spring release button and lift it straight off of the body .
1. PLACE MANUAL
AUTO OPEN
2. DEPRESS LOCKING BUTTON
Fig. 3 - Removing Actuator from Valve Body
LEVER IN OPEN POSITION
3. LIFT ACTUATOR STRAIGHT UP
TO INSTALL REPLACEMENT ACTUATOR ON THE VAL VE BODY
1.
Align the parallel flat surfaces in double-D shaft of valve body with notch in side of body (i.e. 90 flow.) See Fig. 4.
This makes actuator
to water
°
attachment easier.
2. Wiring connections may be made either before or after actuator installed on valve body.
3.
Place the manual lever on the actuator in the MAN. OPEN position.
3
Loading...
+ 7 hidden pages