Current Switches
Solid and Split Core Current Switches
Application: Great for monitoring fans, pumps, motors, compressors, or other electrical equipment
Dimensions, Approximate: 2 45/64 in. high x 3 21/64 in. wide x 1 5/64 in. deep (69 mm high x 85 mm wide x 25 mm deep)
Din Rail Size: 1-3/8 in. (35 mm)
Enclosure Rating/Color: UL94-5V/Burgundy Isolation Voltage: 2200 Vac
Supply Voltage: Induced from monitored conductor
Frequency: 40 Hz to 1 kHz
All of these sensors have a solid-state output with an adjustable or fixed trip point (setpoint). These current switches should be used in applications in which a “Go/No Go” current switch is required.
The current switches can be used to monitor devices with a maximum continuous operating current of up to 250 Amps. These current switches do not need to be externally powered, since the power for the switch is induced from the conductor being monitored. The split core switches are ideal for retrofit or existing installations, since it is not necessary to power down the unit and disconnect any wires during the installation process. Solid core switches are extremely easy to install, they are an excellent choice for new installations.
•Solid or split core switches with fixed or adjustable trip points
•Very low operating trip points
•LED status indication
•Integral DIN rail mounting flange
•Accepts up to a 350 MCM (17.3 mm) cable
•Operates up to 250 continuous amps
•RoHS and WEEE Compliant
•Limited 5 year warranty
Operating Temperature Range: 5 F to 104 F (-15 C to 40 C) Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Weight: 0.23 b (0.1 kg)
Approvals CE: Approved
Underwriters Laboratories, Inc: Approved
Environmental Compliance: RoHS-Directive 2002/95/EC, WEEEDirective 2002/96/EC
|
|
|
|
|
|
|
|
|
|
Core |
Normal |
|
Operating |
|
|
Product Number |
Description |
Type |
Position |
Output Switch Rating |
Range |
Trip Point |
LEDs |
|
|
|
|
|
|
|
|
CSP-C-A200-001/U |
Adjustable |
Split |
N.C. |
0.15 Amps @ 300 Vac/Vdc |
0-250A |
2.5-250 Amps |
Green – Below the trip point; |
|
Current Switch |
|
|
|
|
|
Red – Above the trip point |
|
|
|
|
|
|
|
|
CSP-O-A200-001/U |
Adjustable |
Split |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-250A |
2.0-200 Amps |
Green – Below the trip point; |
|
Current Switch |
|
|
|
|
|
Red – Above the trip point |
|
|
|
|
|
|
|
|
CSP-O-A300-001/U |
Adjustable |
Split |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-250A |
3.0-200 Amps |
Green – Below the trip point; |
|
Current Switch |
|
|
|
|
|
Red – Above the trip point |
|
|
|
|
|
|
|
|
CSP-O-F10-001/U |
Go/No Go |
Split |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-200A |
1.50 Amps |
Red – Above the trip point |
|
Current Switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CSP-O-F15-001/U |
Go/No Go |
Split |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-200A |
2.50 Amps |
Red – Above the trip point |
|
Current Switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CSS-C-F1-001/U |
Go/No Go |
Solid |
N.C. |
0.15 Amps @ 300 Vac/Vdc |
0-250A |
0.50 Amps |
Red – Above the trip point |
|
Current Switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CSS-C-F5-001/U |
Go/No Go |
Solid |
N.C. |
0.15 Amps @ 300 Vac/Vdc |
0-250A |
1.00 Amps |
Red – Above the trip point |
|
Current Switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CSS-O-A200-001/U |
Adjustable |
Solid |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-200A |
0.5-250 Amps |
Green – Below the trip point; |
|
Current Switch |
|
|
|
|
|
Red – Above the trip point |
|
|
|
|
|
|
|
|
CSS-O-A300-001/U |
Adjustable |
Solid |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-200A |
1.0-250 Amps |
Green – Below the trip point; |
|
Current Switch |
|
|
|
|
|
Red – Above the trip point |
|
|
|
|
|
|
|
|
CSS-O-F1-001/U |
Go/No Go |
Solid |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-250A |
0.20 Amps |
Red – Above the trip point |
|
Current Switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CSS-O-F5-001/U |
Go/No Go |
Solid |
N.O. |
0.30 Amps @ 200 Vac/Vdc |
0-250A |
0.50 Amps |
Red – Above the trip point |
|
Current Switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
448 |
customer.honeywell.com |
70-6910 |
Current Switches
Split Core Dimensions in inches (millimeters)
TOP VIEW
1/2 (13)
LEFT SIDE VIEW
TERMINAL
BLOCK
TRIP |
TRIP |
7/32 (6) |
TRIP OFF |
ON |
TYP. |
ADJ |
|
|
TRIP ON Above Trip Point |
|
Adj Range 2 0 250A
Output 0 3A @
200 VDC/VAC
2-27/32 (72)
FRONT VIEW |
RIGHT SIDE VIEW |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C UL US
2-45/64 (69)
49/64 3/4
(19)
(19)
9/64 (4)
1-3/8 (35)
1-5/64 (25)
3-21/64 (85)
M23580
Solid Core Dimensions in inches (millimeters)
TOP VIEW
|
TRIP |
TRIP |
13/64 (5) |
|
TRIP OFF |
ON |
TYP. |
|
ADJ |
|
|
|
TRIP ON ABOVE TRIP POINT |
|
|
|
ADJ RANGE 0 8 250A |
|
|
13/32 (10) |
OUTPUT 0 3A @ |
|
|
200 VDC/VAC |
|
||
|
2-27/32 (72) |
|
|
LEFT SIDE VIEW |
FRONT VIEW |
RIGHT SIDE VIEW |
|
|
|
25/32 |
|
|
|
(20) |
|
2-17/64
(58)
TERMINAL
BLOCK
C U® L US |
|
|
|
9/64 (4) |
|
1-3/8 (35) |
63/64 (25) |
|
3-3/8 (86) |
||
M23581 |
||
|
<![endif]>Commercial
<![if ! IE]><![endif]>Components
70-6910 |
|
|
|
449 |
|
|