Honeywell T8400C1099, T8401C1031 User Manual

T8400C1099, T8401C1031
Electronic Thermostats
The T8400 and T8401 Thermostats provide single-stage, non-programmable temperature control for 24V heating­cooling systems with manual changeover from heat to cool. Heating cycle rate is selectable at 1, 3, 4, 5, 6, 9, or 12 cph. Cooling cycle rate is fixed at 3 cph. Temperature indication can be set for °F or °C.
The T8400 Thermostat is powered through the heating/ cooling system controls. The T8401 requires a common wire for operation. Batteries are not required because setpoints are held permanently by non-volatile memory.
The T8400 and T8401 models include a thermostat, wallplate (for wiring and mounting thermostat) and owner’s guide.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control containing mercury in a sealed tube.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
INSTALLATION INSTRUCTIONS
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1. Do not install the thermostat where it can be affected by: — drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from the sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
This thermostat is a precision instrument and was carefully adjusted at the factory. Handle it carefully.

Mounting Wallplate to Wall

IMPORTANT
Level only for appearance. The thermostat func­tions normally even when not level.
Mount the T8400 and T8401 with the screws provided (see Fig. 2) as follows:
1. Place the wallplate at the desired location on the wall.
2. Pull the thermostat wire through the entrance hole on the wallplate.
3. Fasten the wallplate to the wall using the anchors and screws provided.
4. After wiring the wallplate, plug the hole to prevent drafts from affecting the thermostat; see Wiring section.
® U.S. Registered Trademark Copyright © 2002 Honeywell • • All Rights Reserved
69-1484-2
T8400C1099, T8401C1031 ELECTRONIC THERMOSTATS
M12202A
M12580
FAN OPERATION (FUEL) SWITCH
NO
WALL
MOUNTING SCREWS (2)
1
WHEN USING WALL ANCHORS, DRILL 3/16 INCH HOLES FOR DRYWALL, 7/32 INCH HOLES FOR PLASTER OR WOOD.
WALL ANCHORS (2)
1
WALLPLATE
Fig. 2. Mounting wallplate to wall.
YES
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.

Wiring

IMPORTANT
Use an 18-gauge maximum wire to wire the T8400 and T8401 Thermostats.
All wiring must comply with local electrical codes and ordinances. Disconnect the power supply to prevent electrical shock or equipment damage.
NOTE: To ensure proper mounting of thermostat,
restrict all wiring to the shaded area. See Fig. 4.
The shape of the terminals permits insertion of straight or wraparound wiring connections; either method is acceptable. See Fig. 5.
Refer to Fig. 6 through 10 for typical wiring hookups.
NO
M11338

Setting Fan Operation (Fuel) Switch

The fan operation (fuel) switch is preset at the factory in the F position. See Fig. 3. This is the correct setting for most systems. If this system is an electric heat system, set the switch to the E position. The E setting allows the fan to turn on immediately with the heating or cooling equipment in a system where the G terminal is connected.
69-1484-2 2
E
F
Fig. 3. Fan operation (fuel) switch.
T8400C1099, T8401C1031 ELECTRONIC THERMOSTATS
)
A
T)
L (
L
L (
L
0
KEEP WIRING IN SHADED AREA
G
Rc
R
W
Y
MOUNTING SCREW HOLE
WIRING ENTRANCE HOLE
Fig. 4. Restrict wiring to shaded area
(T8400C1099 shown).
FOR STRAIGHT INSERTION TERMINAL SCREW
STRIP 5/16 IN. (8 MM)
G
Rc
B
O
MOUNTING SCREW HOLE
M16432
FOR WRAPAROUND STRIP 7/16 IN. (11 MM
G Rc
2
R W
Y
1
L1 (HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED. FACTORY INSTALLED JUMPER.
2
Fig. 6. Typical hookup of T8400C1099 in heat-cool
1 1
HOT)
2
COOLING TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSFORMER SYSTEM.
3
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS.
4
POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH IS IN THE OFF POSITION.
Fig. 7. Typical hookup of T8400C1099 in heat-cool
B O
HEATING PRIMARY
24V
CONTROL
system with single transformer.
G
Rc
R
2
W Y
3
FAN
COOL
RELAY
DAMPER
COMPRESSOR CONTACTOR
HEAT RELAY
system with two transformers.
4
B O
HEAT DAMPER
3
FAN RELAY
COOLING CONTACTOR
M13275
HEATING TRANSFORMER
M12562
1
L1 (HO
L2
R
W
B
Y
Fig. 5. Wiring connections
(T8400C1099 shown).
O
M13274
HOT)
TRANSFORMER
Fig. 8. Typical hookup of T8400C1099 in single-stage
G
Rc
3
R
W
4
Y
1
1
2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CAN BE USED FOR CHANGEOVER VALVE ON
2
SINGLE-STAGE HEAT PUMP SYSTEMS.
3
FACTORY INSTALLED JUMPER.
4
FIELD INSTALLED JUMPER.
COMPRESSOR
24V
2
B
2
O
heat pump systems.
HEAT CHANGEOVER
COOL CHANGEOVER
FAN RELAY
M2088
3 69-1484-2