Honeywell ST6008A, ST6008B, ST6008C Information

ST6008A,B,C Energy Management Timers
24-HOUR OR 7-DAY TIME SWITCHES
SPECIFICATION DATA
FEATURES
• Universal application with 24-hour or 7-day programming.
• UL and CSA recognized components.
• Battery backup (quartz drive).
• Screw wiring terminals.
• Three-way override.
• Captive trippers.
ST6008A
ST6008B,C
GENERAL
Minimum on-off times are 15 minutes for the 24-hour timer and two hours for the 7-day timer.
APPLICATION
Time-based control of lighting, ventilation, heating and cooling or other electrical loads in commercial and industrial applications. The ST6008 time switches are available with 24­hour or 7-day program dial and a single pole double pole switch.
The ST6008 series is intended for surface or DIN rail mounting. The control is completely enclosed in a plastic housing and includes a terminal cover and subbase for installation and hard wiring.
® U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • All Rights Reserved
68-3002
ST6008A,B,C ENERGY MANAGEMENT TIMERS
SPECIFICATIONS
Models:
ST6008A1006: 24-hour time-based switching with
synchronous drive.
IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances; therefore, an individual unit may not exactly match the listed
ST6008B1005: 7-day time-based switching with
synchronous drive.
ST6008C1004: 7-day time-based switching with quartz
drive and battery backup.
specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
Model Type Input Voltage Relay Output Battery Reserve
ST6008A1006 24-hour synchronous 120V, 60 Hz 1 spdt N/A ST6008B1005 7-day synchronous 120V, 50 Hz 1 spdt N/A ST6008C1004 7-day quartz 120V, 50/60 Hz 1 spdt 7-day
Supply Voltage:
Synchronous: 120V, 60 Hz. Quartz: 120V, 50/60 Hz.
Switch Type:
spdt.
Switch Rating:
10
11
12
2-15/16 (75)
OUTER RING
TRIPPERS
INNER RING
ST6008A,B,C
CLEAR POLYCARBONATE  COVER
21A, 250V resistive. 1350W tungsten. 1 hp at 120V. 2 hp at 240V. 16 FLA, 96 LRA, 120V inductive. 12 FLA, 72 LRA, 240V inductive.
Power Consumption:
12
9
6
4-1/4 (108)
0.5 VA.
2-1/4 (57)
Ambient Temperature Range:
-40°F (4°C) to 180°F (82°C), synchronous units.
-14°F (26°C) to 131°F (55°C), quartz units.
Reserve Carryover:
150 hours for quartz units.
Dimensions:
See Fig. 1.
DETACHABLE 
2-5/8 (67)
TERMINAL  COVER
1-1/2 (38)
M11336
Fig. 1. ST6008A,B,C dimensions in in. (mm).