Honeywell T775B, T775C, T775D User Manual

Page 1
T775A,B,C,D
Remote Temperature Controller
The T775 family of Electronic Remote Tem­perature Controllers provide on-off temperature control for ducts, tanks, chillers, heating and re­frigeration units, and other applications where electronic accuracy in addition to remote sensing is desired.
In addition, certain models of the T775 family of controllers provide on-off temperature control of heating, cooling, and ventilating systems in agri­cultural confinement buildings, storage areas and heavy industrial applications.
T775A models provide staged on-off control with
one temperature input and one to four relay output
stages.
T775B models provide staged on-off control with
two temperature inputs and two to four relay output
stages.
T775C models provide staged on-off control with
one temperature input and four relay output stages.
T775D models provide staged on-off control with
two temperature inputs and four relay output stages.
T775C,D models meet National Electrical Code
(Article 547) requirements for animal confinement
buildings.
Setpoint temperature range is -40° to +220° F (-40°
to +104°C).
Ambient temperature range is -30° to +140°F for
one and two stage models and -30° to +125°F for
three and four stage models.
T775A,B
Adjustable temperature range and differential.
LCD indication for mode and output status.
Keypad provides ease of programming and operation.
Accuracy is within +/- 1°F (at nominal operating
ambient temperature of 77°F and voltage input).
Stage(s) independently programmed for heating or cooling.
24/120/240 Vac input voltage.
Spdt relay outputs.
IMPORTANT: The T775 is an operating control, not a
limit or safety control. If used in applications requir­ing safety or limit controls, a separate safety or limit control device should be used in conjunction with the T775.
T775C,D
Linear platinum temperature sensor with T775A,B.
Water-tight linear platinum temperature sensor with
T775C,D.
G.R. • 12-94 • ©Honeywell Inc. 1994
CONTENTS
Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 5
Description/Operation ................................... 8
Checkout....................................................... 11
1 63-2489
63-2489
Page 2
T775A,B,C,D SPECIFICATIONS • ORDERING INFORMATION
Specifications
IMPORTANT: The specifications given in this publication
do not include normal manufacturing tolerances. Therefore, an individual unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor difference in performance can be expected if those conditions are changed.
MODELS: The T775A,B family of Electronic Temperature
Controllers for ducts, tanks, chillers, heating and refrig­eration units, and other applications where electronic accuracy is desired in addition to remote sensing. T775A: Staged on-off control with one temperature input
and one to four relay output stages. Includes one 193987GA Sensor.
T775B: Staged on-off control with two temperature in-
puts and two to four relay output stages. Includes two 193987GA Sensors.
MODELS: The T775C,D family of Electronic Remote Tem-
perature Controllers provides on-off temperature control of heating, cooling and ventilating systems in agricultural confinement buildings, storage areas, and heavy indus­trial applications. T775C: Staged on-off control with one temperature input
and four relay output stages. Mounted in NEMA 4X enclosure. Includes one 203401B Remote Sensor.
T775D: Staged on-off control with two temperature inputs
and four relay output stages. Mounted in NEMA 4X enclosure. Includes two 203401B Remote Sensors.
Maximum
Number
Model
Number
T775A1001 1 1 140 T775A1019 1 2 140 T775A1027 1 3 125 T775A1035 1 4 125 T775B1000 2 2 140 T775B1018 2 3 125 T775B1026 2 4 125 T775C1009 1 4 125 T775D1008 2 4 125
ELECTRICAL RATINGS:
Voltage Input: 24/120/240 Vac, 50/60 Hz (+10%/-15%). Power Consumption:
For one and two stage units:
8 VA maximum at 60 Hz. 10 VA maximum at 50 Hz.
For three and four stage units:
13 VA maximum at 60 Hz. 20 VA maximum at 50 Hz.
Inputs
of
Number of Relay Outputs
Operating
Ambient
Temperature (°F)
Ordering Information
When ordering replacement and modernization products from your wholesaler or distributor, refer to the price lists for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check the white pages of your phone directory.
2. Home and Building Control Customer Logistics Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2489 2
Page 3
T775A,B,C,D
SPECIFICATIONS
CONTACT RATINGS:
1/2 hp; 9.8 FLA, 58.8 LRA at 120 Vac. 1/2 hp; 4.9 FLA, 29.4 LRA at 240 Vac. 125 VA pilot duty at 120/240 Vac. 10A at 24 Vac (resistive).
SENSOR: Positive coefficient platinum type, 4.8 ohms/ °F,
1000 ft maximum distance between sensor and solid state controller (requires calibration over 400 ft). To maintain NEMA 4X rating, use environmental proof cable and sensor.
TEMPERATURE ACCURACY: +/-1°F (at nominal volt-
age in 77°F [25°C] ambient, nominal sensor value). Accu­racy may vary based on deviation from nominal values of input voltage, operating ambient and sensor ambient.
DISPLAY RESOLUTION: Sensed temperature and other
operating parameters are displayed via a liquid crystal display (LCD) with a resolution of 1°F or 1°C.
SETPOINT ADJUSTMENT RANGE: -40° to 220°F (-40°
to 104°C).
OPERATING AMBIENT TEMPERATURE:
One and Two Stage units: -30° to 140°F. Three and Four Stage units: -30° to 125°F.
OPERATING HUMIDITY: 5% to 95% relative humidity
(RH) noncondensing.
APPROVALS:
Underwriters Laboratories Inc. Listed: File no. E4436. Canadian Standards Assoc. certified: File no. LR47125.
DIMENSIONS: See Fig. 1 and 2. MOUNTING: Mounts on any suitable horizontal or vertical
surface (see Fig. 3 and 4 for mounting hole locations).
Fig. 1—Approximate dimensions of T775A,B in in. (mm).
SET
SELECT
3-13/16 (97)
4-3/4 (121)
ENTER
5-7/32 (134)
7/8 (22) DIAMETER
8-1/2 (216)
2-3/8 (60)
1-1/4 (32)
1-1/4 (32)
M344C
Fig. 2—Approximate dimensions of T775C,D in in. (mm)
6 (153)
5-1/4 (133)
MOUNTING HOLES
6-1/2 (165)
9
(229)
3-1/2 (89)
1-3/8 (34)
7/8 (22) DIAMETER
1-1/4 (32)
M1301B
3 63-2489
Page 4
T775A,B,C,D SPECIFICATIONS
Fig. 3—Feature locations for T775A,B.
LCD TEMPERATURE DISPLAY
PROGRAMMING KEYS
SENSOR INPUT, TOD, AND 24VAC TERMINALS
HOLE A
OUTPUT 2
KNOCKOUT B
RELAY OUTPUT STAGES
(MAXIMUM OF FOUR STAGES)
Fig. 4—Feature locations for T775C,D.
SENSOR A
NC
COM
NO
SELECT
12
3 TOD
NO
COM
NC
OUTPUT 3
C \ F
SET
4
5
24V
6
SENSOR B
ENTER
8
7
OUTPUT 1
NC COM NO
NO COM NC
120V COM 240V
SA SB
°F/°C SELECTION
1
DIP SWITCHES FOR
2
3
SENSOR SELECTION.
4
PRESENT ON T775B ONLY
MOUNTING HOLE LOCATION
LINE VOLTAGE INPUTS
KNOCKOUT C
OUTPUT 4
NOTE: T775A TERMINAL BLOCK CONTAINS ONLY TERMINALS 1-6 AND HAS NO DIP SWITCHES FOR SENSOR SELECTION
M7423
LCD TEMPERATURE DISPLAY
PROGRAMMING KEYS
SENSOR INPUT, TOD, AND 24VAC TERMINALS
HOLE A
EARTH GROUND WIRE
HOLE B
RELAY OUTPUT STAGES
SELECT
12
SENSOR
A
OUTPUT 2
NC
COM
NO
NO
COM
NC
OUTPUT 3
3 TOD
SET
C \ F
ENTER
1 2 3 4
°F/°C SELECTION
DIP SWITCHES FOR SENSOR SELECTION. PRESENT ON T775D ONLY
SA SB
6
4
5
8
7
SENSOR
24V
B
MOUNTING HOLES
OUTPUT 1
120V
NC
COM
COM
240V
NO
NO COM NC
OUTPUT 4
NOTE: T775C TERMINAL BLOCK CONTAINS ONLY TERMINALS 1-6 AND HAS NO DIP SWITCHES FOR SENSOR SELECTION
LINE VOLTAGE INPUTS
HOLE C
M7427
63-2489 4
Page 5
T775A,B,C,D
SPECIFICATIONS • INSTALLATION
ACCESSORIES:
T775A,B:
A775A1003 Temperature Sensor Simulator. C7100C Duct Mount Averaging Sensor. 198212CA Water Resistant Sensor. 203401B Water Tight Sensor. T7047C1090 Wall Mounted Sensor Case. 107324A Bulb Holder, duct insertion. 121371A Copper Immersion Well. 121371E Stainless Steel Well.
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Disconnect power before installation to prevent electrical shock or equipment damage.
LOCATION AND MOUNTING
Mount the controller on any convenient interior location using the two mounting holes provided on the back of the metal enclosure (mounting screws are not provided and must be obtained separately). Use controller dimensions in Fig. 1 (T775A,B) or Fig. 2 (T775C,D) as a guide.
SENSOR LOCATION
The 193987GA Sensor can be located up to 1000 feet (304 meters) from the T775 using standard AWG 18/2 unshielded wire. For cable runs greater than 25 feet shielded cable is recommended. See Fig. 5. It may be located on pipes, in an immersion well, in a wall-mounted case or on a bulb holder. See Fig. 6. The 193987GA is not a water tight or water resistant sensor. For wet applications, see the Accesso­ries list in the Specifications section.
Multiple sensors can be parallel-series wired to sense average temperatures in large spaces.
To maintain control accuracy, the number of sensors parallel-series wired must be of the n2 power (for example, 4, 9, 16, etc.). See Fig. 7.
107048 Heat Conduction Compound, 4 ounce. C7043A1098 Case and Immersion Well for running
conduit to sensor.
T775C,D:
121371A Copper Immersion Well. 121371E Stainless Steel Well. 107408 Heat Conduction Compound, 4 ounce. C7043A1098 Case and Immersion Well for running
conduit to sensor.
Installation
cap or bulb holder for duct air sensing. To prevent moisture or condensation entering the sensor through the leadwire holes, mount the sensor with the lead wires exiting the bot­tom of the sensor.
Fig. 5—Using shielded cable for cable runs longer than 25 feet.
T775
C \ F
1 2 3
4
3 TOD
SET
4
5
24V
SENSOR
ENTER
6
8
7
SENSOR B
OUTPUT 1
NC COM NO
OUTPUT 4
GROUNDING SCREW
NO COM NC
120V COM 240V
SA SB
M7430
GROUND SHIELD TO T775 CABLE OR TO GROUNDING SCREW
SHIELDED CABLE
SHIELDED CABLE
NOTE: DO NOT GROUND SHIELDED CABLE AT SENSOR END.
NOTE: TO MINIMIZE NOISE PICKUP, MAKE CONNECTION FROM SHIELDED CABLE AS CLOSE TO SENSOR BODY AS POSSIBLE.
SELECT
12
SENSOR A
OUTPUT 2
NC
COM
NO
NO
COM
NC
OUTPUT 3
NOTE: Use heat conductive compound in immersion wells.
See optional Accessories in the Specifications section.
SENSOR MOUNTING
Sensors can be mounted on a wall or panel for sensing space temperature (Fig. 6), strapped to a pipe or inserted in a well (Fig. 8) for hot/cold water sensing, or taped to a standard
CAUTION
Make sure that metal tube of sensor does not short against T terminals in wall-mounted case.
5 63-2489
Page 6
T775A,B,C,D INSTALLATION
Fig. 6—Sensor mounted on wall.
T7047C1090 WALLMOUNT SENSOR CASE (OPTIONAL)
LEADWIRES TO T775
SCREW TERMINAL
SCREW TERMINAL
CAUTION: POSITION SENSOR AWAY FROM SCREW TERMINALS
BLACK LEAD
193987GA SENSOR
WHITE LEAD
M8109A
Fig. 7—Parallel-series wiring of sensors.
SENSORS
TO T775 CONNECTIONS 1 AND 2 (SENSOR A) OR 7 AND 8 (SENSOR B)
M7431
Fig. 8—Sensor inserted in immersion well.
COVER SENSOR LEADS WITH HEAT CONDUCTIVE COMPOUND
SENSOR PLACED IN WELL
1/2 NPT
IMMERSION WELL
M5249
WIRING
WARNING
Disconnect power before installation to prevent electrical shock or equipment damage.
Disconnect external power before wiring to prevent elec­trical shock or equipment damage. All wiring must comply with applicable codes and ordinances.
IMPORTANT: The T775 is an operating control, not a
limit or safety control. If used in applications requir­ing safety or limit controls, use a separate safety or limit control device in conjunction with the T775.
WARNING
Do not use 24 Vac power at terminals 5 and 6 to power any external loads if 120 Vac or 240 Vac is used to power the T775.
Refer to Fig. 3 or 4 for locating the appropriate power inputs, remote sensor input, load output terminals, contact closure input and sensor selection switch. Access to the terminals can be gained through standard conduit knockouts (A through C) located around the perimeter of the enclosure.
NOTE: Hole A should only be used for sensor, low-voltage
and contact closure wiring.
63-2489 6
Page 7
T775A,B,C,D
INSTALLATION
When wiring the input power, only one source of power can be applied to the T775 (for example, 24 Vac or 120 Vac or 240 Vac). Knockouts B and C can be used to gain access to 120 Vac or 240 Vac input terminals and the load relay output terminals.
See Fig. 11 through 14 for typical T775 wiring and applications.
IMPORTANT: Erratic temperature readings from the
193987GA Sensor can be caused by poor wiring prac­tices that must be avoided to assure proper operation:
• Do not route the temperature sensor wiring with building power wiring.
• Do not locate the temperature sensor wiring next to control contactors.
• Do not locate the temperature sensor wiring near electrical motors.
• Do not locate the temperature sensor wiring near welding equipment.
• Make sure good mechanical connections are made to both the sensor and the controller.
• Do not mount the sensor with the leadwire end (wire end) pointing up in an area where condensation can occur.
If any of the above conditions cannot be avoided, use
shielded cable.
NOTE: Ground the cable shield at the T775 connection only,
not at the sensor connection ( see Fig. 5).
DEVICE SETUP
1. Determine the loads to be controlled and the operating
mode (heat or cool) and enter in the Device Programming Worksheet.
For example: Load 1: Compressor 1 (cool)
Setpt 1 ______ On at _______ Diff 1 _______ Off at _______
2. For two sensor models (T775B), determine which
loads will be controlled from sensor A or sensor B and enter on the worksheet.
For example: Load 1: Compressor 1 (cool)—Sensor A
Setpt 1 ______ On at _______ Diff 1 _______ Off at _______
3. Determine the setpoint (Setpt) and the switching dif-
ferential (Diff) for each load and enter on the worksheet.
For example: Load 1: Compressor 1 (cool)—Sensor A
Setpt 1 ______ On at _______ Diff 1 _______ Off at _______
4. Refer to the Control Algorithm subsection in Descrip-
tion/Operation section to calculate the load on and off tem­peratures. Enter them on the worksheet. Remember that the on/off outputs are off at setpoint in both the heating and
78°F
4°F
cooling operating modes. When in cooling mode, the load will be turned off at setpoint plus the differential. When in heating mode, the load will be turned on at setpoint minus the differential.
For example: Load 1: Compressor 1 (cool)—Sensor A
Setpt 1 ______ On at _______ Diff 1 _______ Off at _______
78°F
4°F
82°F 78°F
CAUTION
The T775 will not allow the user to program for both heating and cooling loads to be energized at the same time.
If this situation results, cooling loads will be energized and heating loads will be prevented from also energizing. The number (1,2,3,4) of these nonenergized loads will flash along with the word HEAT to indicate a call for both heating and cool­ing loads controlled by one sensor has occurred and to alert the user to reprogram the affected control values.
5. Remove the T775 cover and enter the values listed on the worksheet and the date in the first column on the label inside the T775 cover.
Device Programming Worksheet
Load 1:
SetPt 1 ______________ On at _______________ Diff 1 _______________ Off at _______________
Load 2:
Setpt 2 ______________ On at _______________ Diff 2 _______________ Off at _______________
Load 3:
Setpt 3 ______________ On at _______________ Diff 3 _______________ Off at _______________
Load 4:
Setpt 4 ______________ On at _______________ Diff 4 _______________ Off at _______________
DEVICE PROGRAMMING Default Values
When power is initially applied to the T775, the control points will be at their default value set at the factory. Default values are:
Setpoint
(°F)
Stage 1 72 2 Heat Stage 2 70 2 Heat Stage 3 68 2 Heat Stage 4 66 2 Heat
Differential
(°F)
Operating
Mode
7 63-2489
Page 8
T775A,B,C,D INSTALLATION • DESCRIPTION/OPERATION
1. For the T775B and T775D, assign the loads to the appropriate sensor by setting the DIP switch in the upper right corner of the T775 (see DIP Switch Selection, Fig. 9).
2. Before programming the T775, verify that the °F/°C selection jumper is properly installed. The T775 is shipped from the factory with the jumper installed in the °F position. If °C is desired, remove the jumper.
3. Apply power to the device. The device will begin counting down from 210. This countdown sequence will last for approximately 3-1/2 minutes.
4. Press Select to override this time delay.
5. Press Select and Enter keys simultaneously to begin programming the load operating mode (Heat or Cool).
6. Press the Set (down arrow) to change to cooling. The Set (up arrow) will change back to heating.
7. Press Enter to program the displayed mode into memory.
8. Press Select to go to the next stage.
9. Repeat steps 6 through 9 for additional stages.
10. Press Select after the last stage is set up to return to the
display of the sensed temperature.
PROGRAMMING STAGE CONTROL VALUES
1. Press Select to display the current stage setpoint.
2. Press Set (up arrow) to increase or Set (down arrow) to decrease to the desired setpoint.
3. Press Enter to enter the displayed value into memory.
4. Press Select to display the current stage switching differential.
5. Press Set (up arrow) to increase or Set (down arrow) to decrease to the desired switching differential.
6. Press Enter to enter the displayed value into memory.
7. Repeat steps 1 through 6 to program each additional stage.
8. For the T775A and T775C, press Select/Select (two times) to return to stage 1 parameters. For the T775B and
T775D, press Select/Select/Select/Select (four times) to re­turn to stage 1 parameters. Scroll through the programming loop a second time to confirm that the appropriate values were entered into memory by pressing Select.
NOTE: The T775B and T775D have three options for dis-
playing the sensed temperature:
1. Sensor A only.
2. Sensor B only.
3. Alternating between Sensor A and Sensor B.
For the T775B and T775D only:
9. Press Select after viewing the switching differential
for the final stage to display Sensor A temperature only.
10. Press Select again to display Sensor B temperature
only.
11. Press Select again to alternate the display between Sensor A temperature and Sensor B temperature at approxi­mately five-second intervals.
12. Before replacing the cover on the T775, check to see that the control values were recorded on the label on the backside of the cover.
IMPORTANT: For the T775A and T775C only: After initial
programming, altering the setpoints for stage 1 up or down will result in a change in setpoints 2, 3, and 4 by the same number of degrees and in the same direction. If increasing or decreasing the setpoint for stage 1 results in exceeding the control limits (-40° to +220°F [-40° to +104°C]) for subsequent stages, the control will not allow the user to enter a value for stage 1 higher or lower than this limit. This will allow for easy sequential output staging to be modified while keeping the margin intact between setpoints
CONTROL ALGORITHM On/Off Control
The T775A and T775C operate with one temperature input supplied by the remote sensor while T775B and T775D have two temperature inputs. The T775A,B,C, and D are all capable of providing up to four stages of relay outputs for on/off control. Each stage of the T775A,B,C, and D has its own independent setpoint that can be configured to operate in either the heating or cooling mode. The mode of operation for each stage is user determined by the programming keys.
Heating Mode Operation
• Relay outputs are energized at the temperature set­point minus the differential value.
• Relay outputs are de-energized at the temperature set­point value.
63-2489 8
Description/Operation
Cooling Mode Operation
• Relay outputs are energized at the temperature set­point plus differential value.
• Relay outputs are de-energized at the temperature set­point value.
EXAMPLE: Using a device with one input and one relay
output, the corresponding load would be energized at the temperatures following based on the initial settings.
Settings
• Setpoint: 68°F
• Differential: 2°F
OUTPUTS ENERGIZED
Heating Mode:
• Stage One: Energized at 66°F.
Page 9
T775A,B,C,D
DESCRIPTION/OPERATION
Cooling Mode:
• Stage One: Energized at 70°F.
The T775B,D have dual sensor inputs and allow two separate controllers to exist within one enclosure. Selection of the stage parameters (operation mode, setpoints, and differentials) is the same as for a single sensor device after each stage is assigned its operating sensor. This assignment is hardware driven via a four position DIP switch. An explanation of the DIP switch assignments appears in Fig. 9. See Fig. 3 and 4 for the DIP switch location.
CONTACT CLOSURE OVERRIDE INPUT
A two-terminal input is provided to allow the user to override a relay-energized condition on all outputs by using a contact closure between terminal pins 3 and 4 of the terminal block for the sensor input shown in Fig. 3 and 4. This can be achieved manually or by using an EMS control­ler or time clock with normally open contacts (W7505 or S7005, for example).
When this override is active, the display will show the number of the stages that would be energized and the words STAGE ENERGIZED will flash on the display. The ener­gized stages will then be de-energized until the override returns to inactive (Off).
°F/°C SELECTION
A single jumper plug controls °F/°C indication of the displayed temperature value. The location of this jumper is shown in Fig. 3 and 4. The unit is shipped with the jumper installed in the °F mode. To operate the device in the °C mode, remove the jumper. Replacing the jumper will rein­state the °F mode.
DIP SWITCH SELECTIONS
On the T775B and D, the DIP switches are provided for assignment of each relay output stage to its operating sensor. If an individual switch is depressed toward its correspond­ing load number (1 through 4 on DIP switch) or to the right, Sensor B will be the controlling sensor for that output stage. If an individual switch is depressed to the left, Sensor A will be the controlling sensor for the output stage. An example of the switches and their corresponding positioning is shown in Fig. 9.
KEYPAD PROGRAMMING AND DISPLAY
The T775 utilizes a Liquid Crystal Display (LCD) for interactive prompting during programming and display of sensed and assigned setpoint and differential values. User programming of the T775 is accomplished through the four programming keys.
Programming Keys
The four programming keys are the Select, Up arrow, Down arrow and Enter keys.
• Select key sequentially prompts the user about what parameter is being displayed: setpoint, differential, stage energized, heat or cool (operation mode), 1,2,3,4 (indicating assigned stage). After the last parameter value is viewed, pressing the Select key will again display the control values from the beginning of the display loop.
• Up and Down arrow keys allow the displayed param­eter to be increased or decreased. After pressing the Select key, a control value can be changed by using the arrow keys. Control values will be increased or de­creased by 1°F or 1°C for each time the arrow key is depressed.
• Enter key places the new value into the memory of the microprocessor.
IMPORTANT: A control value or operation will not be
entered into the memory of the microprocessor until the Enter key is pressed.
• Press the Select and Enter keys at the same time to change the control algorithm from heating to cooling or from cooling to heating. The heating and cooling parameters are not displayed during the normal Select key sequences. The only parameters displayed after pressing the Select and Enter keys at the same time will be the stage indication and the word, heat or cool. To change the operation from heating to cooling or vice versa for a desired output stage, use the arrow keys. Once the mode is changed, pressing the Enter key is necessary to enter this change into the micropro­cessor memory. The next stage of heat or cool assign­ment will appear after the Select key is pressed. When all stages are programmed, the display will revert back to sensed temperature and load energized status.
Fig. 9—DIP switch settings for sensor selection.
SWITCH
SWITCH
PWB
PWB
AB
SIDE VIEW
SENSOR A SENSOR B
LOAD 1
LOAD 2
LOAD 1 IS CONTROLLED BY SENSOR A WHEN SWITCH IS DEPRESSED ON THE LEFT
LOAD 2 IS CONTROLLED BY SENSOR B WHEN SWITCH IS DEPRESSED ON THE RIGHT (AS SHOWN)
M3292
Control values and operation selection will remain in the
device memory even after the power is removed.
Display
Once power is applied or restored to the device, the dis­play will count down from 210 until the display reads zero, during which time any previously energized outputs will be de-energized. This is intended to protect compressors in the event of a power outage.
To avoid viewing this entire countdown, press the Select key. The LCD display will now show what it normally reads: load (sensed) temperature, stages energized, and which sen­sor (Sensor A or Sensor B) is being read for two sensor
9 63-2489
Page 10
T775A,B,C,D DESCRIPTION/OPERATION
devices. At any time during the programming procedure, the display will revert back to showing the sensed temperature and stage status indication 60 seconds after the last key closure.
For two sensor applications, the user has three options for what is displayed. The display can be configured to indicate Sensor A and Sensor B sensed temperature at a five second rate or lock onto Sensor A sensed temperature or lock onto Sensor B sensed temperature continuously.
This selection is accomplished by stopping at Sensor A or Sensor B sensed temperature points in the Select screen scrolling loop. To lock on to either sensor, the user must scroll the Select key through the loop to the sensed tem­perature prompt of interest. The display will remain at that parameter until the Select key is activated to advance the loop. When the loop is stopped at any other prompt, the display will alternatively indicate Sensor A and Sensor B sensed temperature after 60 seconds from the last key closure or immediately after the Select key is pressed at the end of the programming sequence.
Error Messages
There are seven error messages that can be displayed in response to software or hardware problems with the T775. The error Codes flashing on the display are:
SF—Sensor Failure
If the display shows a flashing SF, this indicates an out­of-range or defective sensor. Make sure that the sensors are connected properly. For T775A,C all loads will be de­energized when this error message is flashing.
For the T775B,D the loads controlled by the out-of­range sensor will be de-energized. The display will flash SF to indicate which sensor is defective or in error. In the event that only one sensor is defective, the remaining sensor and its load(s) will operate normally. Only the load(s) controlled by the defective, out-of-range, or unconnected sensor will be de-energized.
NOTE: Sensor values below -40°F or above 220°F will be
out-of-range.
EF—EEPROM Failure
The values read back from the EEPROM are not the same as written into the EEPROM. This error cannot be field
repaired. Replace the device. The EEPROM is not intended to be field repaired.
CF—Calibration Failure
A calibration resistor reading was not within the range of the Analog to Digital converter. This error cannot be field repaired. Replace the device.
OF—Stray Interrupt Failure
An unused interrupt occurred. This error cannot be field repaired. Replace the device.
CE—Configuration Error
The device hardware was configured to a nonexistent device. This error cannot be field repaired. Replace the device.
OE—ROM Error
The internal Read Only Memory (ROM) of the micro­processor is defective. This error cannot be field repaired. Replace the device.
AE—RAM error
The internal Random Access Memory (RAM) of the microprocessor is defective. This error cannot be field re­paired. Replace the device.
Setpoint Calibration
To maintain temperature accuracy, sensor wires should be 18 AWG two-conductor. If the length of the sensor wire exceeds 400 feet, recalibration will be necessary to maintain accuracy. The chart that follows shows the corresponding temperature offset to use for different sensor wire lengths. This temperature offset should be added to the desired temperature setpoint for these applications. Refer to pro­gramming instructions in the Programming section for enter­ing temperature setpoints.
Sensor Wire Length Calibration Offset
0 to 399 ft None required. 400 to 599 ft 1.0 degrees 600 to 799 ft 2.0 degrees
800 to 1000 ft 3.0 degrees
63-2489 10
Page 11
T775A,B,C,D
CHECKOUT
Checkout
After the controller is installed and wired, apply power.
Make initial adjustments and desired settings.
1. As shown in Fig. 8, record the sensed temperatures for both Sensor A and Sensor B as displayed on the device. Use the Select key to advance through the programming loop to determine and then write on the Checkout Table which loads are controlled by each sensor.
2. Write the operating mode (heat or cool) for each stage in the Checkout Table.
3. Write the sensed temperature for each load on the Sensed Temp. line.
4. Write the differential for each load on the Differential line.
5. Write the setpoint for each stage (Off temperature). Calculate the On temperature for each stage. (On tempera­ture is setpoint plus differential for cooling and is setpoint minus differential for heating.)
6. Plot the on and off (open/closed) values at which the device will energize and de-energize each output load, (Re­fer to the Device Programming Worksheet.)
7. Verify which loads are energized by using the Check­out Table. As shown in the example, the display will indi­cate, in the lower right corner, which stages are energized. If no stages are energized, the words “stage energized” will not appear.
NOTE: If the sensed temperature is between the On and Off
temperatures, the load may either be energized or de­energized. Refer to the Control Algorithm section for further explanation.
8. If an error message flashes, refer to the description of these messages. If SF flashes, check the sensor connections. If properly connected and SF continues to flash, check the sensor location to make sure it is located in an ambient con­dition that is within the sensor capability (-40° to +220°F).
9. If an error message other than SF flashes, the device cannot be field repaired. Replace the device.
11 63-2489
Page 12
T775A,B,C,D CHECKOUT
Fig. 10—Checkout Table and checkout example with Sensor A = 68°F and Sensor B = 73°F.
CHECKOUT EXAMPLE WITH SENSOR A = 68° AND SENSOR B = 73°
HEAT OR COOL
LOAD 1 (HEAT)
LOAD 2
(HEAT)
LOAD 3
(HEAT)
MODE
LOAD 4
(HEAT)
DIFFERENTIAL
DESIGNATED SENSOR
SETPOINT
SENSED TEMPERATURE
22
22
A BAB
70
OFF
ON
68
68
LOAD 1
IS ON
OFF72
ON
70
73 68
LOAD 2
IS OFF
STAGE ENERGIZED 1 3 4
SELECT ENTERSET
1
74
2
72
OFF
ON
1
76
2
74
73
LOAD 3
IS ON
LOAD 4
IS ON
OFF
ON
1
2
NOTE: RELAYS ARE DE-ENERGIZED AT SETPOINT
CHECKOUT TABLE
LOAD 1 LOAD 2 LOAD 3 LOAD 4 HEAT OR COOL SETPOINT
DIFFERENTIAL
DESIGNATED SENSOR
SETPOINT
SENSED TEMPERATURE
INDICATES LOAD STATUS WHEN SENSED TEMPERATURE REACHES SETPOINT.
1
INDICATES LOAD STATUS WHEN SENSED TEMPERATURE REACHES SETPOINT
2
MINUS DIFFERENTIAL (HEAT MODE).
63-2489 12
M7426
Page 13
Fig. 11—Two-stage control, 24 Vac input, 24 Vac load.
SENSOR B to pins 7 AND 8 for T775B, D
SENSOR
24 VAC
LOAD 2
LOAD 1
SELECT
12
SENSOR A
OUTPUT 2
NC
COM
NO
3 TOD
C \ F
SET
ENTER
SA SB
6
4
7 8
5
24V
OUTPUT 1
120V
NC
COM
COM
240V
NO
DIP SWITCHES FOR SENSOR
1
SELECTION.
2
PRESENT ON
3
4
T775B, D ONLY
TEMPERATURE FALL
DIFFERENTIAL
2
SETPOINT 2
DIFFERENTIAL
1
SETPOINT 1
TEMPERATURE FALL
COOL MODE
RELAY 1 AND 2 ENERGIZED
RELAY 1 ENERGIZED
NULL
HEAT MODE
NULL
RELAY 1 ENERGIZED
RELAY 1 AND 2 ENERGIZED
T775A,B,C,D
CHECKOUT
TEMPERATURE RISE
SETPOINT 1 DIFFERENTIAL
#1
SETPOINT 2
DIFFERENTIAL
#2
TEMPERATURE RISE
M7421
13 63-2489
Page 14
T775A,B,C,D CHECKOUT
Fig. 12—Two-stage control, 120 or 240 Vac input; 120 or 240 Vac load.
SENSOR B to pins 7 AND 8 for T775B, D
SENSOR A
120 VAC INPUT; 120 VAC LOADS
3 TOD
SET
6
4
7 8
5
24V
SELECT
12
SENSOR A
ENTER
C \ F
SA SB
DIP SWITCHES FOR SENSOR
1
SELECTION.
2
PRESENT ON
3 4
T775B, D ONLY
SENSOR B to pins 7 AND 8 for T775B, D
SENSOR A
OUTPUT 2
NC
COM
NO
LOAD 1 LOAD 2
LOAD 1 LOAD 2
240 VAC INPUT; 240 VAC LOADS
3 TOD
SET
6
4
5
24V
SELECT
12
SENSOR A
OUTPUT 1
NC COM NO
ENTER
7 8
120V COM 240V
C \ F
SA SB
DIP SWITCHES FOR SENSOR
1
SELECTION.
2
PRESENT ON
3 4
T775B ONLY
WHT
120 VAC
BLK
TEMPERATURE FALL
DIFFERENTIAL 2
SETPOINT 2
DIFFERENTIAL 1
SETPOINT 1
TEMPERATURE FALL
COOL MODE
RELAY 1 AND 2 ENERGIZED
RELAY 1 ENERGIZED
NULL
HEAT MODE
NULL
RELAY 1 ENERGIZED
RELAY 1 AND 2 ENERGIZED
TEMPERATURE RISE
SETPOINT 1
DIFFERENTIAL 1
SETPOINT 2
DIFFERENTIAL 2
TEMPERATURE RISE
OUTPUT 2
NC
COM
NO
LOAD 1 LOAD 2
LOAD 1 LOAD 2
OUTPUT 1
NC COM NO
120V COM 240V
63-2489 14
RED
240 VAC
BLK
M7422
Page 15
Fig. 13—Four-stage control, 24 Vac input; 24 Vac load.
SELECT
12
SENSOR A
SENSOR A
24 VAC
SENSOR B to pins 7 AND 8 for T775B,D
3
TOD
T775A,B,C,D
CHECKOUT
C \ F
1 2
DIP SWITCHES
3
FOR SENSOR
4
SELECTION.
SET
ENTER
SA SB
6
4
5
8
7
SENSOR
24V
B
PRESENT ON T775B,D ONLY
LOAD 4
TEMPERATURE FALL
DIFFERENTIAL 3
SETPOINT 3
LOAD 3
RELAY 1,2 AND 3 ENERGIZED
LOAD 1
LOAD 2
COOL MODE
RELAY 1 AND 2 ENERGIZED
OUTPUT 2
NC
COM
NO
NO
COM
NC
OUTPUT 3
TEMPERATURE FALL
OUTPUT 1
120V
NC
COM
COM
240V
NO
NO COM NC
OUTPUT 4
HEAT MODE
RELAY 1 ENERGIZED
NULL
DIFFERENTIAL 2
SETPOINT 2
DIFFERENTIAL 1
SETPOINT 1
N OTE: FOR THERMOSTAT APPLICATIONS, CONNECT NO CONTACT OF COOLING STAGE TO Y1 (AND SECOND STAGE TO Y2) CONNECT NO CONTACT OF HEATING STAGE TO W1 (AND SECOND STAGE TO W2).
RELAY 1 ENERGIZED
NULL
TEMPERATURE RISE
RELAY 1 AND 2 ENERGIZED
RELAY 1,2 AND 3 ENERGIZED
SETPOINT 1
DIFFERENTIAL 1
SETPOINT 2
DIFFERENTIAL 2
SETPOINT 3
DIFFERENTIAL 3
TEMPERATURE RISE
M7425
15 63-2489
Page 16
T775A,B,C,D CHECKOUT
Fig. 14—Four stage control, 120 or 240 Vac input, 120 or 240 Vac load.
SENSOR B to pins 7 AND 8 for T775B, D
SENSOR A
120 VAC INPUT; 120 VAC LOADS
3 TOD
SET
6
4
5
24V
SELECT
12
SENSOR A
OUTPUT 2
NC
COM
NO
NO
COM
NC
OUTPUT 3
8
7
SENSOR B
OUTPUT 1
ENTER
120V
NC
COM
COM
240V
NO
NO COM NC
OUTPUT 4
C \ F
SA SB
1 2 3
4
DIP SWITCHES FOR SENSOR SELECTION. PRESENT ON T775B,D ONLY
WHT
120 VAC
BLK
TEMPERATURE FALL
DIFFERENTIAL 4
SETPOINT 4
DIFFERENTIAL 3
SETPOINT 3
DIFFERENTIAL 2
SETPOINT 2
COOL MODE
RELAY 1,2,3 AND 4 ENERGIZED
RELAY 1,2 AND 3 ENERGIZED
RELAY 1 AND 2 ENERGIZED
RELAY 1 ENERGIZED
SENSOR B to pins 7 AND 8 for T775B, D
SENSOR A
LOAD 4
SENSOR A
OUTPUT 2
NC
COM
NO
COM
OUTPUT 3
LOAD 3
240 VAC INPUT; 240 VAC LOADS
3 TOD
SET
6
4
5
SENSOR
24V
B
T775A
SELECT
12
NO
NC
LOAD 2 LOAD 1
ENTER
8
7
OUTPUT 1
120V
NC
COM
COM
240V
NO
NO COM NC
OUTPUT 4
C \ F
SA SB
1 2 3
4
DIP SWITCHES FOR SENSOR SELECTION. PRESENT ON T775B,D ONLY
RED
240 VAC
BLK
DIFFERENTIAL 1
SETPOINT 1
TEMPERATURE FALL
NULL
HEAT MODE
NULL
RELAY 1 ENERGIZED
RELAY 1 AND 2 ENERGIZED
RELAY 1,2 AND 3 ENERGIZED
RELAY 1 ,2,3 AND 4 ENERGIZED
TEMPERATURE RISE
SETPOINT 1
DIFFERENTIAL 1
SETPOINT 2
DIFFERENTIAL 2
SETPOINT 3
DIFFERENTIAL 3
SETPOINT 4
DIFFERENTIAL 4
TEMPERATURE RISE
LOAD 4
LOAD 3
LOAD 2 LOAD 1
M7424
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9
63-2489 16
Printed in U.S.A. www.honeywell.com/building/components
Loading...