Temperature Controllers

T775 Series 2000 Special Stand-Alone Controllers

The T775 electronic remote temperature controllers are the next generation of commercial and agricultural controls capable of remote sensing of temperature, humidity, pressure, etc., and providing switched and/or proportional outputs to various types of loads.

• Universal model (T775U) can control pressure, humidity, or any variable analog input

• Special boiler model (T775P) for boiler control

• Special Staged Sequencing Model (T775L) for sequence staging of relays with one or two setpoints

• Special Expansion Model (T775S) for staging up to 12 relays with two setpoints (each T775S provides 4 relays)

• Save time on installations with the easy-to-use graphical Interface, large display, and the intuitive programming

• Use the time clock scheduler or digital input to control the setback and disable output options to help save energy

• Provide very fast or very fast response times on modulating outputs by adjusting the integral and derivative times (PI or PID)

• Configure models with reset in a few easy steps

• Eliminate the need for a separate time delay device and protect equipment with the minimum off time option

• Use the T775L and T775P to stage up to 12 relays (with optional T775S) from two independent heat or cool setpoints

• Support for digital output alarm on the T775P configurable based on minimum, maximum, or differential temperature

Type: Stage Sequencer with Reset Option-NEMA 1 Application: Staging controller for applications where electronic

accuracy and remote sensing of temperature is required. Bulb Size (T775L, T775P): 1/4 in. diameter x 2 in. long

(6.35 mm diameter x 50.8 mm) Accuracy: ±1 F at 77 F (±1 C at 25 C)

Sensor Element: 1097 ohms PTC at 77 F (25 C)

Maximum distance to sensor: Up to 1,000 ft (up to 304 m)

Relay Contact Ratings (24 Vac): 10.0A resistive

(120 Vac): 1/2 hp; 9.8 AFL, 58.8 ALR, 125 VA Pilot Duty (240 Vac): 1/2 hp; 4.9 AFL, 29.4 ALR, 125 VA Pilot Duty Voltage: 24 Vac or 120/240 Vac

Analog Output Type: 2-10 Vdc; 0-10 Vdc; 4-20 mA; Electronic Series 90

Frequency: 50 Hz; 60 Hz

Operating Ambient Temperature Range:

-40 F to 125 F @ 50 Hz; -40 F to 140 F @ 60 Hz (-40 C to 52 C @ 50 Hz; -40 C to 60 C @ 60 Hz)

Setpoint Temperature Range: -40 F to 248 F (-40 C to 120 C)

Throttling Range: 1 F to 150 F (0.5 C to 66 C)

Differential Temperature: 1 F to 150 F (0.5 C to 66 C)

Approvals C-Tick: Approved

Underwriters Laboratories, Inc: Approved

CE: Approved

Canadian Underwriters Laboratories, Inc: Approved

Other: IP65: Approved

Accessories:

107324A-Capillary Holder Assembly for duct insertion, 8 3/8 in. long H7655A1001-Humidity Transmitter, 5% RH accuracy, wall mount,

without temp output

H7655B1009-Humidity Transmitter, 5% RH accuracy, duct mount, with optional 20K ohm temp output

P7640A1000-Differential Pressure Transmitter, 0-1.0, 0-0.5, 0-0.25, or 0-0.1 in. w.c., unior bi-directional, panel mount, with display

P7640A1018-Differential Pressure Transmitter, 0-1.0, 0-0.5, 0-0.25, or 0-0.1 in. w.c., unior bi-directional, panel mount, without display

P7640A1026-Differential Pressure Transmitter, 0-10, 0-5, 0-2.5, 0-1.0 in. w.c., unior bi-directional, panel mount, with display

P7640A1034-Differential Pressure Transmitter, 0-10, 0-5, 0-2.5, 0-1.0 in. w.c., unior bi-directional, panel mount, without display

P7640B1008-Differential Pressure Transmitter, 0-1.0, 0-0.5, 0-0.25, or 0-0.1 in. w.c., unior bi-directional, duct mount, with display

P7640B1016-Differential Pressure Transmitter, 0-1.0, 0-0.5, 0-0.25, or 0-0.1 in. w.c., unior bi-directional, duct mount, without display

P7640B1024-Differential Pressure Transmitter, 0-10, 0-5, 0-2.5, 0-1.0 in. w.c., unior bi-directional, duct mount, with display

P7640B1032-Differential Pressure Transmitter, 0-10, 0-5, 0-2.5, 0-1.0 in. w.c., unior bi-directional, duct mount, without display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stages

 

Relay

Sensor

 

 

Digital

Output

 

Sensors

Loop

Product Number

Output

Inputs

Description

Expandable

Output

Reset

Replaces

Included

Control

 

 

 

 

 

 

 

 

 

 

T775L2007/U

4 SPDT

2

Stage sequencer

Add 1 or 2

 

Yes

50021579-001 (1)

Yes

 

 

 

with reset option

T775Ss

 

 

 

 

 

 

 

 

 

(4 relays ea)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T775P2003/U

4 SPDT

3

Special boiler with

Add 1 or 2

1

Yes

50021579-001 (3)

Yes

 

 

 

reset option

T775Ss

 

 

 

 

 

 

 

 

 

(4 relays ea)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T775S2008/U

4 SPDT

Relay Expansion

 

None

 

 

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T775U2006/U

2 SPDT

2

Universal - humidity,

 

Yes

H775E1002; H775D1003;

None

 

 

(Sensor

pressure, etc.

 

 

 

H775C1004; H775B1005;

 

 

 

 

B used

 

 

 

 

H775A1063; H775A1048;

 

 

 

 

for reset

 

 

 

 

H775A1022; H775A1006

 

 

 

 

only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T775U2016/U

2 SPDT

2

Universal-Control to

 

Yes

None

 

 

 

sensor A (universal

 

 

 

 

 

 

 

 

 

input) and Sensor B

 

 

 

 

 

 

 

 

 

(temp) independently

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

356

customer.honeywell.com