Honeywell T4039 Catalog Page

Fan Coil Thermostats
T4039 Fan Coil Thermostat
Dimensions, Approximate: 4 5/8 in. high x 4 15/16 in. wide x 1 5/16 in.
deep (118 mm high x 125 mm wide x 33 mm deep)
Mounting: 4 in. square outlet box or 2-ganged outlet box Electrical Ratings: Fan Switch: 120 Vac: 5.5 AFL, 33.0 ALR; 240 Vac:
2.75 AFL, 16.5 ALR; 277 Vac: 2.4 AFL, 14.4 ALR Thermostat (Valve load): 120 Vac: 0.32 AFL, 1.0 A ALR; 240 Vac:
0.16 AFL, 0.50 ALR; 277 Vac: 0.14 AFL, 0.43 ALR
Voltag e: 120 to 277 Vac Frequency: 50 Hz; 60 Hz Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Display: No Includes: Allen wrench for cover and mounting screws Approvals Canadian Standards Association: Certified
Control line voltage valves of a fan coil unit in cooling, manual or automatic changeover heating-cooling systems.
• Directly operate one or two valves
• Positive deadband separates heating and cooling circuits in automatic models
• Includes allen wrench for cover and mounting screw
Underwriters Laboratories, Inc: File No. E34436, Vol 2, dated 3-19-73;
Guide No. XAPX
Accessories:
TG511A1000-Medium Universal Thermostat Guard with clear cover and
base, and opaque wallplate Fits T822, T834, T8034, T841, T874 with Q674, WR1F46, and others
TG511D1004-Medium Universal Thermostat Guard with Beige painted
steel cover, opaque ring base and wallplate Fits T822, T834, T8034, T841, T874 with Q674, and others
TG512A1009-Large Universal Thermostat Guard with clear cover and
base, and opaque wallplate Fits T8082, T8085, T8600, and most electronic thermostats
TG512D1003-Large Universal Thermostat Guard with Beige painted
steel cover, opaque ring base and wallplate Fits T8082, T8085, T8600, and most electronic thermostats
Commercial
Setting Temperature Range Differential Temperature Switch Position
Product Number Application
T4039B1008/U Fan coil,
T4039J1026/U 4 pipe fan
T4039M1004/U 55 F to 95 F,
T4039M1103/U 55 F to 95 F,
T4039S1016/U 4 pipe fan
T4039S1040/U 55 F to 95 F,
cooling only
coil, automatic heat-cool changeover
coil, manual heat-cool changeover
55 F to 95 F, marked COOL­WARM
55 F to 95 F, marked COOL­WARM
marked COOL­WARM
marked COOL­WARM
55 F to 95 F, marked COOL­WARM
marked COOL­WARM
13 C to 35 C, marked COOL­WARM
13 C to 35 C, marked COOL­WARM
13 C to 35 C, marked COOL­WARM
13 C to 35 C, marked COOL­WARM
13 C to 35 C, marked COOL­WARM
13 C to 35 C, marked COOL­WARM
Approximately 2 F at midscale
The differential from make of one contact to make of the opposite contact is 7 F maximum with a positive deadspot
Approximately 1 C at midscale
The differential from make of one contact to make of the opposite contact is 4 C maximum with a positive deadspot
Changeover Color(F) (C) (F) (C) System Fan
ON-OFF HI-MED-LO — Tan
OFF-HI-LO, Off breaks cooling and fan circuits
ON-OFF HI-MED-LO Automatic Tan
ON-OFF HI-MED-LO Automatic Premier
HEAT-OFF­COOL
HEAT-OFF­COOL
Remote changeover
HI-MED-LO Manual Tan
HI-MED-LO Manual Tan
switch is required to separate circuits in manual changeover heating-cooling models
Ta n
White®
Components
70-6910 487
Loading...