Honeywell T8401C User Manual

Page 1
T8401C
Electronic Thermostats
INSTALLATION INSTRUCTIONS

APPLICATION

The T8401C Thermostat provides single-stage, nonprogrammable cooling systems with manual changeover from heat to cool. Heating cycle rate is selectable at 1, 3, 6, 9 or 12 cph. Cooling cycle reate is fixed at 3 cph. Temperature indicature indication can be set for °F or °C.
The T8401C1031 (Fig. 1) is powered directly from the zone panel. Batteries are not required because setpoints are held permanently by non-volatile memory.
T8401C models include a thermostat, wallplate (for wiring and mounting thermostat) and owner ’s guide. See Table 1 for a listing of thermostat features. See Table 2 for a listing of zone panels that can be used with the T8401C.
temperature control for 24 Vac heating
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Damage to Heating/Cooling System Possible.
Be careful when handling wires during
Set
Room
FAN SYSTEM
Auto On
Fig. 1. The T8401C1031 Thermostat.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Model Powering Method Changeover System Selection Fan Selection
T8401C1031 Hardwired Manual Heat-Off-Cool On-Auto
Cool Off Heat
M14752
Table 1. Thermostat Features
installation. Disconnect power at furnace or main breaker/ fuse box.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 2. Do not install the thermostat where it can be affected by:
— drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from the sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
® U.S. Registered Trademark Copyright © 2002 Honeywell • • All Rights Reserved
69-1483-1
Page 2
T8401C ELECTRONIC THERMOSTATS
Table 2. Zone Panel Cross Reference.
TotalZone
(TZ-3)
MABS EZ
(EZ-2, EZ-4)
Mini Zone
(MM - 2, -3) MABS II, IIL
T8401C1031 Yes Ye s One Oher One Oher
Yes N o Yes No No
Independent
Zone
NO
NO
Fig. 2. Typical location of thermostat.
This thermostat is a precision instrument and was carefully adjusted at the factory. Handle it carefully.

Mounting Wallplate to Wall

IMPORTANT
Level only for appearance. The thermostat func­tions normally even when not level.
Mount wallplate, T8401C, and the screws provided (see Fig. 3) as follows:
1. Place the wallplate at the desired location on the wall.
2. Pull the thermostat wire through the wallplate entrance hole.
3. Select the two mounting holes that best fit the application.
4. Fasten the wallplate to the wall using the anchors and screws provided.
YES
5 FEET
[1.5 METERS]
5. After wiring the wallplate, plug the hole to prevent
.
NO
M11338
drafts from affecting the thermostat; see Wiring section
WALL
MOUNTING SCREWS (2)
1
WHEN USING WALL ANCHORS, DRILL 3/16 INCH HOLES FOR DRYWALL, 7/32 INCH HOLES FOR PLASTER OR WOOD.
WALL ANCHORS (2)
1
WALLPLATE
M12202A
Fig. 3. Mounting wallplate to wall.
69-1483—1 2
Page 3
T8401C ELECTRONIC THERMOSTATS

Setting Fan Operation (Fuel) Switch

The fan operation (fuel) switch is preset at the factory in the F position. See Fig. 4. This is the correct setting for most systems. If this system is an electric heat system, set the switch to the E position. The E setting allows the fan to turn on immediately with the heating or cooling equipment in a system where the G terminal is connected
.
E
F
FAN OPERATION (FUEL) SWITCH
M12580
Fig. 4. Fan operation (fuel) switch.

Wiring

IMPORTANT
Use an 18-gauge thermostat cable for proper wiring.
All wiring must comply with local electrical codes and ordinances. Disconnect the power supply to prevent electrical shock or equipment damage.
NOTE: NOTE: To ensure proper mounting of thermo-
stat, restrict all wiring to the shaded area. See Fig. 5.
The shape of the terminals permits insertion of straight or wraparound wiring connections; either method is acceptable. See Fig. 6.
The T8401C is powered directly from the zone panel.
Refer to Fig. 7, 8, and 9 for typical wiring hookups.
KEEP WIRING IN SHADED AREA
G
C
R
W
Y
MOUNTING SCREW HOLE
WIRING ENTRANCE HOLE
Fig. 5. Restrict wiring to shaded area.
FOR STRAIGHT INSERTION TERMINAL SCREW
STRIP 5/16 IN. (8 MM)
G
C
B
O
MOUNTING SCREW HOLE
M14286
FOR WRAPAROUND STRIP 7/16 IN. (11 MM)
R
W
Y
B
O
M14287
Fig. 6. Wiring connections.
3 69-1483—1
Page 4
T8401C ELECTRONIC THERMOSTATS
TOTAL ZONE MABS EZ PANEL
NO CONNECTION
T8401 THERMOSTAT
Fig. 7. T8401 with TotalZone or MABS EZ control
THERMOSTAT MOTOR
W2 L G Y R W M6 M4 M1
OBGYRWC
M14288
panels (all zones)
.
MM-2 OR MM-3 CONTROL PANEL
CHANGEOVER
CONTROL
O1 G1 B1 T6/Y T5/R T4/W M1 M4 M6
OG BYRWC
T8401 THERMOSTAT
THERMOSTAT
(ZONE 1)
DAMPER MOTOR
(ZONE 1)
NO CONNECTION
TO T8401
M14289
Fig. 8. T8401 with MM-2 or MM-3 panels (zone one).
MABS II OR MABS IIL CONTROL PANEL
CHANGEOVER
CONTROL
O1 G1 B1 T6 T5 T4 M1 M4 M6
OG BYRWC
T8401 THERMOSTAT
Fig. 9. T8401 with MABS II and MABS IIL control
THERMOSTAT
(ZONE 1)
panel (zone one).
DAMPER MOTOR
(ZONE 1)
NO CONNECTION
TO T8401
M14290

Mounting Thermostat to Wallplate

1. Engage the tabs at the top of the thermostat and wallplate.
2. Swing down the thermostat and press the lower edge of the thermostat onto the wallplate to latch. See Fig. 10.
F
A
N
Auto On
Set
Room
A
ENGAGE TABS AT TOP OF THERMOSTAT WITH SLOTS ON MOUNTING PLATE.
Set
Room
F
A
N
A
u
to
O
n
DASHED LINES INDICATE TABS ON BACK OF THERMOSTAT
SYSTEM
Cool Off Heat
S
Y
S
C
T
o
o
E
l O
M
ff H
e
a
t
69-1483—1 4
PRESS LOWER EDGE OF
B
CASE TO LATCH.
M14292
Fig. 10. Mounting thermostat to wallplate.

Removing Thermostat from Wallplate

1. Pull the lower edge of the thermostat away from the wall.
2. Swing the thermostat up and remove the wallplate.
Page 5
T8401C ELECTRONIC THERMOSTATS

SETTINGS AND ADJUSTMENTS

Setting FAN and SYSTEM Switches

Fan and system settings are controlled manually by using the switches located at the bottom of the thermostat case. See Fig. 11.
Set
FAN
A
u
to
O
n
FAN SWITCH
Fig. 11. Digital Display and System Switches.
FAN Switch
Fan switch settings are:
On: The fan runs continuously. Use for improved air
circulation and air quality.
Auto: Normal setting for most homes. In cooling, the
fan starts and stops with the cooling equipment. In heating, the fan is controlled directly by the heating equipment and may start a few minutes after the heating equipment turns on (on most systems). In electric heat applications, the zone panel can be configured to turn the fan on when the thermostat calls for heat.
Slide the FAN switch in the bottom left corner of the thermostat to select the desired fan setting.
SYSTEM Switch
System switch settings control thermostat operation as
follows: Cool: The thermostat controls the cooling system. The
O terminal is energized.
Off: Both heating and cooling are off. O and B termi-
nals are de-engergized.
Heat: The thermostat controls the heating system.
The B terminal is energized.
Slide the SYSTEM switch in the bottom right corner of the thermostat to select the desired system setting.
TEMPERATURE DISPLAY
Room
INCREASE SETTING
DECREASE SETTING
Cool Off Heat
SYSTEM SWITCH
SYSTEM
M14293
Set Temperature Setpoint
NOTE: NOTE: Temperature setpoint range is 40° to
99°F (5° to 37°C).
The temperature setpoint and the room temperature are shown separately on the digital display. The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed.
INDICATOR
ROOM TEMPERATURE
Room
Set
SETPOINT TEMPERATURE
To set temperature setpoint:
1. Select Heat or Cool by sliding the SYSTEM switch in the lower right corner of the thermostat to the desired mode. See Fig. 11.
2. To display the temperature setpoint on the digital display, press either the or key once. The temperature setpoint is displayed for approximately five seconds as the indicator points to Set and flashes.
3. To decrease the temperature setpoint press the key. Each press changes the setpoint one degree; press and hold to change the setpoint several degrees.
4. To increase the temperature setpoint press the key. Each press changes the setpoint one degree; press and hold to change the setpoint several degrees.
Setting
NOTE: NOTE: To save changes to the °F/°C indication
To set the °F/°C indication and heat cycle rate:
C Indication and Heat Cycle Rate
°F/°
and the heat cycle rate, all seven steps must be completed.
1. If the temperature is displayed in °F, set the tem­perature setpoint to 52°F. If the room temperature is displayed in °C, set the temperature setpoint to 11° C.
M14680
M14681
M14682
M14679
M14683
5 69-1483—1
Page 6
T8401C ELECTRONIC THERMOSTATS
Optional System Checkout
When in steps 2 and 3 only, the key can be used to turn heat or cool outputs on and off. Change the SYSTEM switch setting to test heat or cool outputs. No action takes place If the SYSTEM switch is in the Off position.
Examples: System setting at HEAT: If heat is on, the
key turns it off; if heat is off, turns it on.
System setting at COOL: If cool is on, key turns it
off; if cool is off, turns it on.
2. Press the ▲▼ keys simultaneously for more than
one second to light all segments on display and to enter installer setup mode. When the keys are released, a two-digit software revision code is dis­played.
NOTE: NOTE: In installer setup mode only, each press
of the key momentarily displays 01. Each press of the key momentarily displays 02. When the keys are released, these two-digit codes are no longer displayed.
3. Press the ▲ key. Factory information is displayed.
A typical example is shown, but information dis­played varies by model. This information is for fac­tory use only.
4. Press the key again to display °C or °F.
5. Press the key to change the °C or °F indication.
M14684
M14685
M14686
M14687
M14688
scrolling when the desired cycle rate is displayed. See Table 3 for the cycle rate options and the cor­responding system equipment.
M14690
Table 3. Heating Cycle Rates.
System Cycles Per Hour
Steam, Gravity 1
Hydronic Heat, Condensing Gas
a
Furnaces
3
Gas or Oil Forced Air 6
Electric Heat 9
Special Applications
a
High Efficiency Furnace.
b
Refer to equipment manufacturer’s instructions.
NOTE: NOTE: Steps 7 and 8 are available on select
models.
7. Press the ▲ key to display cooling algorithm con- figuration default.
8. Press the ▲ key again to change cooling algorithm to C1 or C3.
C1 = Standard cooling algorithm. C3 = Aggressive cooling algorithm (can cause
9. Press the ▲ key again. Current configuration (CC) is displayed. A typical example is shown, but CC varies by model.
10. Press the ▲ key to save all changes, exit installer
setup mode and return to normal operation.
NOTE: After exiting installer setup mode, change the
setpoint to the desired room temperature.
b
M18419A
overshooting).
12
6. Press the ▲ key to display the heat cycle rate of 1,
3, 4, 5, 6, 9, or 12. If the desired cycle rate is dis­played, press the key to exit the installer setup mode. To change the heat cycle rate, press the key to scroll between 1, 3, 4, 5, 6, 9, and 12. Stop
69-1483—1 6
M14689

CHECKOUT

Heating
1. Slide the SYSTEM switch to Heat and the FAN switch to Auto.
2. Press and hold the ▲ key to raise the temperature setting several degrees above the room tempera­ture. After approximately ten seconds, the heating equipment should start. In conventional systems, the system turns on the fan through the use of a
Page 7
T8401C ELECTRONIC THERMOSTATS
Cooling
NOTE: To bypass the 5 minute delay, see optional sys-
tem checkout on page 6.
CAUTION
Low Temperature Hazard. Operating at too low of an outdoor temperature may cause compressor damage.
Do not operate cooling if outdoor temperature is below 50°F (10°C). Refer to equipment manufacturer instructions.
For compressor protection, during power
interruption and on initial startup, the T8401C Electronic Thermostat will go into a 5 minute delay. During this delay the cooling icon, a snowflake , will flash.
Table 4. Thermostat Sequence of Operations.
Fan Selection System Selection Call Energize Display
Auto Off None None None
On Off None G None
Auto Cool None O None
Auto Cool Snowflake Symbol O, G, Y Snowflake Symbol
Auto Heat None B None
Auto Heat Flame symbol B, W* Flame symbol
*If fan operation (fuel) switch is in E position, G terminal is also energized.
1. Slide the SYSTEM switch to Cool and the FAN switch to Auto.
2. Press the ▼ key to lower the temperature setting several degrees below the room temperature. After approximately five minutes, the cooling equipment should start. The fan starts and stops with the cool­ing equipment.
3. Press the ▲ key to raise the temperature setting above the room temperature. Cooling system should shut down.
Fan
1. Slide the SYSTEM switch to Off and the FAN switch to On. The fan should run continuously.
2. Slide the FAN switch to Auto. In heating, the fan is controlled directly by the heating equipment and may start a few minutes after the heating equip­ment turns on (on most systems). When using an electric heat thermostat, the fan starts and stops with the heating equipment. In cooling, the fan starts and stops with the cooling equipment.
Consult the instructions provided with The Zone Panel to troubleshoot system problems. Refer to Table 4 for the thermostat’s Sequence of Operations.
7 69-1483—1
Page 8
T8401C ELECTRONIC THERMOSTATS
$XWRPDWLRQDQG&RQWURO6ROXWLRQV
+RQH\ZHOO +RQH\ZHOO/LPLWHG+RQH\ZHOO/LPLWpH 'RXJODV'ULYH1RUWK '\QDPLF'ULYH *ROGHQ9DOOH\01 6FDUERURXJK2QWDULR
69-1483—1 G.H. Rev. 2-02 www.honeywell.com/yourhome
09=
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...