Fan Coil Thermostats
T4039 Fan Coil Thermostat
Dimensions, Approximate: 4 5/8 in. high x 4 15/16 in. wide x 1 5/16 in.
deep (118 mm high x 125 mm wide x 33 mm deep)
Mounting: 4 in. square outlet box or 2-ganged outlet box
Electrical Ratings: Fan Switch: 120 Vac: 5.5 AFL, 33.0 ALR; 240 Vac:
2.75 AFL, 16.5 ALR; 277 Vac: 2.4 AFL, 14.4 ALR
Thermostat (Valve load): 120 Vac: 0.32 AFL, 1.0 A ALR; 240 Vac:
0.16 AFL, 0.50 ALR; 277 Vac: 0.14 AFL, 0.43 ALR
Voltag e: 120 to 277 Vac
Frequency: 50 Hz; 60 Hz
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Display: No
Includes: Allen wrench for cover and mounting screws
Approvals
Canadian Standards Association: Certified
Control line voltage valves of a fan coil unit in cooling, manual or
automatic changeover heating-cooling systems.
• Directly operate one or two valves
• Positive deadband separates heating and
cooling circuits in automatic models
• Includes allen wrench for cover and mounting screw
Underwriters Laboratories, Inc: File No. E34436, Vol 2, dated 3-19-73;
Guide No. XAPX
Accessories:
TG511A1000-Medium Universal Thermostat Guard with clear cover and
base, and opaque wallplate Fits T822, T834, T8034, T841, T874 with
Q674, WR1F46, and others
TG511D1004-Medium Universal Thermostat Guard with Beige painted
steel cover, opaque ring base and wallplate Fits T822, T834, T8034,
T841, T874 with Q674, and others
TG512A1009-Large Universal Thermostat Guard with clear cover and
base, and opaque wallplate Fits T8082, T8085, T8600, and most
electronic thermostats
TG512D1003-Large Universal Thermostat Guard with Beige painted
steel cover, opaque ring base and wallplate Fits T8082, T8085, T8600,
and most electronic thermostats
Commercial
Setting Temperature
Range Differential Temperature Switch Position
Product Number Application
T4039B1008/U Fan coil,
T4039J1026/U 4 pipe fan
T4039M1004/U 55 F to 95 F,
T4039M1103/U 55 F to 95 F,
T4039S1016/U 4 pipe fan
T4039S1040/U 55 F to 95 F,
cooling only
coil,
automatic
heat-cool
changeover
coil, manual
heat-cool
changeover
55 F to 95 F,
marked
COOLWARM
55 F to 95 F,
marked
COOLWARM
marked
COOLWARM
marked
COOLWARM
55 F to 95 F,
marked
COOLWARM
marked
COOLWARM
13 C to 35 C,
marked
COOLWARM
13 C to 35 C,
marked
COOLWARM
13 C to 35 C,
marked
COOLWARM
13 C to 35 C,
marked
COOLWARM
13 C to 35 C,
marked
COOLWARM
13 C to 35 C,
marked
COOLWARM
Approximately
2 F at midscale
The differential
from make of
one contact to
make of the
opposite
contact is 7 F
maximum with
a positive
deadspot
Approximately
1 C at midscale
The differential
from make of
one contact to
make of the
opposite
contact is 4 C
maximum with
a positive
deadspot
Changeover Color(F) (C) (F) (C) System Fan
ON-OFF HI-MED-LO — Tan
OFF-HI-LO,
Off breaks
cooling and
fan circuits
ON-OFF HI-MED-LO Automatic Tan
ON-OFF HI-MED-LO Automatic Premier
HEAT-OFFCOOL
HEAT-OFFCOOL
— Remote changeover
HI-MED-LO Manual Tan
HI-MED-LO Manual Tan
switch is required to
separate circuits in
manual changeover
heating-cooling models
Ta n
White®
Components
70-6910 487