does not have trap at its lowest point.
Horizontal run does not have minimum pitch of 2 in. per ft. Sharp hose bends. Downward pitch
nozzle is not pitched up.
Sharp hose bends. Does not have at least 6 in. vertical rise immediately out of humidifier, and
Sharp hose bends. Hose not continuously supported at least every 12 in., resulting in hose sag.
Sharp hose bends. Horizontal run does not have minimum pitch of 2 in. per ft.
wiring diagram in this document.
wet switch under the TrueSTEAM. Wire switch to TrueSTEAM according to the
TrueSTEAM is installed in a living space. You must install a drip pan with overflow
1 gallon per minute water flow for the vertical rise of the installation.
condensate pump rated at 212°F. Pump must have total minimum capacity of
TrueSTEAM is using an auxiliary drain. You must install a wetted drain trap or
Do not use a plastic Tee.
Remote hose has a downward slope. You must use a 212°F rated Tee and P-trap.
ADDITIONAL MATERIALS REQUIRED IF…
AVOID THESE COMMON MISTAKES
upward pitch.
Nozzle at
every connection.
Hose clamps at
Water in elbow.
Clamps
of 2 in. per ft.
Minimum upward pitch
OPEN FOR STEP-BY-STEP INSTRUCTION
allowed.
and maximum temperature
codes for drain pipe size
Always consult plumbing
hose length is 20 ft.
maximum remote
• HM509 and HM512
Minimum 2 in.
Minimum 6 in.
Do not use plastic Tee.
Provide a 212°F rated Tee at the lowest point.
below humidifier steam outlet.
Downward slope can not be more than 3 ft
and bends.
Avoid sharp kinks
provided hooks.
hose every 12 in. using
Otherwise, support
perforated angle iron.
On straight runs, use
every connection.
Hose clamps at
is 10 ft.
remote hose length
• HM506 maximum
vertical rise.
6 in. of straight
and bends.
Avoid sharp kinks
pitch of 2 in. per ft.
Minimum upward
upward pitch.
Nozzle at
Support hook screws, 3/4 in. (7 or 14)
TrueSTEAM screws, 1-1/4 in. (4)
Drywall anchors (4)
Hose clamps (2)
Support hooks (7 or 14)
Foam gasket for remote nozzle
Remote humidifier nozzle
Remote duct nozzle
Insulated hose (10 or 20 ft)
If hose slopes downhill…
ENDLESS INSTALLATION OPTIONS
Upslope Remote
Downslope Remote
REQUIREMENTS FOR PROPER INSTALLATION
™
TrueSTEAM
Remote Mount Kit
MATERIALS PROVIDED
InstallatIon InstructIons
READ THIS BEFORE BEGINNING REMOTE INSTALLATION
!
Living Area Remote Options
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://yourhome.honeywell.com
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
Garage Remote
NON-COMPLIANCE WILL VOID WARRANTY
HM506 maximum remote hose length is 10 ft.
HM509 and HM512 maximum is 20 ft.
For best performance, mount the humidifier as
close as possible to the remote nozzle location.
Horizontal installation must have upward pitch of
at least 2 in. per ft.
Remote hose must be supported to prevent sags.
Where there are long, straight runs, 1-1/2 in. x
2-1/4 in. perforated metal angle is recommended
to provide continuous support under the hose.
Other rigid materials, such as 2x4 lumber, may also
be used to continuously support the hose.
Never support the hose by attaching it to PVC
pipe or other materials that may sag over time,
or materials that cannot support the weight of
the hose.
Where it is not possible to provide continuous
support, anchor the hose every 12 inches by
securing it to a rigid support using the support
hooks provided.
Use the provided insulated hose to sustain output
efficiency.
Never make sharp bends in the steam hose, as
this will cause kinks. Pay particular attention when
routing the steam hose around rafters or joists and
avoid sharp bends and kinks in these areas.
Attach the remote humidifier nozzle so it directs
the hose upward. Do not attempt to route the hose
through the hole in the mounting bracket.
Down sloping remote hose must have a drain with
a wetted trap installed at the lowest point. Use a
Tee that is rated for continuous use for steam.
Do not use a plastic Tee and do not use more than
one downward slope.
ALWAYS inspect the hose installation after the
humidifier has been operating for at least one hour
to confirm that there are no sags or leaks. Note
that the hose gets softer after it heats up so sags
may develop after the initial installation.
Install drain line according to the instructions on
the next page.
Install a drip pan with a wet switch under the
humidifier when installed in finished spaces.
® U.S. Registered Trademark.
© 2009 Honeywell International Inc.
69-2317—01 M.S. 04-09
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
1
M28708
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
RED
TrueSTEAM
TERMINAL
BLACK
GREEN
ORANGE
DIP 4 DIP 5
1-1/2 IN. MINIMUM TRAP
(OR SIZE PER LOCAL CODE)
VENTED PER
LOCAL CODE
ALL PLASTIC PIPE
JOINTS ARE WELDED
M28679
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM) PVC PIPE
3/4 IN. FNPT X 1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
SIZE TO FIT PUMP OUTPUT
HOSE CLAMPS AT
ALL CONNECTIONS
3/8-IN. TUBING
RATED AT 212°F
M28713
3/4 IN. FNPT X 3/4 IN. CPVC
3/4 IN. CPVC PIPE
TO PUMP
ALTERNATIVE
HOSE FROM
TrueSTEAM
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM)
PVC PIPE
3/4 IN. FNPT X 1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
M28680
ALL CONNECTIONS FROM
SOLENOID VALVE TO
DRAIN TRAP ARE SEALED
SINK
1-1/2 IN.
PVC TEE
1-1/2 IN. PVC
1-1/2 IN.
PVC
COUPLING
WELD
WELD
STAINLESS STEEL
SLOTTED BAND
COUPLING SIZED TO
FIT PIPE (COPPER,
PVC, CPVC)
SIZE TO FIT PUMP OUTPUT
ALTERNATIVE
THIS CONFIGURATION ALLOWS FOR
REMOVAL OF THE TRAP
THREADS
WELD
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM)
PVC PIPE
3/4 IN. FNPT X 1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
M28681
ALL PLASTIC PIPE UNDER
SINK 1-1/2 IN. MINIMUM PVC
ALL CONNECTIONS FROM
SOLENOID VALVE TO
DRAIN TRAP ARE SEALED
SINK
COUPLING
WELD
WELD
THREADS
THREADS
WELD
WELD
WYE
1-1/2 IN. PVC
STAINLESS STEEL
SLOTTED BAND
COUPLING SIZED TO
FIT PIPE (COPPER,
PVC, CPVC)
ALTERNATIVE
THIS CONFIGURATION ALLOWS FOR
REMOVAL OF THE TRAP
SIZE TO FIT PUMP OUTPUT
3/4 IN. COPPER PIPE
3/4 IN. FNPT X SWEAT
HOSE
CLAMPS
HOSE FROM
TrueSTEAM
212°F RATED PUMP
1/2 IN. BARB X 3/4 IN. MNPT
FLEXIBLE
HOSE
M28678
SEAL ALL CONNECTIONS FROM
SOLENOID VALVE TO DRAIN STACK
3/4 IN. FNPT X
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM) PVC PIPE
3/4 IN. FNPT X 3/4 IN. CPVC
3/4 IN. CPVC PIPE
3/8-IN. TUBING
RATED AT 212°F
MOUNTING
2
SECURE HOSE
Use provided anchors
if mounting to drywall
or plaster.
Remote Adapter Nozzle:
Always pitch upward.
Diversitech WS-1 wet
switch wiring
Cut a slit in the insulation half way
around the hose.
Do not cut into the
rubber steam hose.
Insert the hose clamp into
the slit and hook it onto the
rubber hose.
Nozzle at upward pitch.
Minimum upward
pitch of 2 in. per ft.
Avoid sharp kinks and
prevent bends.
6 in. of straight
vertical rise.
3 in. minimum clearance from nozzle
outlet to duct.
12 in .
Clearance hole for hose and insulation.
Seal off unconditioned space with
grommet (not provided) or caulk.
Clamp
Clamp
On straight runs, use perforated angle
iron. Otherwise, secure hose every 12 in.
using provided hooks.
Always install nozzle so the
outlet is pointed up.
Do not route the steam
hose through the hole in the
mounting plate.
1-3/4 in. hole
24 in. open air downstream.
Downward slope can not be more than
3 ft below humidifier steam outlet.
On straight runs, use
perforated angle iron.
Otherwise, support
hose every 12 in. using
provided hooks.
Minimum 6 in.
Minimum 2 in.
Always consult and follow local
plumbing codes for drain pipe
size and maximum temperature
requirement.
If hose slopes downhill…
Provide a 212°F rated Tee at the
lowest point. Do not use plastic Tee.
Hose clamps at
every connection.
Minimum upward
pitch of 2 in. per ft.
Nozzle at
upward pitch.
Clamps
Water in elbow.
If humidifier is in finished space, always install a drip pan
with wet switch. Honeywell recommends Diversitech WS-1
(wiring shown here).
PLUMBING TO FLOOR DRAIN
3A 3B
Ideal for Installation
Draining water may be hot.
Direct and secure the hose outlet into the floor drain
to reduce risk of hot water pooling or splashing.
OTHER PLUMBING OPTIONS
Choose the plumbing option that suits your installation. Use A, B, C, or D based on type of pipe or condensate pump. Consult and follow local plumbing codes in addition to these instructions.
FOR ALL OPTIONS SHOWN:
Option 1: Plumbing to drain with
condensate pump.
• Use Hartell A3X-115 condensate pump or equivalent
(212°F temperature rating, > 1 GPM pump flow rate).
• Support rubber hose every 6 in.
• PVC must be schedule 40 or higher rating.
• All plastic pipe joints are welded.
• Drain into a P-trap that will remain wetted at all times.
Option 2: Plumbing to a dedicated trap.
Clamp
Consult and follow plumbing codes for drain pipe
size and maximum temperature requirement.
Install drain hose with
continuous downhill slope.
• Pump must be powered when TrueSTEAM is operating.
• Use a pump with a built-in overflow sensor or install the pump
in a drip pan with wet switch wired to turn off TrueSTEAM.
Option 3: Plumbing to sink with a
dedicated trap.
Connect to TrueSTEAM.
Common to all plumbing options.
TRUESTEAM INSTALLATION
Option 4: Plumbing to sink trap.
COMPLETING
Refer to TrueSTEAM Installation Guide
(# 69-2285) to complete wiring and checkout.