SP970A, B, C and D Manual and
Minimum Position Pressure Regulators
INSTALLATION INSTRUCTIONS
DESCRIPTION
The SP970A, B, C and D Manual and Minimum Position
Pressure Regulators provide regulated pressure to a
(22)
60
40
20
0
FRONT VIEW SIDE VIEW
1-9/16
(40)
80
2-1/4
100
(57)
2-1/2
(63)
Fig. 1. SP970A and C dimensions in in. (mm).
60
40
20
0
80
100
controlled device such as a pneumatic damper operator.
It provides either manually set pressure or manually set
minimum pressure with variable maximum pressure.
Figs. 1 and 2 show approximate dimensions.
7/8
1-7/8
(48)
1-1/2
(38)
SP970C 3-7/8 (98)
4-1/2
(114)
SP970A 3-1/2 (89)
C4857
2-1/16 (62)
3-1/4 (83)
FRONT VIEW
Fig. 2. SP970B and D dimensions in in. (mm).
® U.S. Registered Trademark
Copyright © 2002 Honeywell •All Rights Reserved
7/8
(22)
(25)
1
3-1/2 (89)
SIDE VIEW
C4858
95-7237EF
SP970A, B, C AND D MANUAL AND MINIMUM POSITION PRESSURE REGULATORS
BEFORE INSTALLATION
SP970A and C only
For panels having a thickness greater than 5/16 in.
(8 mm) but less than one in. (25 mm), use 315677A Bus
Assembly.
INSTALLATION
Mounting
The SP970A and C can be panel, surface or wall
mounted. The SP970B and D are surface or wall
mounted. See Fig. 3 and 4.
8 PSI
CENTER PUNCH MARK IN "V" GROOVE
SHOWING 8 PSI (55 kPa) CALIBRATION ENLARGED
SP97O
HEX NUT
CENTER
PUNCH
MARK
IN "V"
GROOVE
Fig. 3. SP970A and C panel mounting.
SP970A AND C
SP970 SWITCH
Fig. 4. SP970 surface or wall mounting.
Panel Mounting SP970A and SP970C
1. Drill a 5/8 in. (16 mm) hole.
2. Lock the SP970 switch and scaleplate to the panel
with a hex nut on the back of the panel. Use a second hex nut on the front panel. See Fig. 3.
MOUNTED
HERE
SHAFT
SCREW
SPRING
CLIP
C8275
PANEL-UP TO 5/16 IN.
(8MM) THICK
5/8 IN. (16MM)
DIA. HOLE
60
80
40
100
20
0
SP970B AND D
40
20
0
SCALEPLATE
HEX NUT
60
80
100
C8277
KNOB
C8278
NOTES:
√ The scaleplate, knob and two mounting nuts
are furnished with SP970A and C.
√ Do not mount the knob during installation.
Refer to the Calibration section of this document.
Surface Mounting
Use the mounting bracket as a template and secure
mounting bracket to surface. See Fig. 4. Screws are not
provided.
Piping
All connections are sharp barb 5/32 in. (4 mm) O.D.
polyethylene tubing.
CAUTION
Equipment Damage Hazard.
To prevent damage to the sharp barb
connections, do not attempt to cut or pull tubing.
To remove the tubing from the barb connections,
cut tubing a few inches from the control device.
Use a coupling to reconnect tubing.
NOTES: When the system is not copper or polyethylene
tubing, adapt as shown in Fig.5. Some models
provide parts for adapting.
SP970A-D
POST FOR
5/32 IN. (4 MM) O.D.
PLASTIC TUBING
CONNECT
1/4 IN.
(6 MM)
PLASTIC
CONNECT
1/4 IN.
(6 MM)
COPPER
Fig. 5. Adaptation piping.
Port Identification Table
The two right columns in Table 1 identifies the ports of
older Honeywell pneumatic relays when upgrading
installation.
5/32 IN. (4 MM)
O.D. PLASTIC
TUBING CUT
TO LENGTH
5/32 IN. X 1/4 IN.
(4 MM X 6 MM)
O.D. PLASTIC
CONNECTOR
(CCTI606B)
1/4 IN. (6 MM)
O.D. PLASTIC
TUBING CUT TO
LENGTH
1/4 IN. (4 MM) O.D.
PLASTIC/COPPER
ADAPTER
(CCTI633BT)
1/4 IN. (6 MM) O.D.
COPPER TUBING
C8276
95-7237EF 2
SP970A, B, C AND D MANUAL AND MINIMUM POSITION PRESSURE REGULATORS
Table 1. Port Identification.
SP970A Pressure
Regulator SP970A Minimum Position SP970B SP970C, D SP92 SP93
Main 1 1 1 1 2 M
Pilot √ 4 √ 3 4 P
Branch 2 2 2 2 3 B
Exhaust 4 √ 4 4 √ √
Calibration
All SP970A and C models are calibrated at 8 psi (55 kPa)
when the calibration mark (center punch) on the shaft is
centered at the bottom of the molded V. To calibrate,
align the center punch mark on the shaft with the bottom
of the molded V groove on the plastic surrounding shaft.
See Fig. 3. This setting equals 8 psi (55 kPa). Secure the
knob to the shaft at the proper scale setting. The knob
should be pointing to 8 psi (55 kPa). See Fig. 4.
All SP970B and D models are calibrated at 8 psi (55 kPa)
when the knob is set at 50 percent.
The large range device can be field recalibrated to other
end points with the same span from 0 psi (0 kPa) lower
limit to 26 psi (179 kPa) upper limit. The small range
device can be field recalibrated to other end points with
the same span from 0 psi (0 kPa) lower limit to 16 psi
(110 kPa) upper limit.
Checkout and Test for All Models
1. With main air connected, insert a pressure gage
into the branch line.
2. Check pressures equivalent to knob settings.
3. When minimum position is used, attach input and
increase pilot pressure.
4. Verify correct operation.
ENGINEERING DATA
Specifications
Models:
- SP970A: A bleed type pressure regulator.
- SP970B: A bleed type pressure regulator mounted
on a sheet metal panel.
- SP970C: A bleed type pressure regulator with a
dead ended pilot chamber for minimum pressure
applications.
- SP970D: A bleed type pressure regulator with a
dead ended pilot chamber for minimum pressure
applications mounted on a sheet metal panel.
Selectable Spans for psi (kPa): See Table 2.
Table 2. Selectable Spans.
Knob Rotation
Model
188 244 300
Small span 5 (34) 6.5 (45) 8 (55)
Large span 10 (69) 13 (90) 16 (110)
a
The setpoint knob normally rotates 188 degrees. Two
breakaway stops on the knob allow rotation of 244 and
300 degrees.
a
Operating Pressure (Switch and Pilot) Range:
Normal Main: 18 psi (124 kPa)
Branch: 3 to 15 psi (21 to 103 kPa)
Pilot: 3 to 15 psi (21 to 103 kPa)
Maximum Safe Air Pressure: 30 psi (207 kPa)
Ambient Operating Limits:
Temperature: 0 to 140°F (-18 to 60°C)
Relative Humidity : 5 to 95%
Air Handling Capacity:
SP970A, B: above minimum position, device feeding
pilot determines capacity. Below minimum position,
air capacity is 0.022 scfm (10 ml/s)
SP970C, D: 0.022 scfm (10 ml/s)
Air Consumption: 0.022 scfm (10 ml/s)
Scaleplate: All models ship with a 0 to 100 scaleplate
(including knob and locknuts).
Construction: Molded plastic with neoprene diaphragm,
steel spring and shaft.
Operation
SP970A and B: Three Port Switches
PRESSURE REGULATOR OPERATION
Main line air flows through the restriction into the
branchline chamber and out the nozzle. Branchline
pressure increases until it is strong enough to compress
the spring and lift the diaphragm off the nozzle. Airflow
out the nozzle is controlled by the balance between the
branchline pressure and spring force.
MINIMUM POSITION OPERATION
An external signal is connected to port 4 (exhaust port).
When the external signal is greater than the spring load,
the nozzle opens and branchline pressure is the same as
the external signal. When the external signal is less than
the spring load, branchline pressure is controlled as
described in the previous paragraph. See Fig. 6.
2 2
BRANCH
PILOT
4
MAIN
Fig. 6. SP970A/B operation.
SP970A,B
BRANCH
1
PILOT
4
SP970A,B
MAIN
1
C4298
3 95-7237EF