TS131
Temperature Relief Valve
With test facility and double sensor
Product specification sheet
Application
The TS131 temperature relief valve for heating systems according to EN 12828 is a self-acting valve which is activated by the
flow temperature of the heat generator. It opens and discharges
water from the heat generator or condensing coil at a flow temperature of 95 °C and thereby prevents a significant temperature
rise in the heat generator.
Special Features
• Construction tested to EN 14597 (TH119507)
• Immersion pocket with double heat sensors
• Test facility
• Capillary tube protected against kinking by steel sheath
• Immersion pocket with external thread
Range of Application
Multi-fuel boilers with integral water heating or condensing coils
in closed solid-fuel fired heating systems to EN 12828.
Construction
The temperature relief valve comprises:
• Housing with internal thread
• Bonnet
• Valve piston with form seal
•Spring
• Remote double temperature sensor with capillary tube
• Immersion pocket G 1/2” (ISO 228)
Materials
• Brass housing, bonnet and immersion pocket
• Copper temperature sensor
• Copper capillary tube
• Brass valve piston
• Hot-water-resistant elastomer seals
Technical Data
Heating system capacity max. 100 kW
Opening temperature 95 °C
Flow capacity 2100 kg/h water at a minimum flow
pressure of 1.0 bar (1 capillary tube)
Connection size Rp
Operating pressure max. 5 bar
3
/4" (DIN EN 10226)
EN0H-1543GE23 R0809 • Subject to change without notice
www.honeywell.com 1
TS131 Temperature Relief Valve
152
Temperature sensor
R1/2“
62
40
98,5
Method of Operation
The temperature relief valve is actuated by the flow temperature
of the heat generator. It comprises a spring-loaded valve and a
bellows operated temperature sensor. When a boiler flow temperature of 95ºC is reached the force exerted by the bellows system
becomes greater than the force of the spring and the valve
opens. Heated potable water then flows out and this is replaced
by cold water from the supply network.
This absorbs excess heat from the heat generator and prevents
overheating.
Options
TS131-3/4A = Opening temperature 95 °C
capillary tube with protection sheath 1300 mm,
with approved construction
TS131-3/4B = Opening temperature 95 °C
capillary tube with protection sheath 4000 mm
TS131-3/4Z = Special Versions available on request
TS131KF
Spare Parts
TS131KF-3/4 Piston guide complete for TS131
Connection size 3/4"
TS131TWG-3/4 Temperature motion transducer for TS131
Opening temperature 95°C
Option A = Capillary tube with protection
sheath 1300 mm
Option B = Capillary tube with protection
sheath 4000 mm
TS131TWG
Automation and Control Solutions
Honeywell GmbH
Hardhofweg
D-74821 Mosbach
Phone: (49) 6261 810
Fax: (49) 6261 81309
http://europe.hbc.honeywell.com
www.honeywell.com
Manufactured for and on behalf of the
Environmental and Combustion Controls Division
of Honeywell Technologies Sàrl, Rolle, Z.A. La
Pièce 16, Switzerland by its Authorised Representative Honeywell GmbH
EN0H-1543GE23 R0809
Subject to change without notice
© 2009 Honeywell GmbH