Current Switches
Solid and Split Core Current Transmitters
Application: Ideal for retrofit or existing installations requiring load trending (current monitoring)
Dimensions, Approximate: 2 45/64 in. high x 3 21/64 in. wide x 1 5/64 in. deep (69 mm high x 85 mm wide x 25 mm deep)
Din Rail Size: 1-3/8 in. (35 mm)
Enclosure Rating/Color: UL94-5V/Burgundy Response Time: <200 mS
Maximum Load Resistance: 650 Ohms @ 24 Vdc (Vs-10)/0.02-40.2
Isolation Voltage: 2200 Vac
Depending on model selected the current is converted into a linear and proportional output signal of 0-5 Vdc, 0-10 Vdc or 4-20 mA, which can be monitored by a building management controller. These current sensors should be used in load trending (current monitoring) type applications. The split core transmitters are ideal for retrofit or existing installations, since it is not necessary to power down the unit and disconnect any wires during the installation process. Solid core transmitters are extremely easy to install, they are an excellent choice for new installations.
•Solid or split core loop-powered current transmitters for 4-20 mA models
•Solid or split core 0-5 or 0-10 Vdc models
•Fast response time
•Integral DIN rail mounting flange
•Easy wiring, polarity sensitive output
•Accepts up to a 350 MCM (17.3 mm) cable
•Operates up to 250 continuous amps
•True RMS versions are available
•RoHS and WEEE Complaint
•Limited 5 Year Warranty
Supply Current: 36 mA max
Operating Temperature Range: 5 F to 104 F (-15 C to 40 C) Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Weight: 0.24 b (0.1 kg)
Approvals
CE: Pending
Underwriters Laboratories, Inc: Approved
Environmental Compliance: RoHS-Directive 2002/95/EC, WEEEDirective 2002/96/EC
|
|
|
|
|
|
|
|
|
|
|
Core |
Output Switch |
|
|
Response |
|
|
Product Number |
Description |
Type |
Rating |
Current Range |
Type |
Time |
Supply Voltage |
Frequency |
|
|
|
|
|
|
|
|
|
CTP-20-050-VFD-001 |
Loop Powered |
Split |
4-20 mA Average |
0-50 Amps; 0-20 |
Adjustable |
<200 mS |
12 to 30 Vdc |
30 Hz to 1 kHz |
|
Current Sensor |
|
True RMS |
Amps; 0-10 Amps |
|
|
|
|
|
|
|
|
|
|
|
|
|
CTP-20-200-AVG-001 |
Loop Powered |
Split |
4-20 mA Average |
0-150 Amps; 0-200 |
Adjustable |
<75 mS |
12 to 30 Vdc |
30 Hz to 1 kHz |
|
Current Sensor |
|
|
Amps; 0-100 Amps |
|
|
|
|
|
|
|
|
|
|
|
|
|
CTS-05-050-VDC-001 |
Current |
Solid |
0 to 5 Vdc |
0-50 Amps; 0-20 |
Adjustable |
<100 mS |
Induced from |
50 Hz to 600 Hz |
|
Sensors |
|
|
Amps; 0-10 Amps |
|
|
monitored conductor |
|
|
|
|
|
|
|
|
|
|
CTS-10-250-VDC-001 |
Current |
Solid |
0 to 10 Vdc |
0-250 Amps; 0-200 |
Adjustable |
<100 mS |
Induced from |
50 Hz to 600 Hz |
|
Sensors |
|
|
Amps; 0-100 Amps |
|
|
monitored conductor |
|
|
|
|
|
|
|
|
|
|
CTS-20-250-AVG-001 |
Loop Powered |
Solid |
4-20 mA Average |
0-250 Amps; 0-200 |
Adjustable |
<75 mS |
12 to 30 Vdc |
30 Hz to 1 kHz |
|
Current Sensor |
|
|
Amps; 0-100 Amps |
|
|
|
|
|
|
|
|
|
|
|
|
|
CTS-20-250-VFD-001 |
Loop Powered |
Solid |
4-20 mA Average |
0-250 Amps; 0-200 |
Adjustable |
<200 mS |
12 to 30 Vdc |
30 Hz to 1 kHz |
|
Current Sensor |
|
True RMS |
Amps; 0-100 Amps |
|
|
|
|
|
|
|
|
|
|
|
|
|
450 |
customer.honeywell.com |
70-6910 |