(Remove thermostat from wallplate and turn over to find model number.)
TH2110D and TH2210D
programmable thermostats
System Types
TH1110D and TH2110D:
• Central heating (gas, oil, electric or highefficiency furnace)
• Central heating (see above) with air
conditioning
• Hot water system (steam or gravity) with or
without pump
• Central air conditioners
• 750 mV heating systems
• 1-Heat/1-Cool heat pumps
TH1210D and TH2210D:
• 2-Heat/1-Cool heat pumps
ENGLISH
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions
can damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit http://yourhome.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502.
1
Installation Guide
Wallplate installation
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power
before beginning installation.
n Loosen the locking screw at the bottom of the thermostat. Note that the screw is
captive and cannot be removed from the wallplate.
o Separate the thermostat from the wallplate as per Figure 1.
p Position the wallplate against the wall and mark hole positions with a pencil.
NOTE: Levelling is for esthetics only and will not affect the performance of the
ENGLISH
thermostat.
q Drill holes at the marked positions and insert supplied wall anchors.
r Pass the wires through the large opening located at the bottom center of the wallplate
as per Figure 2.
s Secure the wallplate to the wall with supplied mounting screws as per Figure 3.
t Connect the wires to the terminals.
Figure 2
Figure 1
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube,
do not place the old control in the trash. Contact your local waste
management authority for instructions regarding recycling and proper
disposal.
2
Figure 3
PRO TH1000 / TH2000 Series
Wiring
Power supply. Provide disconnect means and overload protection as required.
Set the O/B jumper according to the type of reversing valve (see page 4).
Use a piece of wire (not supplied) to connect W and Y terminals to each other.
Optional 24 VAC common connection. If this connection is not made, use batteries
to power the thermostat.
This connection is not required for systems that provide heating only
This connection is not required for systems that provide cooling only
This connection is not required for systems that do have an air recirculating fan.
Gas, oil or electric heating and/or air conditioning (1H / 1C / 1H1C)
Use
TH1110D
or
TH2110D
Heat pump without auxiliary heating (1H1C)
Use
TH1110D
or
TH2110D
Reversing valve
Heat pump with auxiliary heating (2H1C)
Use
TH1210D
or
TH2210D
ENGLISH
Compressor
Fan
Heat
Compressor
Fan
Compressor
Fan
Reversing valve
Heat
3
Installation Guide
Reversing valve setting
NOTE: This setting is necessary only if the thermostat is connected to a heat pump.
The jumper is located on the back of the thermostat faceplate. Set it according to the type
of reversing (changeover) valve used by the heat pump.
• O (factory setting): The reversing valve is energized when the System switch is set to
Cool (cooling mode).
• B: The reversing valve is energized when the System switch is set to Heat (heating
mode).
Incorrect jumper setting: The heat pump operation will be reversed; i.e., it will cool in
Heat mode and will heat in Cool mode.
Fan operation setting
ENGLISH
NOTE: This setting is not applicable if a fan is not connected to the G terminal.
The jumper is located on the back of the thermostat faceplate. It determines how the fan
operates when placed in Automatic mode.
• HG (factory setting): Leave the jumper in this position for gas or oil heating systems. In
this position, the heating system controls the fan operation and activates the fan only
when the plenum air is sufficiently warm.
• HE: Place the jumper to this position for heat pump or electric heating systems. In this
position, the thermostat activates the fan only when there is a call for heat.
Incorrect jumper setting: An incorrect setting is noticeable
When heating starts, you will initially feel cold air coming out of the vents as the fan is running
before the furnace has enough time to heat up the air.
in a gas or oil heating system.
Battery installation
If 24 VAC common wire is connected to the C terminal, batteries are
optional and serve to provide backup power.
If 24 VAC common wire is not connected to the C terminal, batteries
are necessary to power the thermostat.
Install 2 AAA batteries on the back of the thermostat faceplate as
shown.
Thermostat mounting
n Align the two brackets on the top of the thermostat with the
corresponding slots on the top of the wallplate.
o Push the faceplate against the wallplate.
p Tighten the screw at the bottom of the thermostat.
4
PRO TH1000 / TH2000 Series
Installer setup
Follow the procedure below to personalize and
configure the thermostat according to the heating/
cooling system.
n Press S and T for three seconds. The display
will appear as shown on the right.
o Press S or T to change the option.
p Press S and T for three seconds to advance to
the next function.
Function
number
Option
number
q Press Run to exit the menu and save any
changes.
NOTE
: You will also exit the menu if you press S and
T
for three seconds when the last function is
displayed.
Function
1Temperature display format0
2
Time display format
3Heating cycles per hour5
4Cooling cycles per hour32 to 6 cycles per hour
5
Compressor protection
6
Adaptive Intelligent Recovery
1
Applicable to programmable models (TH2110D & TH2210D) only.
2
Damage can occur if the compressor is restarted too soon after shutdown. This feature
1
2
forces the compressor to wait 5 minutes before restarting. During the wait time, the
message Cool On or Heat On flashes on the screen. When the safe wait time has elapsed,
the message stops flashing and the compressor turns on.
3
Applicable to programmable models (TH2110D & TH2210D) only.
Adaptive Intelligent Recovery™ allows the thermostat to “learn” how long your furnace or
air conditioner takes to reach the set temperature. Simply program the desired times and
desired temperatures into the schedule. The thermostat will determine when to activate
heating or cooling so that the desired temperature is attained at the desired time.
Default
setting
0: Fahrenheit
1: Celsius
0: 12-hour display
0
1: 24-hour display
2 to 6 cycles per hour
• 2: 30 min (steam, gravity)
• 3: 20 min (hot water, 90%+ high-efficiency furnace)
• 4: 15 min (gas or oil)
• 5: 12 min (gas or oil)
• 6: 10 min (electric)
0: enabled (for systems without a compressor))
0
1: disabled (for systems equipped with a compressor)
3
0: Off
1
1: On
Options
ENGLISH
5
Installation Guide
Specifications
Temperature Ranges
• Heat: 40 °F to 90 °F (4.5 °C to 32 °C)
• Cool: 50 °F to 99 °F (10 °C to 37 °C)
Operating Ambient Temperature
• 32 °F to 122 °F (0 °C to 50 °C)
Shipping Temperature
• -40 °F to 130 °F (-40 °C to 55 °C)
Operating Relative Humidity
• 5% to 90% (non-condensing)
ENGLISH
Physical Dimensions
• 4.7” H x 2.9” W x 1.1” D (120 mm H x 74 mm W x 28 mm D)
Power Supply
• 24 VAC or 2 AAA batteries
Maximum Load
• 1 A @ 24 VAC per output
6
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.