8.2.1 Technical information on control connections............................................................... 71
Page 4
SAFETYHoneywell • 2
1.SAFETY
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGEROUS VOLTAGE!
= WARNING or CAUTION
Table 1. Warning signs
1.1Danger
The components of the power unit of the Smart VFD HVAC are live when the
drive is connected to mains potential. Coming into contact with this voltage is
extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when
the drive is connected to mains, even if the motor is not running.
After disconnecting the drive from the mains, wait until the indicators on the
keypad go out (if no keypad is attached see the indicators on the cover). Wait 5
more minutes before doing any work on the connections of the drive. Do not open
the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no
absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the drive is disconnected from mains.
Before connecting the drive to mains make sure that the front and cable covers
of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating
voltage to the drive. Therefore, do not touch the components of the drive before
the motor has completely stopped. Wait until the indicators on the keypad go out
(if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.
voltage is present.
Always ensure
1
Page 5
Honeywell • 3SAFETY
1.2Warnings
The Honeywell Smart VFD HVAC is meant for fixed installations only.
Do not perform any measurements when the drive is connected to the mains.
The touch current of the Honeywell Smart VFD HVAC exceeds 3.5mA AC.
According to standard EN61800-5-1, a reinforced protective ground connec-tion must be ensured. See chapter 1.3.
If the drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by Honeywell can be used.
At power-up, power brake, or fault reset the motor will start immediately if the
start signal is active, unless the pulse control for
Futhermore, the I/O functionalities (including start inputs) may change if parameters, applications or software are changed.Disconnect, therefore, the motor if an
unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the autoreset function is activated. See the Application Manual for more detailed information.
Start/Stop logic has been selected
.
Prior to measurements on the motor or the motor cable, disconnect the
motor cable from the drive.
Do not touch the components on the circuit boards. Static voltage discharge
may damage the components.
Check that the EMC level of the drive corresponds to the requirements of your
supply network. See chapter 5.2.
In a domestic environment, this product may cause radio interference in which
case supplementary mitigation measures may be required.
1.3Grounding and ground fault protection
CAUTION!
The Honeywell Smart VFD HVAC AC drive must always be grounded with an grounding conductor connected to the grounding terminal marked with .
The touch current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more of
the following conditions for the associated protective circuit shall be satisfied:
1.A fixed connection and
a)the protective earthing conductor has a cross-sectional area of at least 6 AWG
(10 mm
2
) Cu or 4 AWG (16 mm2) Al through its total run.
b)an automatic disconnection of the supply in case of loss of continuity of the protective
conductor. See chapter 4.
Page 6
SAFETYHoneywell • 4
c)provision of an additional terminal for a second protective earthing conductor of the
same cross-sectional area as the original protective earthing conductor.
OR
2.Connection with an industrial connector according to IEC 60309 and a minimum protec-tive earthing connector cross-section of 12 AWG (2.5 mm
power cable. Adequate strain relief shall be provided.
NOTE: Due to the high capacitive currents present in the drive, fault current protective switches
may not function properly.
Do not perform any voltage withstand tests on any part of the drive. There is a
certain procedure according to which the tests shall be performed. Ignoring this
procedure may result in damaged product.
2
) as part of a multi-conductor
1.4Running the motor
MOTOR RUN CHECK LIST
Before starting the motor, check that the motor is mounted properly and
ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the
machine connected to it.
Before reversing the motor make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
Make sure that the motor terminals are not connected to mains potential.
NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from https://en-US/Pages/de-
fault.aspx.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde applicables sur le site https://en-US/Pages/default.aspx
.
1
Page 7
Honeywell • 5RECEIPTOFDELIVERY
Product modified
Date:
Date:
Date:
9004.emf
2.RECEIPTOFDELIVERY
Check the correctness of delivery by comparing your order data to the drive information found
on the package label. If the delivery does not correspond to your order, contact the supplier
immediately. See chapter 2.3.
2.1‘Product modified’ sticker
In the small plastic bag included with delivery you will find a silver Product modified sticker.
The purpose of the sticker is to notify the service personnel about the modifications made in
the drive. Attach the sticker on the side of the drive to avoid losing it. Should the drive be later
modified mark the change on the sticker.
Figure 1. ‘Product modified’ sticker
2.2Unpacking and lifting the drive
The weights of the drives vary greatly according to the size. You may need to use a piece of
special lifting equipment to remove the drive from its package. Note the weights of each individual frame size in Table 2 below.
If you decide to use a piece of lifting equipment see picture below for recommendations to lift
the drive.
Page 8
RECEIPTOFDELIVERYHoneywell • 6
Max. 45°
9012.emf
NOTE: Place the lifting hooks symmetrically in at least two
holes.The lifting device must be able to carry weight of the
drive.
NOTE: The maximum allowed lifting angle is 45 degrees.
2.2.1Lifting frames MR8 and MR9
Figure 2. Lifting bigger frames
The Honeywell Smart VFD HVAC undergoes scrupulous tests and quality checks at the factory
before it is delivered to the customer. However, after unpacking the product, check that no
signs of transport damages are to be found on the product and that the delivery is complete.
Should the drive have been damaged during the shipping, please contact primarily the cargo
insurance company or the carrier.
2
Page 9
Honeywell • 7RECEIPTOFDELIVERY
11447_uk
A = Updated Control Board
No A = Legacy Control Board
T = Text KeyPad
G = Graphic KeyPad
Interface
1 = NEMA 1
2 = NEMA 12
3 = NEMA 3R
Enclosure Type
0 = Drive Only
1 = Disconnect Only
2 = Two Contactor Bypass
3 = Three Contactor Bypass
Contactors
0 = Drive Only or No Special Options
1 = Auto-Bypass
3 = Auto-Bypass and HOA
Options
0007 = .75 Horse Power
0010 = 1 Horse Power
0100 = 10 Horse Power
Nominal Horsepower
A= 208/230 Vac Drive Alone, 208 Vac Bypass
B = 230 Vac Bypass
C = 480 Vac
D = 600 Vac
Nominal Voltage
3 = Three Phase (3~in, 3~out)
Input Phase
HVFDSD = Honeywell SmartVFD HVAC
HVFDSB = Honeywell SmartVFD BYPASS
Product Family
HVFDSD 3 C 0100 G 1 0 0 A
2.3Type designation code
Honeywell type designation code is formed of a four-segment code. Each segment of the type
designation code uniquely corresponds to the product and options you have ordered. The code
is of the following format:
Page 10
RECEIPTOFDELIVERYHoneywell • 8
2.4Accessories
After having opened the transport package and lifted the converter out, check immediately that
these various accessories were included in the delivery:
•Rubber grommets (sizes vary according to frame)
•Power cable clamps for EMC grounding
•Screws for fixing the power cable clamps
•Control cable grounding clamps
•M4 screw for EMC level change in frame MR7
•Additional grounding screw (if necessary, see chapter 1.3)
•Ferrite holder
•Optional plastic shield to prevent unintended contact with live parts from front (MR8 and
MR9, IP00)
2
Page 11
Honeywell • 9MOUNTING
5.04
3.94
Ø.28
Ø.51
2.83
.55
3.94
2.44
7.48
NEMA 1
Ø.98
1.30
1.26
1.26
NE MA12
1.26
1.30
1.26
Ø.9 8
3.MOUNTING
The drive must be mounted in vertical position on the wall. Ensure that the mounting plane is
relatively even.
The drive shall be fixed with four screws (or bolts, depending on the unit size).
3.1Dimensions
3.1.1Wall mount, MR4-MR7
Figure 3. SmartVFD HVAC dimensions, MR4, wall mount
Page 12
MOUNTINGHoneywell • 10
*Optional mounting holes (for NX replacement)
8.43
5.67
4.53.5 7
Ø.2 8
Ø.5 5
Ø.28
2.83
3.94*
.574.53
Ø.2 8
3.94*
NEMA1
1.38 1 .46 1.46
Ø1.30Ø1.3 0Ø.98
NEMA12
1.36 1.48 1.48
1.38 1.46 1. 46
11449_uk
7.68
5.83
Ø.61
Ø.3 5
2.83
Ø.35
5.83
9.02
2.01 1.83 1.83
NEMA1
Ø1.57Ø1.30Ø1.57
1.421.42
2.40
2.01 1.83
NEMA12
Figure 4. SmartVFD HVAC dimensions, MR5, wall mount
Figure 5. SmartVFD HVAC dimensions, MR6, wall mount
3
Page 13
Honeywell • 11MOUNTING
10.20
Ø.79
9.33
7.48
Ø.35
Ø.63
Ø2.01
NEMA1
2.722.72
1.381.38
NEMA12
Ø.98
Ø1.97
2.722.72
1.77 1.77
11451 00
Ø.98
3 x 1.50
Ø2.36
2.466.46
11.42
Ø.87
Ø.43
Ø.35
13.50
8.54
Ø.35
Ø.35
26.46
27.32
8.50
37.64
9.25
11452 00
Figure 6. SmartVFD HVAC dimensions, MR7, wall mount
3.1.2Wall mount, MR8 and MR9
Figure 7. AC drive dimensions, MR8 NEMA1 and NEMA12
Page 14
MOUNTINGHoneywell • 12
Ø.35
18.90
15.75
Ø.35
14.17
11.50
Ø.87
14.37
13.98
14.17
Ø.35
Ø.35
Cabinet wall
(or similar)
IP21IP54
Cabinet wall
(or similar)
11453_00
Figure 8. AC drive dimensions, MR9 NEMA1 and NEMA12 (preliminary)
3.1.3Flange mount
The AC drive can also be recessed into the cabinet wall or similar surface. A special flange
mount option is available for this purpose. For an example of a flange-mounted drive, see Figure 9.
Figure 9. Example of flange mount (frame MR9)
11454_uk
3
Page 15
Honeywell • 13MOUNTING
A
C
F
11455 00
3.1.3.1Flange mount - Frames MR4 to MR6
Figure 10. presents the dimensions of the mounting opening and Figure 11. the depth dimensions of the drives with the flange mount option.
Drive outline
Opening outline
TOP
Figure 10. Flange mount cutout dimensions for MR4 to MR6
Table 4. Flange mount cutout dimensions for MR7 to MR9 [in]
Opening outline
Page 18
MOUNTINGHoneywell • 16
3.034.45
7.48
8.43
4. 49
3.94
4.174.84
9.02
11456_00
Figure 13. MR7 to MR9, flange mount, depth dimensions
3
Page 19
Honeywell • 17MOUNTING
C
A
9013.emf
D
B
A
B
3.2Cooling
The drive produces heat in operation and is cooled by air circulated by a fan. Enough free
space needs to be left around the drive to ensure sufficient air circulation and cooling. Different
acts of maintenance also require a certain amount of free space.
Make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of the converter.
A = clearance around the drive (see also B)
B = distance from one drive to another or distance to cabinet wall
C = free space above the drive
D = free space underneath the drive
Page 20
MOUNTINGHoneywell • 18
C+D
9014.emf
FRONTSIDE
Note that if several units are mounted above one another the
required free space equals C + D (see Figure 15.). Moreover,
the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit.
Figure 15. Installation space when drives are
Type
Cooling air required
[cfm]
MR426
MR544
MR6112
MR7109
MR8197
MR9366
Table 6. Required cooling air
mounted on top of each other
3
Page 21
Honeywell • 19POWERCABLING
9007.emf
PE conductor
and shield
PE conductors
Shield
4.POWERCABLING
The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals
marked with U, V and W. See Table 7 for the cable recommmendations for different EMC levels.
Use cables with heat resistance of at least +158°F. The cables and the fuses must be dimensioned according to the drive nominal OUTPUT current which you can find on the rating plate.
1st environment 2nd environment
EMC levels
Cable type
Mains cable111
Motor cable3*22
Control cable444
Table 7. Cable types required to meet standards
According to EN61800-3 (2004)
Category C2Category C3Level T
1 = Power cable intended for fixed installation and the specific mains voltage. Shielded
cable not required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and intended for the
specific mains voltage. (MCMK or similar recommended). See Figure 16.
3 = Symmetrical power cable equipped with compact low-impedance shield and intended
for the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recommended cable transfer impedance (1...30MHz) max. 100mohm/m]. See Figure 16.
*360º grounding of the shield with cable glands in motor end needed for EMC level C2.
4 =Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-
O or similar).
Figure 16.
NOTE: The EMC requirements are fulfilled at factory defaults of switching frequencies (all
frames).
NOTE: If safety switch is connected the EMC protection shall be continuous over the whole cable installation.
Page 22
POWERCABLINGHoneywell • 20
4.1UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with
a minimum heat-resistance of +140/167°F. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum.
4.1.1Cable dimensioning and selection
Table 8 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes.
Recommended fuse types are gG/gL.
These instructions apply only to cases with one motor and one cable connection from the drive
to the motor. In any other case, ask the factory for more information.
4.1.1.1Cable and fuse sizes, frames MR4 to MR6, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be
made according to local regulations, cable installation conditions and cable specification. Bigger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used
fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honeywell offers recommendations also for high speed J (UL & CSA), aR (UL recognized, IEC 60269-
A004012.520AWG14AWG24-AWG10 AWG17-AWG10
C 00153.46AWG14AWG24-AWG10 AWG17-AWG10
C 00204.86AWG14AWG24-AWG10 AWG17-AWG10
C 00305.610AWG14AWG24-AWG10 AWG17-AWG10
C 00408.010AWG14AWG24-AWG10 AWG17-AWG10
C 00509.615AWG14AWG24-AWG10 AWG17-AWG10
C 007512.020AWG14AWG24-AWG10 AWG17-AWG10
*
I
[A]
L
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
4
Page 23
Honeywell • 21POWERCABLING
FrameType
A00501825AWG10AWG20-AWG5AWG17-AWG8
A007524.230AWG10AWG20-AWG5AWG17-AWG8
A01003140AWG8AWG20-AWG5AWG17-AWG8
C 010016.025AWG10AWG20-AWG5AWG17-AWG8
C 015023.030AWG10AWG20-AWG5AWG17-AWG8
MR5
C 020031.040AWG8AWG20-AWG5AWG17-AWG8
D00303.96AWG14AWG20-AWG5AWG17-AWG8
D00506.110AWG14AWG20-AWG5AWG17-AWG8
D0075910AWG14AWG20-AWG5AWG17-AWG8
D01001115AWG14AWG20-AWG5AWG17-AWG8
A01504860AWG4AWG13-AWG0AWG13-AWG2
A02006280AWG4AWG13-AWG0AWG13-AWG2
C 025038.050AWG4AWG13-AWG0AWG13-AWG2
C 030046.060AWG4AWG13-AWG0AWG13-AWG2
MR6
C 0400
D01501820AWG10AWG13-AWG0AWG13-AWG2
D02002225AWG10AWG13-AWG0AWG13-AWG2
D02502730AWG8AWG13-AWG0AWG13-AWG2
D03003440AWG8AWG13-AWG0AWG13-AWG2
*
I
L
[A]
**
61.080AWG4AWG13-AWG0AWG13-AWG2
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
*. For more information on type code, see page 7.
**. The 460V models require 90-degree wire to meet UL regulations
Table 8. Cable and fuse sizes for Honeywell Smart VFD HVAC (MR4 to MR6)
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must
be PVC-isolated; Max ambient temperature +86°F, max temperature of cable surface +158°F; Use only
cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel,
area and the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see standard Underwriters’
Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Laboratories UL508C.
NOTE HOWEVER that the requirements of both the cross-sectional
4.1.1.2Cable and fuse sizes, frames MR7 to MR9, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be
made according to local regulations, cable installation conditions and cable specification. Bigger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used
fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honeywell offers recommendations also for high speed J (UL & CSA), aR (UL recognized, IEC 60269-
4) and gS (IEC 60269-4) fuse ranges.
Page 24
POWERCABLINGHoneywell • 22
FrameType
A025075100AWG2AWG9-AWG2/0AWG9-AWG2/0
A030088110AWG1AWG9-AWG2/0AWG9-AWG2/0
A0400105150AWG1/0AWG9-AWG2/0AWG9-AWG2/0
C 050072.0100AWG2AWG9-AWG2/0AWG9-AWG2/0
MR7
MR8
MR9
C 060087.0110AWG1AWG9-AWG2/0AWG9-AWG2/0
C 0750105.0150AWG1/0AWG9-AWG2/0AWG9-AWG2/0
D04004150AWG6AWG9-AWG2/0AWG9-AWG2/0
D05005260AWG6AWG9-AWG2/0AWG9-AWG2/0
D06006270AWG4AWG9-AWG2/0AWG9-AWG2/0
A0500143200AWG3/0AWG1-350kcmilAWG1-350kcmil
A0600170225250kcmilAWG1-350kcmilAWG1-350kcmil
A0750208250350kcmilAWG1-350kcmilAWG1-350kcmil
C 1000140.0200AWG3/0AWG1-350 kcmil AWG1-350 kcmil
C 1250170.0225250 kcmilAWG1-350 kcmil AWG1-350 kcmil
C 1500205.0250350 kcmilAWG1-350 kcmil AWG1-350 kcmil
D07508090AWG1/0AWG1-350kcmil AWG1-350kcmil
D1000100110AWG1/0AWG1-350kcmil AWG1-350kcmil
D1250125150AWG2/0AWG1-350kcmil AWG1-350kcmil
A10002613502x250kcmilAWG1-350kcmil AWG1-350kcmil
A12503104002x350kcmilAWG1-350kcmil AWG1-350kcmil
C 2000261.03502*250 kcmilAWG1-350 kcmil AWG1-350 kcmil
C 2500310.04002*350 kcmilAWG1-350 kcmil AWG1-350 kcmil
D1500144175AWG3/0AWG1-350kcmil AWG1-350kcmil
D2000208250300kcmilAWG1-350kcmilAWG1-350kcmil
I
L
[A]
Fuse
(class T)
[A]
Mains, motor
and ground
cable
Cu
Terminal cable size
Main terminalGround terminal
Table 9. Cable and fuse sizes for Honeywell Smart VFD HVAC (MR7 to MR9)
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must
be PVC-isolated; Max ambient temperature +86°F, max temperature of cable surface +158°F; Use only
cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel,
area and the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see standard Underwriters’
Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Laboratories UL508C.
NOTE HOWEVER that the requirements of both the cross-sectional
4.2Control cables
For information on control cables see chapter 6.
4
Page 25
Honeywell • 23POWERCABLING
9019.emf
D1
B1
C1
A1
D2
C2
E
Earth conductor
MAINSMOTOR
Earth conductor
4.3Cable installation
•Before starting, check that none of the components of the drive is live. Read carefully
the warnings in chapter 1.
•Place the motor cables sufficiently far from other cables
•Avoid placing the motor cables in long parallel lines with other cables.
•If the motor cables run in parallel with other cables note the minimum distances
between the motor cables and other cables given in table below.
Distance between
cables, [in]
Shielded
cable, [ft]
11.8≤ 164
39.4≤ 656
•The given distances also apply between the motor cables and signal cables of other
systems.
•The maximum lengths of motor cables are 328 ft. (MR4), 492 ft. (MR5 and MR6) and
656 ft. (MR7 to MR9).
•The motor cables should cross other cables at an angle of 90 degrees.
•If cable insulation checks are needed, see chapter Cable and motor insulation checks.
Start the cable installation according to the instructions below:
4.3.1Frames MR4 to MR7
1
Strip the motor and mains cables as advised below.
Figure 17. Stripping of cables
Page 26
POWERCABLINGHoneywell • 24
M4x55
FrameA1B1C1D1C2D2E
MR4.591.38.39.79.281.38
MR5.791.57.391.18.391.57
MR6.793.54.592.36.592.36
MR7.793.15.793.15.793.15
Table 10. Cables stripping lengths [in]
Leave
as short
as pos-
sible
2
Open the cover of the drive.
Figure 18.
4
Page 27
Honeywell • 25POWERCABLING
M4x8
9022.emf
11457_00
3
Remove the screws of the cable protection plate. Do not open the cover of the
power unit!
4
Figure 19.
Insert the cable grommets (included in the delivery) in the openings of the cable
entry plate (included) as shown in the picture.
Figure 20.
Page 28
POWERCABLINGHoneywell • 26
9217.emf
Insert the cables - supply cable, motor cable - in the openings of the cable entry
plate. Then cut the rubber grommets open to slide the cables through. Do not cut
the grommet openings wider than what is necessary for the cables you are
using.
5
IMPORTANT NOTE FOR NEMA12 INSTALLATION:
To meet the requirements of the enclosure class NEMA12, the connection
between the grommet and the cable must be tight. Therefore, lead the first bit of
the cable out of the grommet straight before letting it bend. If this is not possible,
the tightness
of the connection must be ensured with insulation
tape or a
cable
tie
.
Figure 21.
4
Page 29
Honeywell • 27POWERCABLING
M4x16
(2.2 Nm)
9024.emf
11458 00
6
Detach the cable clamps and the grounding clamps (Figure 22) and place the
cable entry plate with the cables in the groove on the drive frame (Figure 23).
Figure 22.
Figure 23.
Page 30
POWERCABLINGHoneywell • 28
1
2
3
3
11459_uk
Connect the stripped cables (see Figure 17 and Table 10) as shown in
Figure 24.
•Expose the shield of all three cables in order to make a 360-degree connection with the cable clamp (1).
7
•Connect the (phase) conductors of the supply and motor cables into their
respective terminals (2).
•Form the rest of the cable shield of all three cables into “pigtails” and make
a grounding connection with a clamp as shown in Figure 24 (3).
Make the pigtails just long enough to reach and be fixed to the terminal not longer.
Re-mount the cable protection plate (Figure 26) and the cover of the drive.
1
,
5
1
,
5
N
m
Figure 26. Re-mounting of cover components
N
m
Page 32
POWERCABLINGHoneywell • 30
9019.emf
D1
B1
C1
A1
D2
C2
E
Earth conductor
Earth conductor
4.3.2Frames MR8 and MR9
1
Strip the motor and mains cables as advised below.
Figure 27. Stripping of cables
FrameA1B1C1D1C2D2E
MR81.577.09.9811.81.9811.81
Leave as
short as
MR91.577.09.9811.81.9811.81
Table 12. Cables stripping lengths [in]
possible
4
Page 33
Honeywell • 31POWERCABLING
9046.emf
M4 x 10
1
2
11461_00
2
MR9 only: Remove the main cover of the AC drive.
3
Figure 28.
Remove the cable cover (1) and the cable fitting plate (2).
MR9
Figure 29.
Page 34
POWERCABLINGHoneywell • 32
4
MR9 only: Loosen the screws and remove the sealing plate.
MR9
11462_00
Figure 30.
5
Locate the terminals. OBSERVE the exceptional placement of motor cable terminals in MR8!
11463_00
Figure 31.
4
Page 35
Honeywell • 33POWERCABLING
11464_00
11465_00
Cut the rubber grommets open to slide the cables through. Should the grommets
6
fold in while inserting the cable, just draw the cable back a bit to straighten the
grommets up. Do not cut the grommet openings wider than what is necessary for
the cables you are using.
Figure 32.
7
Place the grommet with the cable so that the frame end plate fits in the groove
on the grommet, see Figure 33.
To meet the requirements of the enclosure class NEMA12, the connection
between the grommet and the cable must be tight. Therefore, lead the first bit of
the cable out of the grommet straight before letting it bend. If this is not possible,
the tightness
As an example,see Figure 21.
of the connection must be ensured with insulation
tape or a
cable
tie.
Figure 33.
Page 36
POWERCABLINGHoneywell • 34
11466_00
8
9
If you use thick cables insert the cable separators in between the terminals in
order to avoid contact between the cables.
Figure 34.
Connect the cables stripped as shown in Figure 27.
•Connect the (phase) conductors of the supply and motor cables into their
respective terminals (a).
•Form the rest of the cable shield of all cables into “pigtails” and make a
grounding connection as shown in Figure 35 (b) using the clamp from the
Accessories bag.
•Note also correct position of the ferrite holder (c) AFTER the cable stripping (in MR8 and EMC class C2 only).
•Note: If you use several cables on one connector observe the position of
cable lugs on top of each other. See Figure 36 below.
4
Page 37
Honeywell • 35POWERCABLING
L1 L2 L3
DC-
DC+
R+
R-
b
a
MR8
c
UWV
11467_00
Cable lug
Cable lug
Connector
Figure 35.
Figure 36. Placing two cable lugs on top of each other
Expose the shield of all three cables in order to make a 360-degree connection
with the cable clamp.
Figure 37.
11
Re-attach first the cable fitting plate and then the cable cover.
Figure 38.
4
Page 39
Honeywell • 37POWERCABLING
11468_00
12
MR9 only: Now re-mount the main cover (unless you want to make the control
connections first).
13
Figure 39.
Check the connection of the earth cable to the motor and the AC drive terminals
marked with .
NOTE: Two protective conductors are required according to standard EN618005-1. See chapter Grounding and ground fault protection.
Connect the protective conductor using a cable shoe and an M8 screw (included
in the
Accessories bag) on either of the screw connectors as advised in
Figure 40.
Page 40
POWERCABLINGHoneywell • 38
11469_00
Figure 40.
4.3.3Cable and motor insulation checks
1.Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the drive and from the motor.
Measure the insulation resistance of the motor cable between each phase conductor as
well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1MΩ at ambient temperature of 68°F.
2.Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 and L3 of the drive and from the mains.
Measure the insulation resistance of the mains cable between each phase conductor as
well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1MΩ at ambient temperature of 68°F.
3.Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the
motor connection box. Measure the insulation resistance of each motor winding. The
measurement voltage must equal at least the motor nominal voltage but not exceed 1000
V. The insulation resistance must be >1MΩ at ambient temperature of 68°F.
4.4Installation in corner-grounded network
Corner grounding is allowed for the drive types rating from 72 A to 310 A at 380...480 V supply
and from 75 A to 310 A at 208...240 V supply.
In these circumstances the EMC protection class must be changed to level C4 following the
instructions in Chapter 5.2 of this manual.
Corner grounding is not allowed for the drive types with rating from 3.4 A to 61 A at 380...480
V supply and 3.7 A to 62 A with 208...240 V supply.
4
Page 41
Honeywell • 39COMMISSIONING
5.COMMISSIONING
Before commissioning, note the following directions and warnings:
Internal components and circuit boards of the drive (except for the galvanically
isolated I/O terminals) are live when it is connected to mains potential. Coming
into contact with this voltage is extremely dangerous and may cause death
or severe injury.
The motor terminals U, V, W and the brake resistor terminals B-/B+ are live
when the drive is connected to mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the drive is disconnected from mains.
Do not make any connections to or from the drive when it is connected to the
mains.
After disconnecting the drive from the mains, wait until the fan stops and the
indicators on the keypad go out (if no keypad is attached see the indicators on
the cover). Wait 5 more minutes before doing any work on the connections of the
drive. Do not open the cover before this time has expired. After expiration of this
time, use a measuring equipment to absolutely ensure that no voltage is present.
Always ensure abscence of voltage before electrical work!
Before connecting the frequency converter to mains make sure that the front
and cable covers of the drive are closed.
Page 42
COMMISSIONINGHoneywell • 40
5.1Commissioning of the SmartVFD HVAC
1
2
3
4
5
6
7
Read carefully the safety instructions in Chapter 1 and above and follow them.
After the installation, make sure that:
•both the drive and the motor are grounded.
•the mains and motor cables comply with the requirements given in chapter
4.1.1.
•the control cables are located as far as possible from the power cables,
see chapter 4.3.
•the shields of the shielded cables are connected to protective ground
marked with .
•check the tightening torques of all terminals
•the wires do not touch the electrical components of the drive.
•the common inputs of digital input groups are connected to +24V or
ground of the I/O terminal or the external supply.
Check the quality and quantity of cooling air (chapter 3.2 and Table 6).
Check the inside of the drive for condensation.
Check that all Start/Stop switches connected to the I/O terminals are in
Stop-position.
Before connecting the AC drive to mains:
•check mounting and condition of all fuses and other protective devices
Run the Startup Wizard (see the Application Manual).
5
Page 43
Honeywell • 41COMMISSIONING
MR4
9064.emf
MR5
MR6
5.2Changing EMC protection class
I
f your supply network is an IT (impedance-grounded) system but your AC drive is EMC-protected according to class C2 you need to modify the EMC protection of the AC drive to EMC-level T. This is done by
removing the built-in EMC jumpers with a simple procedure described b
Warning! Do not perform any modifications on the drive when it is connected to mains.
5.2.1Frames MR4 to MR6
elow:
1
connecting the built-in RFI-filters to ground. See Figure 41. and Figure 42.
NOTE: The locations of the EMC-jumpers have changed in frames MR5 and MR6. Figure 41.
shows the old locations and Figure 42. the new locations in frames MR5 and MR6.
Remove the main cover of the drive (see pages 24 and 31) and locate the jumpers
Figure 41. Current locations of the EMC-jumpers in frame MR4, old locations in frames MR5
and MR6
Page 44
COMMISSIONINGHoneywell • 42
9099.emf
MR 5
MR 6
Figure 42.Current locations of the EMC-jumpers in frames MR5 and MR6
2
Figure 43. Removing the jumper, MR5 as example
Disconnect the RFI-filters from ground by removing the EMC-jumpers using longnose pliers or similar. See Figure 43.
5
Page 45
Honeywell • 43COMMISSIONING
9066.emf
9065.emf
5.2.2Frames MR7 and MR8
Follow the procedure described above to modify the EMC protection of the drive of frames MR7
and MR8 to EMC-level C4.
1
Figure 44.
2
Remove the main cover of the drive and locate the jumper. MR8 only: Push down
the grounding arm. See Figure 44.
MR7 and MR8: Locate the EMC box under the cover. Remove the screws of the
box cover to expose the EMC-jumper. Detach the jumper and re-fix the box cover.
Figure 45.
Page 46
COMMISSIONINGHoneywell • 44
9062.emf
3
Figure 46. MR7: Detaching the DC grounding busbar from frame
MR7 only: locate the DC grounding busbar between connectors R- and U and
detach the busbar from the frame by undoing the M4 screw.
5
Page 47
Honeywell • 45COMMISSIONING
11470_00
5.2.3Frame MR9
Follow the procedure described above to modify the EMC protection of the AC drive of frame
MR9 to EMC-level T.
Find the Molex connector in the accessories bag. Remove the main cover of the
1
Molex connector
AC drive and locate the place for the connector next to the fan. Push the Molex
connector in its place. See Figure 47.
2
Figure 47.
Further remove the extension box cover (1), the touch shield (2) the I/O plate (4)
with I/O grommet plate (3). Locate the EMC jumper on the EMC board (see magnification below) and remove it.
Figure 48.
11471_00
Page 48
COMMISSIONINGHoneywell • 46
CAUTION! Before connecting the AC drive to mains make sure that the EMC protection class settings of the drive are appropriately made.
NOTE! After having performed the change write ‘EMC level modified’ on the stick-
er included with the drive delivery (see below) and note the date. Unless already
done, attach the sticker close to the name plate of the drive.
5
Page 49
Honeywell • 47CONTROLUNIT
STO JMP
L
I
M
K
H
G
F
J
E
D
A
B
C
6.CONTROLUNIT
The control unit of the AC drive contains the standard boards and the option boards. The option
boards are connected to the slots of the control board (see 6.3 Installation of Option Boards).
Figure 49.The components of the control unit
A. The control terminals for the standard I/O
B. The Ethernet connection
connections
C. The relay board terminals for 3 relay out-
D. The option boards
puts or 2 relay outputs and a thermistor
E. A DIP switch for the RS485 bus termina-
tion
G. A DIP switch for the isolation of the digital
inputs from ground
I.A DIP switch for the signal selection of
Analogue Input 1
K. A fan (only in IP54 of MR4 and of MR5)L.The battery for the RTC
F.A DIP switch for the signal selection of
Analogue Output
H. A DIP switch for the signal selection of
Analogue Input 2
J.The status indicator of the Ethernet con-
nection
M. The location and the default position of
the Safe Torque Off (STO) jumper
(feature not available, do not touch)
Page 50
CONTROLUNITHoneywell • 48
When you receive the AC drive, the control unit contains the standard control interface. If you
included special options in your order, the AC drive will be as in your order. On the next pages,
you will find information on the terminals and general wiring examples.
It is possible to use the drive with an external power source with these properties: +24 VDC
±10%, minimum 1000 mA. Connect the external power source to terminal 30. This voltage is
sufficient to keep the control unit on and for you to set the parameters. The measurements of
the main circuit (for example, the DC link voltage, and the unit temperature) are not available
when the drive is not connected to mains.
The status LED of the drive shows the status of the drive. The status LED is located in the control panel, below the keypad, and it can show 5 different statuses.
Table 14. The statuses of the status LED of the drive
6.1Control Unit Cabling
The standard I/O board has 22 fixed control terminals and 8 relay board terminals. You can see
the standard connections of the control unit and the descriptions of signals in Fig. 39.
6.1.1Selection of the Control Cables
The control cables must be a minimum of 20 AWG (0.5 mm
more on the cable types in Table 7 on page 19. The terminal wires must be a maximum of
12 AWG (2.5 mm
The terminalThe terminal screw
All the terminals of the I/O
board and the relay board
6.1.2Control Terminals and Dip Switches
Here you see the basic description of the terminals of the standard I/O board and the relay
board. For more information, see 8.2.1 Technical information on control connections.
2
) for the relay board terminals and other terminals.
M30.54.5
Table 15. Control cable tightening torques
2
) screened multicore cables. See
Tightening torque
Nmlb-in.
Some terminals are assigned for signals that have optional functions that you can use with the
DIP switches. See more in 6.1.2.1 Selection of terminal functions with DIP switches.
Figure 50.The signals of the control terminals on the standard I/O board, and a connection
example. If you include the optional code +SBF4 in your order, the relay output 3 is re-
placed with a thermistor input.
Page 52
CONTROLUNITHoneywell • 50
RO1 NC
RO1 CM
RO1 NO
RO2 NC
RO2 CM
RO2 NO
RO3 CM
RO3 NO
21
22
23
24
25
26
32
33
RUN
RUN
FAULT
READY
Relay output 1
Relay output 2
Relay output 3
From Standard I/O board
TerminalSignal
Default
Relay board 1
From term.
#6 or 12
From term.
#13
Figure 51.The standard relay board
6.1.2.1Selection of terminal functions with DIP switches
You can make 2 selections with the DIP switches for specified terminals. The switches have 2
positions: up and down. You can see the location of the DIP switches and the possible selections in Figure 52.
6
Page 53
Honeywell • 51CONTROLUNIT
AB
A
B
C
D
E
AI2
U
I
AI1
U
I
RS-485
OFF
ON
AO1
U
I
Figure 52.The selections of the DIP switches
A. The voltage signal (U), 0-10 V inputB. The current signal (I), 0-20 mA input
C. OFFD. ON
E. The RS-485 bus termination
The DIP switchThe default position
AI1U
AI2I
AO1I
RS485 bus terminationOFF
Table 16. The default positions of the DIP switches
Page 54
CONTROLUNITHoneywell • 52
C
D
B
A
6.1.2.2Isolation of digital inputs from ground
It is possible to isolate from ground the digital inputs (terminals 8-10 and 14-16) on the standard
I/O board. To do this, change the position of a DIP switch on the control board.
A
B
C
Figure 53.Change the position of this switch to isolate the digital inputs from ground
A. The digital inputsB. Floating
C. Connected to GND (default)
6.2Fieldbus Connection
You can connect the drive to fieldbus with an RS485 or an Ethernet cable. If you use an RS485
cable, connect it to terminal A and B of the standard I/O board. If you use an Ethernet cable,
connect it to the Ethernet terminal below the cover of the drive.
A. RS485 terminal A = Data -B. RS485 terminal B = Data +
C. The Ethernet terminalD. The control terminals
Figure 54.The Ethernet and RS485 connections
6
Page 55
Honeywell • 53CONTROLUNIT
IP54
6.2.1Using Fieldbus Through an Ethernet Cable
ItemDescription
The plug typeA shielded RJ45 plug, maximum length 40 mm (1.57 in)
The cable typeCAT5e STP
The cable lengthMaximum 100 m (328 ft)
Table 17. Ethernet cable data
6.2.1.1ETHERNET CABLING
1
2
Connect the Ethernet cable to its terminal.
In IP21, cut free the opening on the cover
of the AC drive for the Ethernet cable. In
IP54, cut a hole in a grommet and move
the cable through it.
a.If the grommet folds in when you
put the cable, pull the cable back
to make the grommet straight.
b.The hole in the grommet must
not be wider than your cable.
c.Pull the first bit of the cable out
of the grommet so that it stays
straight. If this is not possible,
make the connection tight with
some insulation tape or a cable
tie.
IP21
Page 56
CONTROLUNITHoneywell • 54
A
A. The Ethernet cable in IP21
A
A. The Ethernet cable in IP54
Put the cover of the drive back. Keep the
distance between the Ethernet cable and
the motor cable at a minimum of 30 cm
(11.81 in).
See more in the Installation Manual of the
fieldbus that you have.
3
6
Page 57
Honeywell • 55CONTROLUNIT
10
5
15 mm
6.2.2Using Fieldbus Through an RS485 Cable
ItemDescription
The plug type
The cable typeSTP (shielded twisted pair), Belden 9841 or almost the same
The cable lengthSo that it agrees with the fieldbus. See the fieldbus manual.
RS485 CABLING
Remove approximately 15 mm (0.59 in)
of the grey shield of the RS485 cable. Do
this for the 2 fieldbus cables.
a.Strip the cables for approxi-
mately 5 mm (0.20 in) to put
them in the terminals. Do not
keep more than 10 mm (0.39 in)
of the cable outside the termi-
1
nals.
b.Strip the cable at such a dis-
tance from the terminal that you
can attach it to the frame with
the grounding clamp for control
cable. Strip the cable at a maximum length of 15 mm (0.59 in).
Do not remove the aluminium
shield of the cable.
2.5 mm
2
Table 18. RS485 cable data
Page 58
CONTROLUNITHoneywell • 56
Connect the cable to the standard I/O
board of the drive, in terminals A and B.
•A = negative
•B = positive
2
3
Attach the shield of the cable to the
frame of the drive with a grounding
clamp for control cable to make a
grounding connection.
6
Page 59
Honeywell • 57CONTROLUNIT
If the drive is the last device on the fieldbus line, set the bus termination.
a.Find the DIP switches on the left
side of the control unit of the
drive.
b.Set the DIP switch of the RS485
bus termination to the ON position.
c.Biasing is built in the bus termi-
nation resistor. The termination
resistance is 220 ȍ.
4
5
In IP21, unless you have cut the openings
for other cables, cut an opening on the
cover of the drive for the RS485 cable.
Page 60
CONTROLUNITHoneywell • 58
A
A. The fieldbus cables
Put the cover of the drive back. Pull the
RS485 cables to the side.
a.Keep the distance of the Ether-
net, I/O and Fieldbus cables
from the motor cable at a minimum of 30 cm (11.81 in).
b.Move the fieldbus cables away
from the motor cable.
6
7
Set the bus termination for the first and the last device of the fieldbus line. We recommend that the first device on the fieldbus is the master device.
D
A
D
E
A. The termination is activatedB. The termination is deactivated
C. The termination is activated with a
DIP switch
E. The fieldbus
B
D. The bus termination. The resistance
is 220 ȍ.
C
6
Page 61
Honeywell • 59CONTROLUNIT
M4x55
Note: If you do power-down to the last device, there is no bus termination.
6.3Installation of Option Boards
CAUTION!
Do not install, remove, or replace option boards on the drive when the power is on. Doing this
can cause damage to the boards.
Install the option boards into the option board slots of the drive. Refer to Table 19.
Type of the option
board
HVFDSDOPT6DI
HVFDSDOPT2RO1TThe Thermistor relay boardC, D, E
HVFDSDOPT1AI2AOThe I/O expander boardC, D, E
HVFDSDOPT3ROThe Relay boardC, D, E
HVFDSDOPT1RO5DIThe I/O expander boardC, D, E
HVFDOPTTMP
32006630-001The LonWorks fieldbus boardD, E
Table 19. The option boards and their correct option board slots
THE INSTALLATION PROCEDURE
Open the cover of the AC drive.
WARNING
Do not touch the control terminals.
They can have a dangerous voltage also when the drive is discon-
1
nected from mains.
Description of the option boardThe correct slot or slots
The I/O expander board
The Temperature measurement
board
C, D, E
C, D, E
Page 62
CONTROLUNITHoneywell • 60
A. The slot coding
If you have an HVFDSDOPT or an
32006630-001 option board, make sure
that the label on it says "dv" (dual voltage). This shows that the option board is
2
compatible with the drive.
Note: It is not possible to install option
boards that are not compatible with the
drive.
To get access to the option board slots,
open the cover of the control unit.
dv
OPT
A
3
6
Page 63
Honeywell • 61CONTROLUNIT
A. The slot coding
B. The option board slots
Install the option board into the correct
slot: C, D or E. See Table 19.
a.The option board has a slot cod-
ing, because of which it is not
possible to install the option
board in an incorrect slot.
A
4
B
5
6.4Installation of a Battery for the Real Time Clock (RTC)
To use the Real Time Clock (RTC), you must install a battery in the drive.
1
2
The battery will last approximately 10 years. See more about the functions of the RTC in the
Application Manual.
Close the cover of the control unit. Put the cover of the AC drive back.
Use a ½ AA battery with 3.6 V and a capacity of 1000-1200 mAh. You can use,
for example, a Panasonic BR-1/2 AA or a Vitzrocell SB-AA02.
Install the battery on the left side of the control panel. See Figure 49 on page 47.
Page 64
CONTROLUNITHoneywell • 62
6.5Galvanic Isolation Barriers
The control connections are isolated from mains. The GND terminals are permanently connected to I/O ground.
The digital inputs on the standard I/O board can be galvanically isolated from the I/O ground.
To isolate the digital inputs, use the DIP switch that has the positions FLOAT and GND.
A
10Vref
GND
+24V
GND
AI1+
AI1-
AI2+
AI2DI1...
DI6
CM
AO1+
AO1+24Vin
RS485
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
TI1+
TI1-
L1
L2
L3
DC-DC+/R+R-
Table 20. The galvanic isolation barriers
A. The control unitB. The power unit
B
U
V
W
6
Page 65
Honeywell • 63MAINTENANCE
7.MAINTENANCE
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is recommended to ensure a trouble-free operation and a long lifetime of the drive. We recommend
to follow the table below for maintenance intervals.
NOTE: Because of capacitor type (thin film capacitors), reforming of capacitors is not necessary.
Maintenance intervalMaintenance action
Regularly and according to general maintenance interval
6–24 months (depending on
environment)
24 monthsClean heatsink and cooling tunnel
3–6 yearsChange internal IP54 fan
6–10 yearsChange main fan
• Check tightening torques of terminals
• Check input and output terminals and control I/O
terminals.
• Check operation of cooling fan
• Check for corrosion on terminals, busbars and other
surfaces
Table 1. Maintenance
Page 66
Honeywell • 64PRODUCTDATA
8.PRODUCTDATA
8.1Power ratings
8.1.1Mains voltage 208-240 V
Mains voltage 208-240V, 50-60 Hz, 3~
LoadabilityMotor shaft power
*
[A]
Low
L
10% overload
current
[A]
Converter
type
Rated continuous
current I
A 00073.74.10.550.75
A 00104.85.30.751.0
A 00156.67.31.11.5
A 00208.08.81.52.0
MR4
A 003011.012.12.23.0
A 004012.513.83.04.0
A 005018.019.84.05.0
A 007524.226.45.57.5
MR5
A 0100
**
31.034.17.510.0
A 015048.052.811.015.0
230 supply208-240V supply
10% overload
40°C
[kW]
10% overload
40°C
[hp]
A 0200**62.068.215.020.0
MR6
A 025075.082.518.525.0
A 030088.096.822.030.0
MR7
A 0400105.0115.530.040.0
A 0500143.0154.037.050.0
A 0600170.0187.045.060.0
MR8
A 0750208.0225.555.075.0
A 1000261.0287.175.0100.0
A 1250310.0341.090.0125.0
MR9
*
See chapter 8.1.4.
**
Given low loadabilities valid for 230V drives at a switching frequency of
4kHz
Table 20. Power ratings, supply voltage 208-240V.
NOTE: The rated currents in given ambient temperatures (in Table 3) are
achieved only when the switching frequency is equal to or less than the factory default.
Page 67
PRODUCTDATAHoneywell • 65
8.1.2Mains voltage 380-480V
Mains voltage 380-480V, 50-60 Hz, 3~
LoadabilityMotor shaft power
*
[A]
Low
L
10% overload
current
[A]
Converter
type
Rated continuous
current I
C 00153.43.71.11.5
C 00204.85.31.52.0
C 00305.66.22.23.0
C 00408.08.83.04.0
MR4
C 00509.610.64.05.0
C 0075
**
12.013.25.57.5
C 010016.017.67.510
C 015023.025.311.015.0
MR5
C 0200**31.034.115.020.0
C 025038.041.818.525.0
C 030046.050.622.030.0
MR6
C 0400**61.067.130.040.0
C 050072.079.237.050.0
C 060087.095.745.060.0
MR7
C 0750105.0115.555.075.0
C 1000140.0154.075100
C 1250170.0187.090125
MR8
C 1500205.0225.5110150
C 2000261.0287.1132200
400V supply480V supply
10% overload
104°F
[kW]
10% overload
104°F
[HP]
C 2500310.0341.0160250
MR9
*
See chapter 8.1.4
**
Given low loadabilities valid for 480V drives at a switching frequency of
4kHz
Table 1. Power ratings, supply voltage 380-480V.
NOTE: The rated currents in given ambient temperatures (in Table 3) are achieved only when
the switching frequency is equal to or less than the factory default.
8
Page 68
Honeywell • 66PRODUCTDATA
8.1.3Mains voltage 525-600V
Mains voltage 525-600V, 50-60 Hz,
3~
Loadability
Converter
type
Rated continuous
current I
[A]
Low
L
*
10% overload
current
[A]
D00303.94.33.0
D00506.16.75.0
D00759.09.97.5
MR5
D010011.012.110.0
D015018.019.815.0
D020022.024.220.0
D025027.029.725.0
MR6
D030034.037.430.0
D040041.045.340.0
D050052.057.250.0
MR7
D060062.068.260.0
D075088.0154.075.0
D1000110.0187.0100.0
MR8
D1250137.5225.5125.0
D1500144.0158.4150.0
Motor shaft
power
600V supply
10% overload
104°F
[HP]
D2000208.0228.8200.0
MR9
*
See chapter 8.1.4
Table 2. Power ratings, supply voltage 525-600V.
Page 69
PRODUCTDATAHoneywell • 67
I
L
I
L* 11 0%
1 min9 min
I
L*11 0%
Current
Time
8.1.4Definitions of overloadability
Low overload
Example:If the duty cycle requires 110% rated current I
=Following continuous operation at rated output current IL, the converter is fed with
110% * I
9 min must be at rated current or less.
for 1 min, followed by a period of IL.
L
Figure 1. Low overload
for 1 min in every 10 min, the remaining
L
11481_uk
8
Page 70
Honeywell • 68PRODUCTDATA
8.2SmartVFD HVAC - technical data
Mains connection
Motor connection
Control
characteristics
Input voltage U
in
208...240V; 380…480V; 525…600V;
-10%…+10%
Input frequency47…66 Hz
Connection to mainsOnce per minute or less
Starting delay4 s (MR4 to MR6); 6 s (MR7 to MR9)
Output voltage
Continuous output
current
Starting current
0-U
in
IL:Ambient temperature max. +104°F,
overload 1.1 x I
(1 min./10 min.)
L
IS for 2 s every 20 s
Output frequency0…320 Hz (standard)
Frequency resolution0.01 Hz
200-500 V
• MR4-MR6:
• 1.5-10 kHz
• Default: 6 kHz (except for A 0040,
A 0100, A 0200, C 0075, C 0200 and
C 0400: 4 kHz)
• MR7-MR9:
•1.5-6 kHz
• Default: MR7: 4 kHz, MR8: 3 kHz, MR9:
Switching frequency
2kHz
(see parameter
M3.1.2.1)
600 V
• MR5-MR9:
•1.5-6 kHz
• Default: 2 kHz
• For a product that is configured for a C4
installation on IT network the maximum
switching frequency is limited to default
2kHz.
Automatic switching frequency derating in
case of overload.
Frequency reference
Analogue input
Panel reference
IL : -10°C (no frost)…+40°C,
Ambient operating
temperature
14 (no frost) ... 104 F
Up to 50 °C with derating (1.5%/1°C)
Ambient conditions
Ambient conditions
(cont.)
Storage temperature
Relative humidity
Air quality:
chemical vapours
mechanical particles
Altitude
Vibration
EN61800-5-1/
EN60068-2-6
Shock
EN61800-5-1
EN60068-2-27
-40°C ... +70°C
-40°F…+158°F
0 to 95% RH, non-condensing, non-corro-
sive
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to
1,000 m / 3280 ft
1-% derating for each 100m/328ft above
1,000m/3280ft
Max. altitudes:
208...240V: 4,500m/14763 ft
tems)
380...480V:
tems)
525...690 V: 2,000m/6562 ft (TN and IT
systems, no corner grounding)
Voltage for I/O signals:
Up to 2,000m/6561ft : Allowed up to 240V
2,000m...4,500m / 6561...14763ft: Allowed
up to 120V
5…150 Hz
Displacement amplitude 1 mm (peak) at
5…15.8 Hz (MR4…MR9)
Max acceleration amplitude 1 G at
15.8…150 Hz (MR4…MR9)
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in
package)
4,500m/14763 ft (TN and IT sys-
(TN and IT sys-
Enclosure class
IP21/NEMA 1 standard in entire kW/HP range
IP54/NEMA12 option
Note! Keypad required for IP54/NEMA12
8
Page 72
Honeywell • 70PRODUCTDATA
EMC (at default
settings)
Emissions
Safety
Immunity
Emissions
Average noise level
(cooling fan) sound
power level in dB(A)
Fulfils EN61800-3 (2004), first and second
environment
Depend on EMC level.
+EMC2: EN61800-3 (2004), Category C2
Honeywell Smart VFD HVAC will be deliv-
ered with class C2 EMC filtering, if not oth-
erwise specified.
Honeywell Smart VFD HVAC can be modi-
fied for IT-networks. See chapter 5.2.
• 200-500 V: EN 61800-3 (2004), category
C2.
• 600 V: EN 61800-3 (2004), category C3.
• All: The product is configurable to category C4 for installation on IT networks.
The drive can be modified for IT type
mains. See chapter 7.6 Installation in an
IT system. The IP00 / UL Open Type
drive has by default category C4.
MR4: 65MR7: 77
MR5: 70MR8: 86
MR6: 77MR9: 87
EN 61800-5-1 (2007), CE, cUL; (see unit
nameplate for more detailed approvals)
Control connectionsSee chapter 8.2.1.
Protections
Overvoltage trip limit
Undervoltage trip limit
Ground fault protection
Mains supervisionYe s
Motor phase supervision
Yes
Yes
In case of ground fault in motor or motor
cable, only the drive is protected
Trips if any of the output phases is missing
Overcurrent protection Yes
Unit overtemperature
protection
Motor overload protection
Yes
Yes
Motor stall protectionYes
Protections (cont.)
Motor underload
protection
Yes
Short-circuit protection
of +24V and +10V
Yes
reference voltages
Table 3. Smart VFD HVAC technical data
Page 73
PRODUCTDATAHoneywell • 71
8.2.1Technical information on control connections
Basic I/O board
TerminalSignalTechnical information
Reference output+10V, +3%; Maximum current 10 mA
1
Analogue input channel 1
0- +10V (Ri = 200 kΩ)
4-20 mA (Ri =250 Ω)
Resolution 0.1 %, accuracy ±1 %
Selection V/mA with dip-switches (see page 50)
Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
Analogue input channel 1
Defauit:4-20 mA (Ri =250 Ω)
0-10 V (Ri=200kΩ)
Resolution 0.1 %, accuracy ±1 %
Selection V/mA with dip-switches (see page 50)
Differential input if not connected to ground;
Allows 20V differential mode voltage to GND
+24VDC, ±10%, max volt. ripple < 100mVrms; max. 250mA
Dimensioning: max. 1000mA/control box.
Short-circuit protected
Ground for reference and controls (connected internally to
frame ground through 1MΩ)
Positive or negative logic
Ri = min. 5kΩ
18…30V = "1"
Digital inputs can be disconnected from ground, see chapter
6.1.2.2.
+24VDC, ±10%, max volt. ripple < 100mVrms; max. 250mA
circuitry must be powered with a separate isolation transformer to limit
short circuit current and overvoltage spikes. This is to prevent welding on
the relay contacts. Refer to standard EN 60204-1, section 7.2.9