Honeywell T775 Series Catalog Page

Temperature Sensors
T775 Series 2000 Sensors
A family of general use, simple to use, broadly featured electronic temperature and universal controllers for use in HVAC, agricultural, and industrial applications.
• Use the T775-SENS-OAT to measure outside air temperature.
• Some typical applications for the 50021579-001 and T775­SENSWT/WR sensors include:
• Monitoring return air temperatures
• Monitoring discharge air temperatures
• Monitoring mixed air temperatures
• All sensors:
• Fast response time and highly accurate
• 1/2 in. (6.35 mm) stainless steel probe with a thermally conductive epoxy
• 1,097 Ohms PTC at 77ÞF (25C)
• The 50021579-001 is a standard temperature sensor for indoor applications
• The T775-SENS-WR is a water resistant sensor with 5 ft leads
• The T775-SENS-WT is a water tight sensor with 6 ft leads
• The T775-SENS-OAT is for sensing outdoor air temperature and is housed in a weatherproof case for outdoor use (knockouts allow for 1/2 in. conduit connection)
• Two year warranty
Application: For indoor use in applications such as monitoring return
air, discharge air, and mixed air temperatures
Used With: T775 Series 2000
Product Number Application Sensor Type
50021579-001/U For indoor use in
T775-SENS-OAT/U Outside air temperature PT1000, 1097
T775-SENS-STRAP/U Hot or chilled water (strap
T775-SENS-WR/U For use in applications
T775-SENS-WT/U For use in applications
applications such as monitoring return air, discharge air, and mixed air temperatures
on)
such as monitoring return air, discharge air, and mixed air temperatures
such as monitoring return air, discharge air, and mixed air temperatures
1097 ohm @ 77 F PTC
ohms @ 77 F PTC
PT1000, 1097 ohms @ 77 F PTC
PT1000, 1097 ohms @ 77 F PTC
PT1000, 1097 ohms @ 77 F PTC
Operating Temperature Range Dimensions, Approximate
-40 F to 270 F
-40 F to 158 F
-40 F to +250 F
-40 F to 270 F
-40 F to 270 F
-40 C to 132 C
-40 C to 70 C
-40 C to +121 C
-40 C to 132 C
-40 C to 132 C
2 in. long x 1/4 in. dia probe with 9 in. lead
8 5/16 in. high x 3 5/8 in. wide x 2 1/4 in. deep
4 3/16 in. high x 2 5/16 in. wide x 1 11/16 in. deep
2 in. long x 1/4 in. dia probe with 5 ft. lead
2 in. long x 1/4 in. dia probe with 6 ft. lead
51 mm long x 6 mm dia probe with 227 mm lead
211 mm high x 91 mm wide x 57 mm deep
107 mm high x 59 mm wide x 43 mm deep
51 mm long x 6 mm dia probe with 1524 mm lead
51 mm long x 6 mm dia probe with 1829 mm lead
Description(F) (C) (inch) (mm)
Standard Temperature Sensor for the T775 Series 2000
1097 ohm Outdoor Air Temperature Sensor
Strap-on Sensor for Hot or Chilled Water
Water-resistant Sensor for T775 Series 2000.
Water-tight Sensor for T775 Series 2000
470 customer.honeywell.com 70-6910