V2047
GB type TRV Body
RADIATOR VALVE WITH OPTIONAL FLOW DIRECTION
PRODUCT DATA
Application
Thermostatic radiator valve bodies (TRV bodies) are fitted on
the supply or return of radiators or heat exchangers. Together
with a radiator thermostat, for example the Thera-3, they
control the room temperature by regulating the flow of hot
water into the heat exchanger. The temperature of different
rooms is controlled individually and energy is saved.
GB type TRV bodies have quiet operation and are fitted to the
supply or return of radiators on one-pipe or two-pipe systems
with medium to high flow rates. The GB type has optional flow
direction.
The valve insert can be replaced while the system is running
and without draining using the service tool (see ‘Accessories’
on page 2).
GB type TRV bodies are suitable for all Honeywell radiator
thermostats with M30 x 1,5 connection and 11,5 mm closing
dimensions.
Design
The thermostatic radiator valve body consists of:
• Valve housing PN10, DN15 with external thread connections to DIN/ISO228
• Valve insert with UBG-R type cartridge
• Two compression fittings, also suitable for supplied ex-
tended radiator tailpiece
• Protection cap
Materials
• Valve housing made of nickel-plated red bronze
• Valve insert made of brass with EPDM O-rings and soft
seals and stainless steel spindle
• Protection cap made of white plastic
• Nuts and tailpiece made of nickel-plated brass
Features
• Optional flow direction
• Suitable for the supply and return
• For heating systems with medium flow rates
• Dimensions according to HD1215, Part 2, Series GB
• Valve insert can be replaced while system is operating
and without draining the system
• Valve opening spring is not in the water
• Standard M30 x 1,5 thermostat connection
Specifications
Medium
Operating temperature
Operationg pressure
Differential pressure
vs (cv)-value
k
Body to head thread
Closing dimension
Stroke
Heating water, water quality to
VDI2035
max. 130°C (266°F)
max. 10 bar (145 psi)
max. 1 bar (14,5 psi) –
max. 0,25 bar (3,6 psi) recommended for quiet operation
2,10 (2,46) normal flow direction
1,90 (2,22) reverse flow direction
M30 x 1, 5
11,5 mm
2,5 mm
Copyright © 2002 Honeywell AG • All rights reserved EN0H-0061GE25 R0402
GB TYPE TRV BODY (V2047)
Function
Thermostatic radiator valves enable individual control of room
temperature and thus save energy.
The TRV body is controlled by the radiator thermostat. Air
from the room passing over the sensor of the radiator thermostat causes the sensor to expand when the temperature
rises. The sensor acts onto the valve spindle and this causes
Dimensions
the TRV body to close. When the temperature falls the sensor
contracts and the spring-loaded valve spindle is opened. The
TRV opens in proportion to the temperature of the sensor.
Only the amount of water required to maintain the room temperature set on the radiator thermostat can flow into the radiator.
NOTE: All dimensions in mm unless otherwise stated.
Ordering Information
Table 1. Available versions and OS-Nos. (OS=Ordering System)
Body type DN Pipe-Ø kvs (cv)-values OS-No.
Angle 15 8 mm 2,10 (2,46) 1,90 (2,22) V2047EUB08
reverse flow 15 10 mm 2,10 (2,46) 1,90 (2,22) V2047EUB08
15 15 mm 2,10 (2,46) 1,90 (2,22) V2047EUB08
Accessories
Service tool for replacing valve insert without draining system
for all sizes VA8200A001
Pressure cap – for shutting off valves on radiator outlet
for valves DN15 (1/2”) VA2202A015
Sealing ring for pressure cap
for valves DN15 (1/2”) VA5090A015
Fig. 1. Dimensions
standard flow reverse flow
Manual handwhee l cap
Replacement valve insert
Pre-settable, with integrated
locking device
UBG-R type VS1200UB02
VA2200D001
EN0H-0061GE25 R0402 2 Honeywell AG • All rights reserved