Honeywell V2000KX PRODUCT DATA

RADIATOR VALVE WITH KV-SPECIALIZED CARTRIDGE
1/2
1/2
Angle to DIN
1/2
Straight to DIN
1/2
V2000Kx
KV type TRV Body
PRODUCT DATA
Application
Thermostatic radiator valve bodies (TRV bodies) are fitted on the supply or return of radiators or heat exchangers. Together with a radiator thermostat, for example the Thera-4, they control the room temperature by regulating the flow of hot water into the radiator. The temperature of different rooms is controlled individually and energy is saved.
TRV bodies of this type have quiet operation and are fitted to the supply of radiators on two-pipe systems with low, medium or high flow rates.
The valve insert can be replaced while the system is running and without draining using the service tool (see ‘Accessories’).
TRV bodies of this type are suitable for
• Honeywell radiator thermostats with M30 x 1.5 connection
• Certain Honeywell MT4 actuators
• Honeywell Hometronic HR80 and Roomtronic HR40 actua­tors
Horizontal angle
Corner angle
Straight with swanneck
AT-Concept
AT-Concept valves share the same valve housing design. The valve insert can be replaced by any other AT-Concept valve insert, i.e. BB, KV, UBG, SL, VS, FS, FV and SC.
Features
• With valve disc specially designed for three different
flow rates
k
v
• For heating systems with low, medium or high flow
rates
• Quiet operation
• DIN type bodies with dimensions according to EN215,
Appendix A, Series D
• NF type bodies with dimensions according to EN215,
Appendix A, Series F
• AT-Concept valve housing and insert
• Valve insert can be replaced while system is operating
and without draining the system
• Valve opening spring is not in the water
• Standard M30 x 1.5 thermostat connection
• Supplied with red, blue or green protection cap, im-
printed for clear identification
Honeywell y Subject to change EN0H-2102GE25 R0307
V2000KX - KV TYPE TRV BODY
Design
The thermostatic radiator valve body consists of:
• Valve housing PN10, DN10, 15 or 20 with
• internal thread connection to DIN2999 (ISO7) for threaded, copper or precision steel pipe on inlet fittings see ‘Accessories’)
• external thread connection with union-nut and radiator tail­piece on outlet
• angle to DIN and straight to DIN bodies with dimensions according to EN215, Appendix A, Series D
• angle to NF and straight to NF bodies with dimensions according to EN215, Appendix A, Series F
• Valve insert with KV type cartridge
• Protection cap
• Union-nut and radiator tailpiece
1
(Eurocone for DN15)
1
(compression ring
Materials
• Angle/straight to DIN: valve housing made of nickel-plated red bronze
• Corner angle, horizontal angle and swanneck tailpiece: valve housing made of nickel-plated hot-forged brass
• Valve insert made of brass with EPDM O-rings and soft seals and stainless steel spindel
• Protection cap made of red, blue or green plastic
• Union-nut and tailpiece made of brass, union-nut nickel­plated, tailpiece optionally nickel-plated
Please Note:
• To avoid stone deposit and corrosion the composition of the medium should conform with VDI-Guideline 2035
• Additives have to be suitable for EPDM sealings
• System has to be flushed thoroughly before initial operation with all valves fully open
• Any complaints or costs resulting from non-compliance with above rules will not be accepted by Honeywell
• Please contact us if you should have any special require­ments or needs
Specifications
Medium Heating water, water quality to
VDI2035
Operating temperature max. 130°C (266°F)
Operating pressure PN10
Differential pressure max. 1 bar (14.5 psi) –
max. 0.2 bar (2.9 psi) recommended for quiet operation
k
(cv)-values 0.14 (0.16) with valve disc 3 (K3)
vs
0.36 (0.42) with valve disc 4 (K4)
0.80 (0.84) with valve disc 5 (K5)
Nominal flow K3 30 kg/h
K4 76 kg/h K5 190 kg/h
Thermostat connection M30 x1.5
Closing dimension 11.5 mm
Stroke 2.5 mm
Identification
• Red (K3), blue (K4) or green (K5) protection cap, ‘3’, ‘4’ or ‘5’ embossed on top of cap
• ‘3’, ‘4’ or ‘5’ imprinted 3x on top of valve insert
Function
Thermostatic radiator valves enable individual control of room temperature and thus save energy.
The TRV body is controlled by the radiator thermostat. Air from the room passing over the sensor of the radiator thermostat causes the sensor to expand when the temperature rises. The sensor acts onto the valve spindle and this causes the TRV body to close. When the temperature falls the sensor contracts and the spring-loaded valve spindle is opened. The TRV opens in proportion to the temperature of the sensor. Only the amount of water required to maintain the room temperature set on the radiator thermostat can flow into the radiator.
Honeywell y Subject to change 2 EN0H-2102GE25 R0307
Installation Examples
Fig. 1. Angle Fig. 2. Straight
Fig. 3. Horizontal angle Fig. 4. Corner angle Fig. 5. Straight with swanneck
V2000KX - KV TYPE TRV BODY
Dimensions and Ordering Information
Fig. 6. Angle Fig. 7. Straight
h
l
L
H
52
G1/2
L
l
h
Fig. 8. Horizontal angle Fig. 9. Corner angle Fig. 10. Straight with swanneck
Honeywell y Subject to change 3 EN0H-2102GE25 R0307
V2000KX - KV TYPE TRV BODY
Table 1. Dimensions and OS-Nos (OS=Ordering System)
Body type DN EN215
certified
For the supply
Angle to EN215 (D)
(Fig. 6)
K3 10 0,140 (0,164) Rp K4 0,360 (0,421) V2000EK410 K5 0,800 (0,936) V2000EK510 K3 15 0,140 (0,164) Rp K4 0,360 (0,421) V2000EK415 K5 0,800 (0,936) V2000EK515 K5 20 0,800 (0,936) Rp
Straight to EN215 (D)
(Fig. 7)
K3 10 0,140 (0,164) Rp 3/8" 59 85 25 V2000DK310 K4 0,360 (0,421) V2000DK410 K5 0,800 (0,936) V2000DK510 K3 15 0,140 (0,164) Rp K4 0,360 (0,421) V2000DK415 K5 0,800 (0,936) V2000DK515 K5 20 0,800 (0,936) Rp
Angle to EN215 (F)
(Fig. 6)
Straight to EN215 (F)
(Fig. 7)
Horizontal angle
(Fig. 8)
K4 10 0,360 (0,421) Rp K4 15 0,360 (0,421) Rp 1/2" 26 53 23 22 V2020EK415 K5 0,800 (0,936) V2020EK515 K4 10 0,360 (0,421) Rp K4 15 0,360 (0,421) Rp 1/2" 55 82 26 V2020DK415 K5 0,800 (0,936) V2020DK515 K4 10 0,360 (0,421) Rp K5 0,800 (0,936) V2000AK510 K4 15 0,360 (0,421) Rp 1/2" 26 24 26 35 V2000AK415 K5 0,800 (0,936) V2000AK515
Corner angle, radiator connection left
K4 10 0,360 (0,421) Rp K4 15 0,360 (0,421) Rp 1/2" 24 53 26 26 30.5 V2000LK415
(Fig. 9) Corner angle, radiator connection right
K4 10 0,360 (0,421) Rp K4 15 0,360 (0,421) Rp 1/2" 24 53 26 26 30.5 V2000RK415
(Fig. 9) Swanneck
(Fig. 10)
K4 15 0,360 (0,421) Rp K5 0,800 (0,936) V2000BK515
For the supply or return
Angle with external
K5 15 0,800 (0,936) G
threads (Fig. 6) Straight with external
K5 15 0,800 (0,936) G
threads (Fig. 8) Corner angle with
K5 15 0,800 (0,936) G external threads, radiator connection left (Fig. 9) Corner angle with
K5 15 0,800 (0,936) G external threads, radiator connection right (Fig. 9)
NOTE: All dimensions in mm unless stated otherwise.
kvs(cv)-value Pipe
l L h H h
2
connection
3
/8" 26 52 22 20 V2000EK310
1
/2" 29 58 26 20 V2000EK315
3
/4" 34 66 29 19 V2000EK520
1
/2" 66 95 25 V2000DK315
3
/4" 74 106 25 V2000DK520
3
/8" 24 49 20 21 V2020EK410
3
/8" 50 75 26 V2020DK410
3
/8" 24 50 22 33 V2000AK410
3
/8" 24 53 26 22 26.5 V2000LK410
3
/8" 24 53 26 22 26.5 V2000RK410
1
/2" 66 108 25 V2000BK415
3
/4" A 29 26 20 V2060EK515
3
/4" A 66 25 V2060DK515
3
/4" A 24 26 26 30,5 V2060LK515
3
/4" A 24 26 26 30,5 V2060RK515
OS-No.
EN0H-2102GE25 R0307 4 Honeywell y Subject to change
Accessories
Pipe Connections Valve Accessories
Compression ring and nut
3/8" x 10 mm VA620A1010
3/8" x 12 mm VA620A1012
1/2" x 10 mm VA620A1510
1/2" x 12 mm VA620A1512
1/2" x 14 mm VA620A1514
1/2" x 15 mm VA620A1515
1/2" x 16 mm VA620A1516
3/4" x 18 mm VA620A2018
3/4" x 22 mm VA620A2022
NOTE: Support inserts have to be used for copper or soft
steel pipe with 1.0 mm wall thickness
Compression ring and nut with support insert for compo­site pipe (2 pcs each)
1/2" x 14 mm VA622B1514
1/2" x 16 mm VA622B1516
Manual handwheel cap
Pre-settable, with integrated locking device
Pressure cap – for shutting off valves on radiator outlet
for valves DN10 (3/8") VA2202A010
for valves DN15 (1/2") VA2202A015
for valves DN20 (3/4") VA2202A020
Sealing ring for pressure cap
for valves DN10 (3/8") VA5090A010
for valves DN15 (1/2") VA5090A015
for valves DN20 (3/4") VA5090A020
Service tool to replace valve insert
for all sizes VA8200A001
V2000KX - KV TYPE TRV BODY
VA2200D001
Compression ring and nut with support insert (2 pcs each)
3/8" x 12 mm VA621A1012
1/2" x 12 mm VA621A1512
1/2" x 15 mm VA621A1515
1/2" x 16 mm VA621A1516
3/4" x 18 mm VA621A2018
Reduction piece
1" pipe > 1/2" valve VA6290A260
1 1/4" pipe > 1/2" valve VA6290A280
1" pipe > 3/4" valve VA6290A285
1 1/4" pipe > 3/4" valve VA6290A305
Radiator tailpiece with thread up to collar
for valves DN10 (3/8") VA5201A010
for valves DN15 (1/2") VA5201A015
for valves DN20 (3/4") VA5201A020
Extended radiator tailpiece, nickel-plated, to be shortened as required
3/8" x 70 mm (for DN10) thread approx. 50 mm
1/2" x 76 mm (for DN15) thread approx. 65 mm
3/4" x 70 mm (for DN20) thread approx. 60 mm
Soldering tailpiece
3/8" x 12 mm (for DN10) VA5230A010
1/2" x 15 mm (for DN15) VA5230A015
3/4" x 22 mm (for DN20) VA5230A020
VA5204A010
VA5204A015
VA5204A020
Replacement valve insert
KV3 type VS1200K301
KV4 type VS1200K401
KV5 type VS1200K501
Honeywell y Subject to change 5 EN0H-2102GE25 R0307
V2000KX - KV TYPE TRV BODY
Flow Diagram
P-Band 1K 2K 3K kv(cv)-value - valve disc K3 0.047 (0.055) 0.095 (0.111) 0.140 (0.164) kv(cv)-value - valve disc K4 0.120 (0.140) 0.240 (0.281) 0.360 (0.421) kv(cv)-value - valve disc K5 0.300 (0.351) 0.600 (0.702) 0.800 (0.936)
NOTE: kv (cv)= 0.7 (0.82) for corner angle versions
Design Example
Given: Flow rate 150 kg/h Required: Pressure loss (p) with a P-band of 2K Solution: The required pressure loss for the K5 valve disc is found at the intersection of the flow line
with the line for the chosen valve performance P=2K
Result: p = 62 mbar = 6 200 Pa
Automation and Control Solutions
Honeywell GmbH
Hardhofweg
74821 Mosbach, Germany
Phone: +49 (6261) 810
Fax: +49 (6261) 81393
www.honeywell.com
EN0H-2102GE25 R0307 March 2007 © 2007 Honeywell International Inc. Subject to change • All rights reserved Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland or its authorized representative.