Current Switches

Solid and Split Core Current Transmitters

Application: Ideal for retrofit or existing installations requiring load trending (current monitoring)

Dimensions, Approximate: 2 45/64 in. high x 3 21/64 in. wide x 1 5/64 in. deep (69 mm high x 85 mm wide x 25 mm deep)

Din Rail Size: 1-3/8 in. (35 mm)

Enclosure Rating/Color: UL94-5V/Burgundy Response Time: <200 mS

Maximum Load Resistance: 650 Ohms @ 24 Vdc (Vs-10)/0.02-40.2

Isolation Voltage: 2200 Vac

Depending on model selected the current is converted into a linear and proportional output signal of 0-5 Vdc, 0-10 Vdc or 4-20 mA, which can be monitored by a building management controller. These current sensors should be used in load trending (current monitoring) type applications. The split core transmitters are ideal for retrofit or existing installations, since it is not necessary to power down the unit and disconnect any wires during the installation process. Solid core transmitters are extremely easy to install, they are an excellent choice for new installations.

Solid or split core loop-powered current transmitters for 4-20 mA models

Solid or split core 0-5 or 0-10 Vdc models

Fast response time

Integral DIN rail mounting flange

Easy wiring, polarity sensitive output

Accepts up to a 350 MCM (17.3 mm) cable

Operates up to 250 continuous amps

True RMS versions are available

RoHS and WEEE Complaint

Limited 5 Year Warranty

Supply Current: 36 mA max

Operating Temperature Range: 5 F to 104 F (-15 C to 40 C) Operating Humidity Range (% RH): 0 to 95% RH, non-condensing

Weight: 0.24 b (0.1 kg)

Approvals

CE: Pending

Underwriters Laboratories, Inc: Approved

Environmental Compliance: RoHS-Directive 2002/95/EC, WEEEDirective 2002/96/EC

 

 

 

 

 

 

 

 

 

 

 

Core

Output Switch

 

 

Response

 

 

Product Number

Description

Type

Rating

Current Range

Type

Time

Supply Voltage

Frequency

 

 

 

 

 

 

 

 

 

CTP-20-050-VFD-001

Loop Powered

Split

4-20 mA Average

0-50 Amps; 0-20

Adjustable

<200 mS

12 to 30 Vdc

30 Hz to 1 kHz

 

Current Sensor

 

True RMS

Amps; 0-10 Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

CTP-20-200-AVG-001

Loop Powered

Split

4-20 mA Average

0-150 Amps; 0-200

Adjustable

<75 mS

12 to 30 Vdc

30 Hz to 1 kHz

 

Current Sensor

 

 

Amps; 0-100 Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

CTS-05-050-VDC-001

Current

Solid

0 to 5 Vdc

0-50 Amps; 0-20

Adjustable

<100 mS

Induced from

50 Hz to 600 Hz

 

Sensors

 

 

Amps; 0-10 Amps

 

 

monitored conductor

 

 

 

 

 

 

 

 

 

 

CTS-10-250-VDC-001

Current

Solid

0 to 10 Vdc

0-250 Amps; 0-200

Adjustable

<100 mS

Induced from

50 Hz to 600 Hz

 

Sensors

 

 

Amps; 0-100 Amps

 

 

monitored conductor

 

 

 

 

 

 

 

 

 

 

CTS-20-250-AVG-001

Loop Powered

Solid

4-20 mA Average

0-250 Amps; 0-200

Adjustable

<75 mS

12 to 30 Vdc

30 Hz to 1 kHz

 

Current Sensor

 

 

Amps; 0-100 Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

CTS-20-250-VFD-001

Loop Powered

Solid

4-20 mA Average

0-250 Amps; 0-200

Adjustable

<200 mS

12 to 30 Vdc

30 Hz to 1 kHz

 

Current Sensor

 

True RMS

Amps; 0-100 Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

450

customer.honeywell.com

70-6910