8.2.1 Technical information on control connections............................................................... 71
SAFETYHoneywell • 2
1.SAFETY
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGEROUS VOLTAGE!
= WARNING or CAUTION
Table 1. Warning signs
1.1Danger
The components of the power unit of the Smart VFD HVAC are live when the
drive is connected to mains potential. Coming into contact with this voltage is
extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when
the drive is connected to mains, even if the motor is not running.
After disconnecting the drive from the mains, wait until the indicators on the
keypad go out (if no keypad is attached see the indicators on the cover). Wait 5
more minutes before doing any work on the connections of the drive. Do not open
the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no
absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the drive is disconnected from mains.
Before connecting the drive to mains make sure that the front and cable covers
of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating
voltage to the drive. Therefore, do not touch the components of the drive before
the motor has completely stopped. Wait until the indicators on the keypad go out
(if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.
voltage is present.
Always ensure
1
Honeywell • 3SAFETY
1.2Warnings
The Honeywell Smart VFD HVAC is meant for fixed installations only.
Do not perform any measurements when the drive is connected to the mains.
The touch current of the Honeywell Smart VFD HVAC exceeds 3.5mA AC.
According to standard EN61800-5-1, a reinforced protective ground connec-tion must be ensured. See chapter 1.3.
If the drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by Honeywell can be used.
At power-up, power brake, or fault reset the motor will start immediately if the
start signal is active, unless the pulse control for
Futhermore, the I/O functionalities (including start inputs) may change if parameters, applications or software are changed.Disconnect, therefore, the motor if an
unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the autoreset function is activated. See the Application Manual for more detailed information.
Start/Stop logic has been selected
.
Prior to measurements on the motor or the motor cable, disconnect the
motor cable from the drive.
Do not touch the components on the circuit boards. Static voltage discharge
may damage the components.
Check that the EMC level of the drive corresponds to the requirements of your
supply network. See chapter 5.2.
In a domestic environment, this product may cause radio interference in which
case supplementary mitigation measures may be required.
1.3Grounding and ground fault protection
CAUTION!
The Honeywell Smart VFD HVAC AC drive must always be grounded with an grounding conductor connected to the grounding terminal marked with .
The touch current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more of
the following conditions for the associated protective circuit shall be satisfied:
1.A fixed connection and
a)the protective earthing conductor has a cross-sectional area of at least 6 AWG
(10 mm
2
) Cu or 4 AWG (16 mm2) Al through its total run.
b)an automatic disconnection of the supply in case of loss of continuity of the protective
conductor. See chapter 4.
SAFETYHoneywell • 4
c)provision of an additional terminal for a second protective earthing conductor of the
same cross-sectional area as the original protective earthing conductor.
OR
2.Connection with an industrial connector according to IEC 60309 and a minimum protec-tive earthing connector cross-section of 12 AWG (2.5 mm
power cable. Adequate strain relief shall be provided.
NOTE: Due to the high capacitive currents present in the drive, fault current protective switches
may not function properly.
Do not perform any voltage withstand tests on any part of the drive. There is a
certain procedure according to which the tests shall be performed. Ignoring this
procedure may result in damaged product.
2
) as part of a multi-conductor
1.4Running the motor
MOTOR RUN CHECK LIST
Before starting the motor, check that the motor is mounted properly and
ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the
machine connected to it.
Before reversing the motor make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
Make sure that the motor terminals are not connected to mains potential.
NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from https://en-US/Pages/de-
fault.aspx.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde applicables sur le site https://en-US/Pages/default.aspx
.
1
Honeywell • 5RECEIPTOFDELIVERY
Product modified
Date:
Date:
Date:
9004.emf
2.RECEIPTOFDELIVERY
Check the correctness of delivery by comparing your order data to the drive information found
on the package label. If the delivery does not correspond to your order, contact the supplier
immediately. See chapter 2.3.
2.1‘Product modified’ sticker
In the small plastic bag included with delivery you will find a silver Product modified sticker.
The purpose of the sticker is to notify the service personnel about the modifications made in
the drive. Attach the sticker on the side of the drive to avoid losing it. Should the drive be later
modified mark the change on the sticker.
Figure 1. ‘Product modified’ sticker
2.2Unpacking and lifting the drive
The weights of the drives vary greatly according to the size. You may need to use a piece of
special lifting equipment to remove the drive from its package. Note the weights of each individual frame size in Table 2 below.
If you decide to use a piece of lifting equipment see picture below for recommendations to lift
the drive.
RECEIPTOFDELIVERYHoneywell • 6
Max. 45°
9012.emf
NOTE: Place the lifting hooks symmetrically in at least two
holes.The lifting device must be able to carry weight of the
drive.
NOTE: The maximum allowed lifting angle is 45 degrees.
2.2.1Lifting frames MR8 and MR9
Figure 2. Lifting bigger frames
The Honeywell Smart VFD HVAC undergoes scrupulous tests and quality checks at the factory
before it is delivered to the customer. However, after unpacking the product, check that no
signs of transport damages are to be found on the product and that the delivery is complete.
Should the drive have been damaged during the shipping, please contact primarily the cargo
insurance company or the carrier.
2
Honeywell • 7RECEIPTOFDELIVERY
11447_uk
A = Updated Control Board
No A = Legacy Control Board
T = Text KeyPad
G = Graphic KeyPad
Interface
1 = NEMA 1
2 = NEMA 12
3 = NEMA 3R
Enclosure Type
0 = Drive Only
1 = Disconnect Only
2 = Two Contactor Bypass
3 = Three Contactor Bypass
Contactors
0 = Drive Only or No Special Options
1 = Auto-Bypass
3 = Auto-Bypass and HOA
Options
0007 = .75 Horse Power
0010 = 1 Horse Power
0100 = 10 Horse Power
Nominal Horsepower
A= 208/230 Vac Drive Alone, 208 Vac Bypass
B = 230 Vac Bypass
C = 480 Vac
D = 600 Vac
Nominal Voltage
3 = Three Phase (3~in, 3~out)
Input Phase
HVFDSD = Honeywell SmartVFD HVAC
HVFDSB = Honeywell SmartVFD BYPASS
Product Family
HVFDSD 3 C 0100 G 1 0 0 A
2.3Type designation code
Honeywell type designation code is formed of a four-segment code. Each segment of the type
designation code uniquely corresponds to the product and options you have ordered. The code
is of the following format:
RECEIPTOFDELIVERYHoneywell • 8
2.4Accessories
After having opened the transport package and lifted the converter out, check immediately that
these various accessories were included in the delivery:
•Rubber grommets (sizes vary according to frame)
•Power cable clamps for EMC grounding
•Screws for fixing the power cable clamps
•Control cable grounding clamps
•M4 screw for EMC level change in frame MR7
•Additional grounding screw (if necessary, see chapter 1.3)
•Ferrite holder
•Optional plastic shield to prevent unintended contact with live parts from front (MR8 and
MR9, IP00)
2
Honeywell • 9MOUNTING
5.04
3.94
Ø.28
Ø.51
2.83
.55
3.94
2.44
7.48
NEMA 1
Ø.98
1.30
1.26
1.26
NE MA12
1.26
1.30
1.26
Ø.9 8
3.MOUNTING
The drive must be mounted in vertical position on the wall. Ensure that the mounting plane is
relatively even.
The drive shall be fixed with four screws (or bolts, depending on the unit size).
3.1Dimensions
3.1.1Wall mount, MR4-MR7
Figure 3. SmartVFD HVAC dimensions, MR4, wall mount
MOUNTINGHoneywell • 10
*Optional mounting holes (for NX replacement)
8.43
5.67
4.53.5 7
Ø.2 8
Ø.5 5
Ø.28
2.83
3.94*
.574.53
Ø.2 8
3.94*
NEMA1
1.38 1 .46 1.46
Ø1.30Ø1.3 0Ø.98
NEMA12
1.36 1.48 1.48
1.38 1.46 1. 46
11449_uk
7.68
5.83
Ø.61
Ø.3 5
2.83
Ø.35
5.83
9.02
2.01 1.83 1.83
NEMA1
Ø1.57Ø1.30Ø1.57
1.421.42
2.40
2.01 1.83
NEMA12
Figure 4. SmartVFD HVAC dimensions, MR5, wall mount
Figure 5. SmartVFD HVAC dimensions, MR6, wall mount
3
Honeywell • 11MOUNTING
10.20
Ø.79
9.33
7.48
Ø.35
Ø.63
Ø2.01
NEMA1
2.722.72
1.381.38
NEMA12
Ø.98
Ø1.97
2.722.72
1.77 1.77
11451 00
Ø.98
3 x 1.50
Ø2.36
2.466.46
11.42
Ø.87
Ø.43
Ø.35
13.50
8.54
Ø.35
Ø.35
26.46
27.32
8.50
37.64
9.25
11452 00
Figure 6. SmartVFD HVAC dimensions, MR7, wall mount
3.1.2Wall mount, MR8 and MR9
Figure 7. AC drive dimensions, MR8 NEMA1 and NEMA12
MOUNTINGHoneywell • 12
Ø.35
18.90
15.75
Ø.35
14.17
11.50
Ø.87
14.37
13.98
14.17
Ø.35
Ø.35
Cabinet wall
(or similar)
IP21IP54
Cabinet wall
(or similar)
11453_00
Figure 8. AC drive dimensions, MR9 NEMA1 and NEMA12 (preliminary)
3.1.3Flange mount
The AC drive can also be recessed into the cabinet wall or similar surface. A special flange
mount option is available for this purpose. For an example of a flange-mounted drive, see Figure 9.
Figure 9. Example of flange mount (frame MR9)
11454_uk
3
Honeywell • 13MOUNTING
A
C
F
11455 00
3.1.3.1Flange mount - Frames MR4 to MR6
Figure 10. presents the dimensions of the mounting opening and Figure 11. the depth dimensions of the drives with the flange mount option.
Drive outline
Opening outline
TOP
Figure 10. Flange mount cutout dimensions for MR4 to MR6
Table 4. Flange mount cutout dimensions for MR7 to MR9 [in]
Opening outline
MOUNTINGHoneywell • 16
3.034.45
7.48
8.43
4. 49
3.94
4.174.84
9.02
11456_00
Figure 13. MR7 to MR9, flange mount, depth dimensions
3
Honeywell • 17MOUNTING
C
A
9013.emf
D
B
A
B
3.2Cooling
The drive produces heat in operation and is cooled by air circulated by a fan. Enough free
space needs to be left around the drive to ensure sufficient air circulation and cooling. Different
acts of maintenance also require a certain amount of free space.
Make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of the converter.
A = clearance around the drive (see also B)
B = distance from one drive to another or distance to cabinet wall
C = free space above the drive
D = free space underneath the drive
MOUNTINGHoneywell • 18
C+D
9014.emf
FRONTSIDE
Note that if several units are mounted above one another the
required free space equals C + D (see Figure 15.). Moreover,
the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit.
Figure 15. Installation space when drives are
Type
Cooling air required
[cfm]
MR426
MR544
MR6112
MR7109
MR8197
MR9366
Table 6. Required cooling air
mounted on top of each other
3
Honeywell • 19POWERCABLING
9007.emf
PE conductor
and shield
PE conductors
Shield
4.POWERCABLING
The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals
marked with U, V and W. See Table 7 for the cable recommmendations for different EMC levels.
Use cables with heat resistance of at least +158°F. The cables and the fuses must be dimensioned according to the drive nominal OUTPUT current which you can find on the rating plate.
1st environment 2nd environment
EMC levels
Cable type
Mains cable111
Motor cable3*22
Control cable444
Table 7. Cable types required to meet standards
According to EN61800-3 (2004)
Category C2Category C3Level T
1 = Power cable intended for fixed installation and the specific mains voltage. Shielded
cable not required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and intended for the
specific mains voltage. (MCMK or similar recommended). See Figure 16.
3 = Symmetrical power cable equipped with compact low-impedance shield and intended
for the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recommended cable transfer impedance (1...30MHz) max. 100mohm/m]. See Figure 16.
*360º grounding of the shield with cable glands in motor end needed for EMC level C2.
4 =Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-
O or similar).
Figure 16.
NOTE: The EMC requirements are fulfilled at factory defaults of switching frequencies (all
frames).
NOTE: If safety switch is connected the EMC protection shall be continuous over the whole cable installation.
POWERCABLINGHoneywell • 20
4.1UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with
a minimum heat-resistance of +140/167°F. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum.
4.1.1Cable dimensioning and selection
Table 8 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes.
Recommended fuse types are gG/gL.
These instructions apply only to cases with one motor and one cable connection from the drive
to the motor. In any other case, ask the factory for more information.
4.1.1.1Cable and fuse sizes, frames MR4 to MR6, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be
made according to local regulations, cable installation conditions and cable specification. Bigger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used
fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honeywell offers recommendations also for high speed J (UL & CSA), aR (UL recognized, IEC 60269-
A004012.520AWG14AWG24-AWG10 AWG17-AWG10
C 00153.46AWG14AWG24-AWG10 AWG17-AWG10
C 00204.86AWG14AWG24-AWG10 AWG17-AWG10
C 00305.610AWG14AWG24-AWG10 AWG17-AWG10
C 00408.010AWG14AWG24-AWG10 AWG17-AWG10
C 00509.615AWG14AWG24-AWG10 AWG17-AWG10
C 007512.020AWG14AWG24-AWG10 AWG17-AWG10
*
I
[A]
L
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
4
Honeywell • 21POWERCABLING
FrameType
A00501825AWG10AWG20-AWG5AWG17-AWG8
A007524.230AWG10AWG20-AWG5AWG17-AWG8
A01003140AWG8AWG20-AWG5AWG17-AWG8
C 010016.025AWG10AWG20-AWG5AWG17-AWG8
C 015023.030AWG10AWG20-AWG5AWG17-AWG8
MR5
C 020031.040AWG8AWG20-AWG5AWG17-AWG8
D00303.96AWG14AWG20-AWG5AWG17-AWG8
D00506.110AWG14AWG20-AWG5AWG17-AWG8
D0075910AWG14AWG20-AWG5AWG17-AWG8
D01001115AWG14AWG20-AWG5AWG17-AWG8
A01504860AWG4AWG13-AWG0AWG13-AWG2
A02006280AWG4AWG13-AWG0AWG13-AWG2
C 025038.050AWG4AWG13-AWG0AWG13-AWG2
C 030046.060AWG4AWG13-AWG0AWG13-AWG2
MR6
C 0400
D01501820AWG10AWG13-AWG0AWG13-AWG2
D02002225AWG10AWG13-AWG0AWG13-AWG2
D02502730AWG8AWG13-AWG0AWG13-AWG2
D03003440AWG8AWG13-AWG0AWG13-AWG2
*
I
L
[A]
**
61.080AWG4AWG13-AWG0AWG13-AWG2
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
*. For more information on type code, see page 7.
**. The 460V models require 90-degree wire to meet UL regulations
Table 8. Cable and fuse sizes for Honeywell Smart VFD HVAC (MR4 to MR6)
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must
be PVC-isolated; Max ambient temperature +86°F, max temperature of cable surface +158°F; Use only
cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel,
area and the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see standard Underwriters’
Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Laboratories UL508C.
NOTE HOWEVER that the requirements of both the cross-sectional
4.1.1.2Cable and fuse sizes, frames MR7 to MR9, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be
made according to local regulations, cable installation conditions and cable specification. Bigger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used
fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honeywell offers recommendations also for high speed J (UL & CSA), aR (UL recognized, IEC 60269-
4) and gS (IEC 60269-4) fuse ranges.
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.