Honeywell T8024F, T8001F User Manual

T8001F, T8024F Flush Mount
Programmable Thermostat
INSTALLATION INSTRUCTIONS

APPLICATION

The T8001F Thermostat provides single-stage, programmable temperature control for 24 Vac heating­cooling systems with manual changeover from heat to cool. The T8024F Thermostat provides multistage electronic control of single-zone heating and c ooling systems. Heating cycle rate is selectable at 1, 3, 4, 5, 6, 9, or 12 cph. Cooling cycle rate is fixed at 3 cph. Temperature indication can be set for °F or °C.
The T8001F, T8024F Thermostat is powered directly from the system transformer. Batteries are not required because setpoints are held permanently by non-volatile memory.
The T8001F, T8024F model includes a thermostat, wallplate and owner’s guide. See Table 1.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of it properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the control.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
Table 1. Thermostat Descriptions.
Model System Changeover System Selection Fan Selection Powering Method
T8001F Heat-Cool Manual Cool-Off-Heat Auto-On Hardwired
T8024F Heat-Cool Manual Cool-Off-Heat Auto-On Hardwired
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Hazardous Voltage. Can damage heating/cooling system.
Disconnect power at furnace or main breaker/ fuse box.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1. Do not install the thermostat where it can be affected by: — drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from the sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.

Installing Wallplate in Wall

IMPORTANT
Level only for appearance. The thermostat func­tions normally even when not level.
Mount wallplate and the T8001F or T8024F with the wing anchors provided (see Fig. 2) as follows:
1. Place the wallplate template at the desired location on the wall.
2. Trace and cutout the opening.
3. Pull the thermostat wire through the wallplate
entrance hole.
4. Fasten the wallplate to the wall using the wing anchors.
® U.S. Registered Trademark Copyright © 2001 Honeywell • • All Rights Reserved
69- 1465- 3
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
2)
A
F I S (
NO
WALL
WALLPLATE
MOUNTING SCREWS (2)
Fig. 2. Mounting wallplate to wall.

Wiring

IMPORTANT
Use an 18-gauge maximum wire for wiring the T8001F Thermostat.
YES
NO
5 FEET
[1.5 METERS]
NO
Fig. 1. Typical location of thermostat.
All wiring must comply with local electrical codes and ordinances. Disconnect the power supply to prevent electrical shock or equipment damage.
The shape of the terminals permits insertion of straight or wraparound wiring connections; either method is acceptable. A letter code is located near each terminal for identification. See Fig. 3 and 4.
NOTE: To ensure correct mounting of thermostat,
restrict all wiring to shaded area in center of terminals. See Fig. 5.
OR STRAIGHT
NSERTION
TRIP 5/16 IN.
9 MM)
WING ANCHORS (
M18610
FOR WRAP AROUND STRIP 7/16 IN. (11 MM)
TERMINAL SCREW
Fig. 3. T8001F wiring connections.
M11338
G
C
R
W
Y
B O
M18609
69-1465—3 2
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
T S
2
)
A
T8001 THERMOSTAT
1
M12567
T8001 THERMOSTAT
L (
L
-
ERMINAL CREW
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM)
FOR WRAPAROUND STRIP 7/16 IN. (11 MM
G
C
R
W1
Y
Fig. 4. T8024F wiring connections.
KEEP WIRING IN SHADED AREA
G
C
R
W
Y
MOUNTING SCREW HOLE
W2
Y2
B
O
M2021
KEEP WIRING IN SHADED AREA
B O
G C
R W
Y
HEAT
1
L1 (HOT)
L2
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
2
PUMP SYSTEMS.
Fig. 6. Typical T8001Fhookup in heat-cool
O1
G1
B1
E1
CHANGEOVER CONTROL
Fig. 7. Typical wiring diagram for T8001F on a zone 1
MABS II or Masterol™ control panel.
RELAY
COMPRESSOR
FAN
CONTACTOR
RELAY
system with one transformer.
G C
R W Y
B
2
O
2
COOL DAMPER
2
HEAT DAMPER
B O
ZONE
T8
T7
T6
T5
T4
M1
MOUNTING SCREW HOLE
WIRING
Fig. 5. Restrict wiring to shaded area (T8001 shown).
The T8001F Thermostat is powered directly from the system transformer and is adaptable to most 18 to 30 Vac heating-cooling systems. All T8001F Thermostats require a common wire to supply power. Refer to Fig. 6 through 8 for typical wiring hookups.
ENTRANCE HOLE (2)
T8024 THERMOSTAT
G C
R
W1
Y
M18608
1
1
HOT)
2 TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 8. Typical diagram for T8024F two-stage heat and
two-stage cool system with manual changeover.
FAN RELAY
STAGE­ONE HEAT RELAY
STAGE ONE COOLING
COOL DAMPER
W2 Y2
B O
HEAT DAMPER
STAGE­TWO COOL­ING
M20214
STAGE TWO HEAT RELAY
3 69-1465—3
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
M12580
FAN OPERATION (FUEL) SWITCH
1
A
3
A
A
A

Setting Fan Operation (Fuel) Switch (T8001F Only)

The fan operation (fuel) switch is preset at the factory in the F position. See Fig. 9. This is the correct setting for most systems. If this system is an electric heat system, set the switch to the E position. The E setting allows the fan to turn on immediately with the heating or cooling equipment in a system where the G terminal is connected.
E
F
Fig. 9. Fan operation (fuel) switch.

Mounting Thermostat to Wallplate

1. Slide SYSTEM switch to the Off position.
2. Slide the thermostat straight into the wallplate until
it is flush against the wall. See Fig. 10.
PM
TUE
Fan
Auto
On
PRESS THERMOSTAT STRAIGHT
BACK ONTO WALLPLATE
Hold
Select
System
Cool
Off
Heat
M1861
Fig. 10. Mounting thermostat to wallplate.

INSTALLER SETUP

1. Enter Installer Setup. a. Use or keys to set the temperature set-
point to 52°F (11°C).
SET
HT.
b. Press the and keys simultaneously for
more than two seconds to enter installer setup.
c. When released, the three-digit software revi-
sion code is displayed.
d. Press the key. Factory configuration (FC) is
displayed. (A typical example is shown, but information displayed varies by model. This information is for factory use only).
M12582
M1258
M12584
Optional System Checkout
When in steps 1c and 1d only, pressing the key can be used to turn heat or cool outputs on and off. Change the SYSTEM switch setting to test heat or cool outputs. No action takes place If the system switch is in the Off position.
Examples:
System setting at HEAT: If heat is on, pressing
the key turns it off; if heat is off, pressing the key turns it on.
System setting at COOL: If cool is on, pressing
the key turns it off; if cool is off, pressing the key turns it on. The 5 minute minimum off time is bypassed.
NOTE: In installer setup only, each press of the key
momentarily displays 1. Each press of the key momentarily displays 2. When the keys are released, these one-digit codes are no longer displayed.
2. Setting °C or °F. a. Press the key again to display the current
setting.
Setting °F/°C Indication and Heat Cycle Rate
The following instructions provide the information necessary to change the heating cycle rate to match the heating equipment and to choose either Fahrenheit (°F) or Celsius (°C) display.
NOTE: All four steps must be completed to save
changes to the °F/°C indication and the heat cycle rate.
69-1465—3 4
b. Press the key to change the °C or °F indica-
tion.
M12587
M12586
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
6
5
7
8
A
A
1
2
3. Setting Number of Cool/Heat Stages (T8024F Only). a. Press to display number of cool stages.
M2021
b. Press to change number of cool stages.
c. Press to display number of heat stages.
M2021
M2021
d. Press to change number of heat stages.
M2021
4. Setting Heat Cycle Rate (see Table 2) for the cycle rate options and equipment. a. Press the key to display the current heat
cycle rate setting of 1,3, 4, 5, 6, 9, or 12 cph.
M12589
NOTE: If thermostat is set to operate two stages of heat
(T8024 only), both stages operate at the selected cycle rate.
b. To change the heat cycle rate, press the key
until your choice of 1, 3, 4, 5, 6, 9, or 12 is dis­played. See Table 2.
c. Press the key to display control algorithm
configuration default.
d. Press the key again to change control algo-
rithm to C1 or C3.
C1 = Standard control algorithm. C3 = Aggressive control algorithm (can
e. Press the key again. Current configuration
cause overshooting).
(CC) is displayed. A typical example is shown, but CC varies by model. (This information is for factory use only.)
5. Exit Installer Setup.
PM
a. Press the key to save all changes and return
to normal operation.
Table 2. Heating Cycle Rate
System Cycles Per Hour
Steam, gravity 1
Hydronic heat, condensing gas
a
furnaces
3
Gas or oil forced air 6
Electric heat 9
Special applications
a
High efficiency furnace (90+).
b
Refer to the equipment manufacturer ’s instructions.
b
4, 5, 12
M12588
M1469
M1469
M12590A
5 69-1465—3
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
A
A
A
A

OPERATION

Setting FAN and SYSTEM Switches

Fan and system settings are controlled manually by using the switches located at the bottom of the thermostat case. See Fig. 11.
FAN Switch
Fan switch settings are:
On: The fan runs continuously. Use for improved air
circulation and air quality.
Auto: Normal setting for most homes. In cooling, the
fan starts and stops with the cooling equipment. In heating, the fan is controlled directly by the heating equipment and may start a few minutes after the heating equipment turns on (most systems). When the fan operation (fuel) switch is in the E position, the fan starts and stops with the heating equip­ment.
Slide the FAN switch in the lower left corner of the thermostat to select the desired fan setting.
SYSTEM Switch
System switch settings control thermostat operation as follows:
Cool: The thermostat controls the cooling system. Off: Both heating and cooling are off. Heat: The thermostat controls the heating system.
Slide the SYSTEM switch in the lower right corner of the thermostat to select the desired system setting.
PM
TUE
Fan
Auto
On
Fig. 11. Digital Display and System switches.
Hold
Select
System
Cool
Off
Heat
M18612

Setting Current Time and Day

1. To Set Curren t Time. a. Press Select twice.
SET
PM
M12591
b. Press or to set current time.
SET
PM
2. To Set Day of Week. a. Press Select again.
M12592
M12593
b. Press or to set current day.
M12594
To use the preprogrammed time and temperature (see Table 3) press Hold to exit the programming mode.

Setting Time and Temperature

The T8001F and T8024F are preprogrammed with the time and temperature settings shown in Table 3. For instructions on programming the thermostat, refer to the Owner’s Guide, form no. 69-1464.
Table 3. Preprogrammed Time and
Temperature Settings.
Period Time Heat Setpoint Cool Setpoint
Wake 6:00 AM 70°F (21°C) 78°F (26°C)
Leave 8:00 AM 62°F (17°C) 85°F (29°C)
Return 6:00 PM 70°F (21°C) 78°F (26°C)
Sleep 10:00 PM 62°F (17°C) 82°F (28°C)
69-1465—3 6

CHECKOUT

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT

Heating

1. Slide the SYSTEM switch to Heat and the FAN switch to Auto.
2. Press and hold the ▲ key to raise the temperature setting several degrees above the room tempera­ture; the heating equipment should start. In con­ventional systems, the system turns on the fan through the use of a time delay relay or through a limit control. When the fan operation (fuel) switch is in the E position, the fan starts immediately.
3. Press the ▼ key to lower the temperature setting below the room temperature. Heating equipment should stop.

Cooling

CAUTION
Damage To compressor possible. Operating at too low of an outdoor temperature may cause compressor damage.
Do not operate cooling if outdoor temperature is
below 50°F (10°C).
Allow compressor to remain off for five minutes
before restarting.
Refer to manufacturer’s recommendations.
1. Slide the SYSTEM switch to Cool and the FAN switch to Auto.
2. Press the ▼ key to lower the temperature setting several degrees below the room temperature; the cooling equipment should start. The fan starts and stops with the cooling equipment.
NOTE: If unit doesn’t start immediately, remem-
ber, the thermostat has a built-in minimum off-time of five minutes to protect the com­pressor.
3. Press the ▲ key to raise the temperature setting above the room temperature. Cooling system should shut down.
Fan
1. Slide the SYSTEM switch to Off and the FAN switch to On. The fan should run continuously.
2. Slide the FAN switch to Auto. In heating, the fan is controlled directly by the heating equipment and may start a few minutes after the heating equip­ment turns on (on most systems). In cooling, the fan starts and stops with the cooling equipment.
Be sure all equipment responds correctly to the thermostat.
7 69-1465—3
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
Home and Building Control Home and Building Control
Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
69-1465—3 G.H. Rev. 9-01 Printed in Mexico www.honeywell.com/yourhome
Loading...