V5011R
INTERNAL THREADED END-CONNECTION LINEAR VALVE PN16
PRODUCT DATA
Single seated control or shutoff valve for:
•hot water;
•chilled water;
•saturated steam;
•superheated steam;
•domestic hot water;
•Brass body with internal threaded end connections
•Low seat leakage rate
•Self-adjusting packing
•Accurate positioning to ensure state-of-the-art temperature control
•Directly-coupled electric and pneumatic actuators for easy mounting
Action: |
Stem down to close |
Nominal pressure rating: |
PN16 |
Flow characteristic: |
equal percentage |
Rangeability: |
50:1 |
Leakage rate: |
≤0.05% of kvs |
Stroke: |
20 mm |
Valve body: |
|
Pipe connections: |
Internal threading as per ISO228 |
Material: |
Brass |
Dimensions: |
See Fig. 1 on page 3 |
Trim: |
|
Seat: |
DN15: stainless steel |
|
DN20...50: body integrated |
Plug: |
Brass |
Stem: |
Stainless steel |
Packing: |
Spring-loaded carbon fiber |
Medium temperature and |
reinforced PTFE V-rings |
|
|
pressure: |
|
Water |
2 to 120 °C max. 1600 kPa |
|
120 to 170 °C max. 1490 kPa |
Steam |
< 120 °C max. 150 kPa |
Max. temperature differen- |
|
tial in alternating hot/cold |
|
water use: |
60 K |
in heating, ventilation, air conditioning systems, and open circuits.
Operated by
•electric linear actuators (e.g. ML6420/25, ML7420/25, M6421, and M7421) and
•pneumatic actuators (e.g. MP953).
Registered Trademark |
EN0B-0064GE51 R0403 |
Copyright © 2003 Honeywell Inc. • All Rights Reserved |
|
V5011R
Table 1. Size and flow capacity (in m3/h)
Order Number |
Valve size |
kVS m3/h |
|
|
|
V5011R1000 |
DN15 |
0.63 |
V5011R1018 |
DN15 |
1 |
|
|
|
V5011R1026 |
DN15 |
1.6 |
|
|
|
V5011R1034 |
DN15 |
2.5 |
|
|
|
V5011R1042 |
DN15 |
4 |
|
|
|
V5011R1059 |
DN20 |
6.3 |
|
|
|
V5011R1067 |
DN25 |
10 |
|
|
|
V5011R1075 |
DN32 |
16 |
|
|
|
V5011R1083 |
DN40 |
25 |
|
|
|
V5011R1091 |
DN50 |
40 |
|
|
|
Water should meet VDI2035 requirements.
Do not install valve with stem below the horizontal.
Fluid flow must correspond with the arrow direction on the valve body.
The installation of a strainer is strongly recommended.
Repair packing kit for red-brass models (old) – RG5 DN15...32: Order number 0901786
DN40...50: Order number 0901787
Repair packing kit for yellow-brass models (new) – DR DN15...50: Order number 0901787
Table 2. Close-off pressure ratings (in kPa) of electric actuators
actuator |
|
|
|
|
|
|
|
|
|
valve size |
|
|
|
|
|
||||||||
type |
|
|
force |
|
DN15 |
|
DN20 |
|
|
DN25 |
|
DN32 |
DN40 |
|
|
DN50 |
|||||||
ML6420 / ML6425 |
|
600 N |
|
1600 |
|
1600 |
|
|
1000 |
700 |
|
460 |
|
|
260 |
||||||||
ML7420 / ML7425 |
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
M6421 / M7421 |
|
|
1800 N |
|
- |
|
|
- |
|
|
1600 |
1600 |
|
1500 |
|
|
850 |
||||||
Pneumatic Actuators MP953 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
Table 3. Close-off pressure ratings (in kPa) of pneumatic actuators MP953 |
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
actuator |
|
|
|
|
|
|
|
|
|
valve size |
|
|
|
|
|
|||||||
type |
|
spring range |
|
|
air |
|
DN15 |
|
DN15 |
|
DN20 |
|
DN25 |
|
DN32 |
|
DN40 |
DN50 |
|||||
|
|
pressure |
kvs0.63-2.5 |
|
kvs4 |
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
MP953C5001 |
|
|
14...48 kPa |
|
|
|
|
1600 |
|
1600 |
|
1400 |
|
760 |
|
520 |
|
280 |
140 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MP953C5027 |
|
|
27...76 kPa |
|
|
|
|
1600 |
|
1150 |
|
670 |
|
350 |
|
230 |
|
100 |
40 |
||||
MP953A5005 |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MP953C5019 |
|
|
55...83 kPa |
|
115 kPa |
|
1600 |
|
860 |
|
490 |
|
240 |
|
150 |
|
50 |
10 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
MP953C5068 |
|
|
14...48 kPa |
|
|
1600 |
|
1600 |
|
1600 |
|
1600 |
|
1600 |
|
1130 |
630 |
||||||
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MP953C5084 |
|
|
27...76 kPa |
|
|
|
|
1600 |
|
1600 |
|
1600 |
|
1500 |
|
1050 |
|
600 |
320 |
||||
MP953A5039 |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MP953C5076 |
|
|
55...83 kPa |
|
|
|
|
1600 |
|
1600 |
|
1600 |
|
1190 |
|
830 |
|
460 |
250 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
MP953D5025 |
|
|
27...76 kPa |
|
0 kPa |
|
1600 |
|
1600 |
|
1050 |
|
570 |
|
390 |
|
200 |
90 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
MP953D5009 |
|
|
55...90 kPa |
|
|
1600 |
|
1600 |
|
1600 |
|
1400 |
|
980 |
|
550 |
300 |
||||||
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
MP953B5003 |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
EN0B-0064GE51 R0403 |