T775 Series 2000 Electronic
Stand-Alone Controllers
SPECIFICATION DATA
• Internal Time Clock Scheduler The Setback and Disable
Output options, controlled by the built-in scheduler or digital
input, will help save energy during unoccupied times and
give you more control of the equipment without needing to
purchase an additional time clock. Run times can be
displayed for the first 4 relay outputs.
• Up To Two Independent Modulating Outputs Each
output can be individually configured for 0-10 Vdc, 2-10
Vdc, 4-20 mA or Series 90.
• Modulating High Or Low Limit Control To protect your
equipment from freezing or overheating, models offering
this feature give you the ability to adjust your control
temperature at Sensor A to protect equipment at Sensor B.
The control adjusts its modulating output to prevent
exceeding the user-entered High or Low limit for Sensor B.
• Optional Configurable Integral And Derivative Times
Standard on every device, this feature delivers pinpoint (PI
or PID) control on modulating outputs set up by default to
behave just like the previous T775 Series 1000, but now
you can adjust reaction times and behavior, giving you
more control. Anti-integral wind-up is standard.
• Reset Models With Simplified Setup Reset programming is easy. Simply enter the high and low control temper-
DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of commercial and agricultural controls capable of
remote sensing of temperature and providing switched and/or
proportional outputs to various types of loads.
IMPORTANT
The T775 is an operating control, not a limit or safety
control. If used in applications requiring safety or limit
controls, a separate safety or limit control device is
required.
FEATURES
• Easy-To-Use Graphical Interface Operating the new
T775 is easy and the intuitive programming will save you
time on every job. Each model includes a keypad lockout.
• NEMA 4X Enclosure Option Certain models are offered
with NEMA 4X enclosures to protect them from water and
corrosion for installations like washdown areas, animal
confinement areas, swimming pools and other similar
locations.
atures and the corresponding high and low outdoor
temperatures. As your outside temperature gets colder, the
setpoint temperature automatically adjusts to save energy.
• Configurable Minimum Off Time If needed, setting a
minimum off time can protect equipment and reduce the
need for a separate time delay device.
• Sensor Calibration Calibrate input sensors up to +/-10° F
(+/-6° C) for temperature and up to +/-10% of range for
other sensors (e.g. pressure, humidity) to compensate for
resistance drops in longer sensor wire runs.
• Special Models Five T775 models are available for
special applications:
— Universal Models (T775U2006 and T775U2016) to
control pressure, humidity, or any medium with an
analog input
— Special Boiler Model (T775P) for boiler control
— Special Staged Sequencing Model (T775L) for
sequence staging of relays with one or two setpoints
— Special Expansion Model (T775S) for staging up to
12 relays with two setpoints
E4436

T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SPECIFICATIONS
Power: 24, 120, or 240 Vac; 50/60 Hz
A separate earth ground is required for any power source.
Power Consumption:
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz
Operating & Storage Temperature Ambient Rating:
• -40°F to 125°F (-40°C to 52°C) @ 50 Hz
• -40°F to 140°F (-40°C to 60°C) @ 60 Hz
Relative Humidity: 5% to 95% non-condensing
Dimensions: refer to Fig. 1 on page 4.
All T775 controllers are field-mountable in any orientation
to either a panel or wall.
Digital Input (DI): 18 Vdc and 3.5 mA (for choosing external
contact)
Digital Output (DO) Alarm (T775P only):
• Alternating Current (AC):
— 30 Vac RMS; 1.5 A steady 3 A inrush P.F. 0.45 NC
— 20 Vac RMS; 100 mA minimum load on NO and NC
contacts
• Direct Current (DC): 1 mA at 100 mV DC minimum load
NOTE: In applications requiring a gold contact signal
relay, an external signal relay or additional load
resistor may be needed for the digital output.
Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)
Modulating Outputs:
• 0-10 Vdc; drive a minimum of 2,000 Ohms
• 2-10 Vdc; drive a minimum of 2,000 Ohms
• 4-20 mA; drive a maximum of 600 Ohms
• Electronic Series 90; requires 340 Ohm resistor (included)
across terminals R and W
• Floating
Sensed Temperature Limits (displayed):
• Minimum -60°F (-51°C)
• Maximum 270°F (132°C)
High Setpoint Limit: An irreversible high limit setpoint can be
configured to meet local code requirements.
Sensed Temperature Accuracy:
• T775: 1°F/C @ ambient room temperature of 77°F (25°C)
• 50021579-001 and T775-SENS-WR: ±0.42°F from -22°F
to 248°F (+/-.24°C from -30°C to 120°C)
Setpoint Range: -40°F to 248°F (-40°C to 120°C)
Time Clock: Two settable time periods per day are standard
on all models.
Volatile Memory: The date and time settings are retained for
24 hours after a power outage. After a power loss of more
than 24 hours, the date and time settings may need to be
reentered. All other settings are stored permanently.
Approvals: UL 60730-1 for US and Canada, CuL, C-tick
COMPATIBLE COMPONENTS
Temperature Sensors
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all models
except NEMA 4X models)
• T775-SENS-STRAP – Strap on sensor with wiring box
• T775-SENS-WR – Water resistant with 5 foot leads
(included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031D2003 – 5 inch immersion sensor with wiring box
(use immersion well; P/N 50001774-001)
• C7031J2009 – 12 foot duct averaging sensor with wiring
box
• C7046D1008 – 8 inch duct probe with mounting flange
• C7100D1001 – 12 inch fast response, duct averaging
sensor with flange
• C7130B1009 – Room mount sensor
Humidity Sensors (T775U only)
The controller accepts 0-10 Vdc or 4-20 mA input with a range
of 0-100%
H7625, H7635, and H7655 models (available in 2, 3, and
5% RH accuracy) can be used.
Differential Pressure Sensors (T775U only)
P7640A and PWT pressure transducer models with selectable
pressure ranges can be used.
The controller accepts pressure sensors with a signal output
of 0-10 Vdc or 4-20 mA for any output range within the
following ranges (the minimum and maximum for the sensor
output range can be adjusted within the following limits):
• -500 to 500 PSI
• -30.0 to 30.0 inches w.c.
• -3,000 to 3,000 Pa
• -3,000 to 3,000 kPa
Universal Sensors (T775U only)
The controller accepts 0-5 Vdc, 0-10 Vdc or 4-20 mA input for
temperature, pressure, humidity, etc. They may be
programmed in units of °F, °C, %, Pa, kPa, PSI, Inches W.C.,
PPM, or None (no units). CO
are also compatible.
Actuators
For more information on compatible actuators or other
Honeywell products, such as dampers and valves, go to
www.customer.honeywell.com
Product Selection Tool under Products.
• Spring return models: ML6425, ML7425, MS4105,
MS4110, MS4120, MS7505, MS7510, MS7520, MS8105,
MS8110, MS8120
• Non-spring return models: ML6161, ML6174, ML7161,
ML7174, MN6105, MN6110, MN7505, MN7510
Accessories
• 107324A – Bulb Holder, duct insertion
• 107408 – Heat Conductive Compound, 4 ounce
• 50001774-001 – Immersion Well, stainless steel 304,
1/2 in. threading
a
See form 62-0265 – Temperature Sensors for the T775
Series 2000 Stand-alone Controller
a
sensors (C7232 and C7632)
2