Honeywell SmartVFD HVAC Installation Instructions

Page 1
Honeywell
Installation manual
SmartVFD HVAC
Variable Frequency Drives
for Variable Torque Applications
%\XVLQJWKLV+RQH\ZHOOOLWHUDWXUH\RXDJUHHWKDW+RQH\ZHOOZLOOKDYHQROLDELOLW\ IRUDQ\GDPDJHVDULVLQJRXWRI\RXUXVHRUPRGLILFDWLRQWRWKHOLWHUDWXUH<RXZLOO GHIHQGDQGLQGHPQLI\+RQH\ZHOOLWVDIILOLDWHVDQGVXEVLGLDULHVIURPDQGDJDLQVW DQ\OLDELOLW\FRVWRUGDPDJHVLQFOXGLQJDWWRUQH\V¶IHHVDULVLQJRXWRIRUUHVXOWLQJ IURPDQ\PRGLILFDWLRQWRWKHOLWHUDWXUHE\\RX
38-00007-03
Page 2
Honeywell • 0
INDEX
Document: DPD00323D
Version release date: 18.1.18
1. Safety ..................................................................................................................2
1.1 Danger ............................................................................................................................ 2
1.2 Warnings......................................................................................................................... 3
1.3 Grounding and ground fault protection ........................................................................... 3
1.4 Running the motor .......................................................................................................... 4
2. Receipt of delivery.............................................................................................5
2.1 ‘Product modified’ sticker ................................................................................................ 5
2.2 Unpacking and lifting the drive........................................................................................ 5
2.2.1 Lifting frames MR8 and MR9 .......................................................................................... 6
2.3 Type designation code.................................................................................................... 7
2.4 Accessories..................................................................................................................... 8
3. Mounting.............................................................................................................9
3.1 Dimensions ..................................................................................................................... 9
3.1.1 Wall mount, MR4-MR7.................................................................................................... 9
3.1.2 Wall mount, MR8 and MR9........................................................................................... 11
3.1.3 Flange mount................................................................................................................ 12
3.2 Cooling.......................................................................................................................... 17
4. Power cabling ..................................................................................................19
4.1 UL standards on cabling ............................................................................................... 20
4.1.1 Cable dimensioning and selection ................................................................................ 20
4.2 Control cables ...............................................................................................................22
4.3 Cable installation...........................................................................................................23
4.3.1 Frames MR4 to MR7..................................................................................................... 23
4.3.2 Frames MR8 and MR9.................................................................................................. 30
4.3.3 Cable and motor insulation checks............................................................................... 38
4.4 Installation in corner-grounded network........................................................................ 38
5. Commissioning................................................................................................39
5.1 Commissioning of the SmartVFD HVAC....................................................................... 40
5.2 Changing EMC protection class.................................................................................... 41
5.2.1 Frames MR4 to MR6..................................................................................................... 41
5.2.2 Frames MR7 and MR8.................................................................................................. 43
5.2.3 Frame MR9 ................................................................................................................... 45
6. Control unit ......................................................................................................47
6.1 Control Unit Cabling...................................................................................................... 48
6.1.1 Selection of the Control Cables .................................................................................... 48
6.1.2 Control Terminals and Dip Switches............................................................................. 48
6.2 Fieldbus Connection ..................................................................................................... 52
6.2.1 Using Fieldbus Through an Ethernet Cable.................................................................. 53
6.2.2 Using Fieldbus Through an RS485 Cable .................................................................... 55
6.3 Installation of Option Boards......................................................................................... 59
6.4 Installation of a Battery for the Real Time Clock (RTC)................................................ 61
6.5 Galvanic Isolation Barriers............................................................................................ 62
7. Maintenance .....................................................................................................63
8. Product data.....................................................................................................64
8.1 Power ratings................................................................................................................64
Page 3
Honeywell • 1
8.1.1 Mains voltage 208-240 V .............................................................................................. 64
8.1.2 Mains voltage 380-480V ............................................................................................... 65
8.1.3 Mains voltage 525-600V ............................................................................................... 66
8.1.4 Definitions of overloadability ......................................................................................... 67
8.2 SmartVFD HVAC - technical data................................................................................. 68
8.2.1 Technical information on control connections............................................................... 71
Page 4
SAFETY Honeywell • 2
1. SAFETY
This manual contains clearly marked cautions and warnings which are intended for your per­sonal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGEROUS VOLTAGE!
= WARNING or CAUTION
Table 1. Warning signs
1.1 Danger
The components of the power unit of the Smart VFD HVAC are live when the drive is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when the drive is connected to mains, even if the motor is not running.
After disconnecting the drive from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of the drive. Do not open the cover before this time has expired. After expiration of this time, use a measur­ing equipment to absolutely ensure that no
absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when the drive is disconnected from mains.
Before connecting the drive to mains make sure that the front and cable covers of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the drive before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 min­utes before starting any work on the drive.
voltage is present.
Always ensure
1
Page 5
Honeywell • 3 SAFETY
1.2 Warnings
The Honeywell Smart VFD HVAC is meant for fixed installations only.
Do not perform any measurements when the drive is connected to the mains.
The touch current of the Honeywell Smart VFD HVAC exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connec- tion must be ensured. See chapter 1.3.
If the drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN 60204-1).
Only spare parts delivered by Honeywell can be used.
At power-up, power brake, or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Futhermore, the I/O functionalities (including start inputs) may change if parame­ters, applications or software are changed.Disconnect, therefore, the motor if an unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the autoreset func­tion is activated. See the Application Manual for more detailed information.
Start/Stop logic has been selected
.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the drive.
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
Check that the EMC level of the drive corresponds to the requirements of your supply network. See chapter 5.2.
In a domestic environment, this product may cause radio interference in which case supplementary mitigation measures may be required.
1.3 Grounding and ground fault protection
CAUTION!
The Honeywell Smart VFD HVAC AC drive must always be grounded with an grounding con­ductor connected to the grounding terminal marked with .
The touch current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
1. A fixed connection and a) the protective earthing conductor has a cross-sectional area of at least 6 AWG
(10 mm
2
) Cu or 4 AWG (16 mm2) Al through its total run.
b) an automatic disconnection of the supply in case of loss of continuity of the protective
conductor. See chapter 4.
Page 6
SAFETY Honeywell • 4
c) provision of an additional terminal for a second protective earthing conductor of the
same cross-sectional area as the original protective earthing conductor.
OR
2. Connection with an industrial connector according to IEC 60309 and a minimum protec- tive earthing connector cross-section of 12 AWG (2.5 mm power cable. Adequate strain relief shall be provided.
NOTE: Due to the high capacitive currents present in the drive, fault current protective switches may not function properly.
Do not perform any voltage withstand tests on any part of the drive. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
2
) as part of a multi-conductor
1.4 Running the motor
MOTOR RUN CHECK LIST
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
Make sure that the motor terminals are not connected to mains potential.
NOTE! You can download the English and French product manuals with applicable safety, warning and caution information from https:// en-US/Pages/de-
fault.aspx.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde applica­bles sur le site https:// en-US/Pages/default.aspx
.
1
Page 7
Honeywell • 5 RECEIPT OF DELIVERY
Product modified
Date:
Date:
Date:
9004.emf
2. RECEIPT OF DELIVERY
Check the correctness of delivery by comparing your order data to the drive information found on the package label. If the delivery does not correspond to your order, contact the supplier immediately. See chapter 2.3.
2.1 ‘Product modified’ sticker
In the small plastic bag included with delivery you will find a silver Product modified sticker. The purpose of the sticker is to notify the service personnel about the modifications made in the drive. Attach the sticker on the side of the drive to avoid losing it. Should the drive be later modified mark the change on the sticker.
Figure 1. ‘Product modified’ sticker
2.2 Unpacking and lifting the drive
The weights of the drives vary greatly according to the size. You may need to use a piece of special lifting equipment to remove the drive from its package. Note the weights of each indi­vidual frame size in Table 2 below.
Frame Weight [kg] Weight [lb.]
MR4 6.0 13.2 MR5 10.0 22.0 MR6 20.0 44.1 MR7 37.5 82.7 MR8 70.0 154.3 MR9 108.0 238.1
Table 2. Frame weights
If you decide to use a piece of lifting equipment see picture below for recommendations to lift the drive.
Page 8
RECEIPT OF DELIVERY Honeywell • 6
Max. 45°
9012.emf
NOTE: Place the lifting hooks symmetrically in at least two holes.The lifting device must be able to carry weight of the drive.
NOTE: The maximum allowed lifting angle is 45 degrees.
2.2.1 Lifting frames MR8 and MR9
Figure 2. Lifting bigger frames
The Honeywell Smart VFD HVAC undergoes scrupulous tests and quality checks at the factory before it is delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete.
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
2
Page 9
Honeywell • 7 RECEIPT OF DELIVERY
11447_uk
A = Updated Control Board No A = Legacy Control Board
T = Text KeyPad G = Graphic KeyPad
Interface
1 = NEMA 1 2 = NEMA 12 3 = NEMA 3R
Enclosure Type
0 = Drive Only 1 = Disconnect Only 2 = Two Contactor Bypass 3 = Three Contactor Bypass
Contactors
0 = Drive Only or No Special Options 1 = Auto-Bypass 3 = Auto-Bypass and HOA
Options
0007 = .75 Horse Power
0010 = 1 Horse Power
0100 = 10 Horse Power
Nominal Horsepower
A= 208/230 Vac Drive Alone, 208 Vac Bypass
B = 230 Vac Bypass
C = 480 Vac D = 600 Vac
Nominal Voltage
3 = Three Phase (3~in, 3~out)
Input Phase
HVFDSD = Honeywell SmartVFD HVAC
HVFDSB = Honeywell SmartVFD BYPASS
Product Family
HVFDSD 3 C 0100 G 1 0 0 A
2.3 Type designation code
Honeywell type designation code is formed of a four-segment code. Each segment of the type designation code uniquely corresponds to the product and options you have ordered. The code is of the following format:
Page 10
RECEIPT OF DELIVERY Honeywell • 8
2.4 Accessories
After having opened the transport package and lifted the converter out, check immediately that these various accessories were included in the delivery:
Rubber grommets (sizes vary according to frame)
Power cable clamps for EMC grounding
Screws for fixing the power cable clamps
Control cable grounding clamps
M4 screw for EMC level change in frame MR7
Additional grounding screw (if necessary, see chapter 1.3)
Ferrite holder
Optional plastic shield to prevent unintended contact with live parts from front (MR8 and MR9, IP00)
2
Page 11
Honeywell • 9 MOUNTING
5.04
3.94
Ø.28
Ø.51
2.83
.55
3.94
2.44
7.48
NEMA 1
Ø.98
1.30
1.26
1.26
NE MA12
1.26
1.30
1.26
Ø.9 8
3. MOUNTING
The drive must be mounted in vertical position on the wall. Ensure that the mounting plane is relatively even.
The drive shall be fixed with four screws (or bolts, depending on the unit size).
3.1 Dimensions
3.1.1 Wall mount, MR4-MR7
Figure 3. SmartVFD HVAC dimensions, MR4, wall mount
Page 12
MOUNTING Honeywell • 10
*Optional mounting holes (for NX replacement)
8.43
5.67
4.53.5 7 Ø.2 8 Ø.5 5
Ø.28
2.83
3.94*
.57 4.53
Ø.2 8
3.94*
NEMA1
1.38 1 .46 1.46
Ø1.30 Ø1.3 0Ø.98
NEMA12
1.36 1.48 1.48
1.38 1.46 1. 46
11449_uk
7.68
5.83
Ø.61
Ø.3 5
2.83
Ø.35
5.83
9.02
2.01 1.83 1.83
NEMA1
Ø1.57Ø1.30Ø1.57
1.42 1.42
2.40
2.01 1.83
NEMA12
Figure 4. SmartVFD HVAC dimensions, MR5, wall mount
Figure 5. SmartVFD HVAC dimensions, MR6, wall mount
3
Page 13
Honeywell • 11 MOUNTING
10.20
Ø.79
9.33
7.48
Ø.35
Ø.63
Ø2.01
NEMA1
2.72 2.72
1.381.38
NEMA12
Ø.98
Ø1.97
2.72 2.72
1.77 1.77
11451 00
Ø.98
3 x 1.50
Ø2.36
2.46 6.46
11.42
Ø.87
Ø.43
Ø.35
13.50
8.54
Ø.35
Ø.35
26.46
27.32
8.50
37.64
9.25
11452 00
Figure 6. SmartVFD HVAC dimensions, MR7, wall mount
3.1.2 Wall mount, MR8 and MR9
Figure 7. AC drive dimensions, MR8 NEMA1 and NEMA12
Page 14
MOUNTING Honeywell • 12
Ø.35
18.90
15.75
Ø.35
14.17
11.50
Ø.87
14.37
13.98
14.17
Ø.35
Ø.35
Cabinet wall (or similar)
IP21 IP54
Cabinet wall (or similar)
11453_00
Figure 8. AC drive dimensions, MR9 NEMA1 and NEMA12 (preliminary)
3.1.3 Flange mount
The AC drive can also be recessed into the cabinet wall or similar surface. A special flange mount option is available for this purpose. For an example of a flange-mounted drive, see Fig­ure 9.
Figure 9. Example of flange mount (frame MR9)
11454_uk
3
Page 15
Honeywell • 13 MOUNTING
A
C
F
11455 00
3.1.3.1 Flange mount - Frames MR4 to MR6
Figure 10. presents the dimensions of the mounting opening and Figure 11. the depth dimen­sions of the drives with the flange mount option.
Drive outline
Opening outline
TOP
Figure 10. Flange mount cutout dimensions for MR4 to MR6
Frame A B C D E F
MR4 12.20 5.39 13.27 5.67 4.33 12.44 MR5 16.06 5.98 17.09 6.30 5.20 16.30 MR6 21.02 7.99 22.05 8.31 7.24 21.30
Page 16
MOUNTING Honeywell • 14
MR4 MR5 MR6
3.03 4.45
7.48
8.43
4. 49
3.94
4.17 4.84
9.02
Table 3. Flange mount cutout dimensions for MR4 to MR6 [in]
Figure 11. MR4 to MR6, flange mount, depth dimensions
3
Page 17
Honeywell • 15 MOUNTING
C
A E
11482_00
3.1.3.2 Flange mount MR7 to MR9
Figure 12. presents the dimensions of the mounting opening and Figure 13. the dimensions of the drives with the flange mount option.
Drive outline
TOP
Figure 12. Flange mount cutout dimensions for MR7 to MR9
Frame A B C D E
MR7 25.79 9.45 26.85 10.55 .53 MR8 33.82 11.73 34.96 14.13 .67 MR9 38.39 19.09 41.34 20.87 2.13
Table 4. Flange mount cutout dimensions for MR7 to MR9 [in]
Opening outline
Page 18
MOUNTING Honeywell • 16
3.03 4.45
7.48
8.43
4. 49
3.94
4.17 4.84
9.02
11456_00
Figure 13. MR7 to MR9, flange mount, depth dimensions
3
Page 19
Honeywell • 17 MOUNTING
C
A
9013.emf
D
B
A
B
3.2 Cooling
The drive produces heat in operation and is cooled by air circulated by a fan. Enough free space needs to be left around the drive to ensure sufficient air circulation and cooling. Different acts of maintenance also require a certain amount of free space.
Make sure that the temperature of the cooling air does not exceed the maximum ambient tem­perature of the converter.
Min clearance [in], NEMA1
Type A
*
MR4 .79 .79 3.94 1.97 MR5 .79 .79 4.72 2.36 MR6 .79 .79 6.30 3.15 MR7 .79 .79 9.84 3.94 MR8 .79 .79 11.8 5.91 MR9 .79 .79 13.78 7.87
*. Min clearances A and B for
drives with IP54 enclosure is 0 in.
*
B
C D
Table 5. Min. clearances around drive
Figure 14. Installation space
A = clearance around the drive (see also B) B = distance from one drive to another or distance to cabinet wall C = free space above the drive D = free space underneath the drive
Page 20
MOUNTING Honeywell • 18
C+D
9014.emf
FRONT SIDE
Note that if several units are mounted above one another the required free space equals C + D (see Figure 15.). Moreover, the outlet air used for cooling by the lower unit must be direct­ed away from the air intake of the upper unit.
Figure 15. Installation space when drives are
Type
Cooling air required
[cfm]
MR4 26 MR5 44 MR6 112 MR7 109 MR8 197 MR9 366
Table 6. Required cooling air
mounted on top of each other
3
Page 21
Honeywell • 19 POWER CABLING
9007.emf
PE conductor and shield
PE conductors
Shield
4. POWER CABLING
The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals marked with U, V and W. See Table 7 for the cable recommmendations for different EMC lev­els.
Use cables with heat resistance of at least +158°F. The cables and the fuses must be dimen­sioned according to the drive nominal OUTPUT current which you can find on the rating plate.
1st environment 2nd environment
EMC levels
Cable type
Mains cable 1 1 1 Motor cable 3* 2 2 Control cable 4 4 4
Table 7. Cable types required to meet standards
According to EN61800-3 (2004)
Category C2 Category C3 Level T
1 = Power cable intended for fixed installation and the specific mains voltage. Shielded
cable not required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and intended for the
specific mains voltage. (MCMK or similar recommended). See Figure 16.
3 = Symmetrical power cable equipped with compact low-impedance shield and intended
for the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recom­mended cable transfer impedance (1...30MHz) max. 100mohm/m]. See Figure 16. *360º grounding of the shield with cable glands in motor end needed for EMC level C2.
4 =Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-
O or similar).
Figure 16.
NOTE: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames). NOTE: If safety switch is connected the EMC protection shall be continuous over the whole ca­ble installation.
Page 22
POWER CABLING Honeywell • 20
4.1 UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with a minimum heat-resistance of +140/167°F. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms sym­metrical amperes, 600V maximum.
4.1.1 Cable dimensioning and selection
Table 8 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes. Recommended fuse types are gG/gL.
These instructions apply only to cases with one motor and one cable connection from the drive to the motor. In any other case, ask the factory for more information.
4.1.1.1 Cable and fuse sizes, frames MR4 to MR6, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse volt­age rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specification. Big­ger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honey­well offers recommendations also for high speed J (UL & CSA), aR (UL recognized, IEC 60269-
4) and gS (IEC 60269-4) fuse ranges.
Frame Type
A007 3.7 6 AWG14 AWG24-AWG10 AWG17-AWG10 A0010 4.8 6 AWG14 AWG24-AWG10 AWG17-AWG10 A0015 6.6 10 AWG14 AWG24-AWG10 AWG17-AWG10 A0020 8 10 AWG14 AWG24-AWG10 AWG17-AWG10 A0030 11 15 AWG14 AWG24-AWG10 AWG17-AWG10
MR4
A0040 12.5 20 AWG14 AWG24-AWG10 AWG17-AWG10 C 0015 3.4 6 AWG14 AWG24-AWG10 AWG17-AWG10 C 0020 4.8 6 AWG14 AWG24-AWG10 AWG17-AWG10 C 0030 5.6 10 AWG14 AWG24-AWG10 AWG17-AWG10 C 0040 8.0 10 AWG14 AWG24-AWG10 AWG17-AWG10 C 0050 9.6 15 AWG14 AWG24-AWG10 AWG17-AWG10 C 0075 12.0 20 AWG14 AWG24-AWG10 AWG17-AWG10
*
I
[A]
L
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
4
Page 23
Honeywell • 21 POWER CABLING
Frame Type
A0050 18 25 AWG10 AWG20-AWG5 AWG17-AWG8 A0075 24.2 30 AWG10 AWG20-AWG5 AWG17-AWG8 A0100 31 40 AWG8 AWG20-AWG5 AWG17-AWG8 C 0100 16.0 25 AWG10 AWG20-AWG5 AWG17-AWG8 C 0150 23.0 30 AWG10 AWG20-AWG5 AWG17-AWG8
MR5
C 0200 31.0 40 AWG8 AWG20-AWG5 AWG17-AWG8 D0030 3.9 6 AWG14 AWG20-AWG5 AWG17-AWG8 D0050 6.1 10 AWG14 AWG20-AWG5 AWG17-AWG8 D0075 9 10 AWG14 AWG20-AWG5 AWG17-AWG8 D0100 11 15 AWG14 AWG20-AWG5 AWG17-AWG8 A0150 48 60 AWG4 AWG13-AWG0 AWG13-AWG2 A0200 62 80 AWG4 AWG13-AWG0 AWG13-AWG2 C 0250 38.0 50 AWG4 AWG13-AWG0 AWG13-AWG2 C 0300 46.0 60 AWG4 AWG13-AWG0 AWG13-AWG2
MR6
C 0400 D0150 18 20 AWG10 AWG13-AWG0 AWG13-AWG2 D0200 22 25 AWG10 AWG13-AWG0 AWG13-AWG2 D0250 27 30 AWG8 AWG13-AWG0 AWG13-AWG2 D0300 34 40 AWG8 AWG13-AWG0 AWG13-AWG2
*
I
L
[A]
**
61.0 80 AWG4 AWG13-AWG0 AWG13-AWG2
Fuse
(class T)
[A]
Mains, motor and
ground cable
Cu
Terminal cable size
Main terminal
Ground
terminal
*. For more information on type code, see page 7. **. The 460V models require 90-degree wire to meet UL regulations
Table 8. Cable and fuse sizes for Honeywell Smart VFD HVAC (MR4 to MR6)
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must be PVC-isolated; Max ambient temperature +86°F, max temperature of cable surface +158°F; Use only cables with concentric copper shield; Max number of parallel cables is 9. When using cables in parallel, area and the max number of cables must be observed. For important information on the requirements of the grounding conductor, see standard Underwriters’ Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Labora­tories UL508C.
NOTE HOWEVER that the requirements of both the cross-sectional
4.1.1.2 Cable and fuse sizes, frames MR7 to MR9, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse volt­age rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specification. Big­ger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honey­well offers recommendations also for high speed J (UL & CSA), aR (UL recognized, IEC 60269-
4) and gS (IEC 60269-4) fuse ranges.
Page 24
POWER CABLING Honeywell • 22
Frame Type
A0250 75 100 AWG2 AWG9-AWG2/0 AWG9-AWG2/0 A0300 88 110 AWG1 AWG9-AWG2/0 AWG9-AWG2/0 A0400 105 150 AWG1/0 AWG9-AWG2/0 AWG9-AWG2/0 C 0500 72.0 100 AWG2 AWG9-AWG2/0 AWG9-AWG2/0
MR7
MR8
MR9
C 0600 87.0 110 AWG1 AWG9-AWG2/0 AWG9-AWG2/0 C 0750 105.0 150 AWG1/0 AWG9-AWG2/0 AWG9-AWG2/0 D0400 41 50 AWG6 AWG9-AWG2/0 AWG9-AWG2/0 D0500 52 60 AWG6 AWG9-AWG2/0 AWG9-AWG2/0 D0600 62 70 AWG4 AWG9-AWG2/0 AWG9-AWG2/0 A0500 143 200 AWG3/0 AWG1-350kcmil AWG1-350kcmil A0600 170 225 250kcmil AWG1-350kcmil AWG1-350kcmil A0750 208 250 350kcmil AWG1-350kcmil AWG1-350kcmil C 1000 140.0 200 AWG3/0 AWG1-350 kcmil AWG1-350 kcmil C 1250 170.0 225 250 kcmil AWG1-350 kcmil AWG1-350 kcmil C 1500 205.0 250 350 kcmil AWG1-350 kcmil AWG1-350 kcmil D0750 80 90 AWG1/0 AWG1-350kcmil AWG1-350kcmil D1000 100 110 AWG1/0 AWG1-350kcmil AWG1-350kcmil D1250 125 150 AWG2/0 AWG1-350kcmil AWG1-350kcmil A1000 261 350 2x250kcmil AWG1-350kcmil AWG1-350kcmil A1250 310 400 2x350kcmil AWG1-350kcmil AWG1-350kcmil C 2000 261.0 350 2*250 kcmil AWG1-350 kcmil AWG1-350 kcmil C 2500 310.0 400 2*350 kcmil AWG1-350 kcmil AWG1-350 kcmil D1500 144 175 AWG3/0 AWG1-350kcmil AWG1-350kcmil D2000 208 250 300kcmil AWG1-350kcmil AWG1-350kcmil
I
L
[A]
Fuse
(class T)
[A]
Mains, motor
and ground
cable
Cu
Terminal cable size
Main terminal Ground terminal
Table 9. Cable and fuse sizes for Honeywell Smart VFD HVAC (MR7 to MR9)
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must be PVC-isolated; Max ambient temperature +86°F, max temperature of cable surface +158°F; Use only cables with concentric copper shield; Max number of parallel cables is 9. When using cables in parallel, area and the max number of cables must be observed. For important information on the requirements of the grounding conductor, see standard Underwriters’ Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Labora­tories UL508C.
NOTE HOWEVER that the requirements of both the cross-sectional
4.2 Control cables
For information on control cables see chapter 6.
4
Page 25
Honeywell • 23 POWER CABLING
9019.emf
D1
B1
C1
A1
D2
C2
E
Earth conductor
MAINS MOTOR
Earth conductor
4.3 Cable installation
Before starting, check that none of the components of the drive is live. Read carefully the warnings in chapter 1.
Place the motor cables sufficiently far from other cables
Avoid placing the motor cables in long parallel lines with other cables.
If the motor cables run in parallel with other cables note the minimum distances between the motor cables and other cables given in table below.
Distance between
cables, [in]
Shielded
cable, [ft]
11.8 164
39.4 656
The given distances also apply between the motor cables and signal cables of other systems.
The maximum lengths of motor cables are 328 ft. (MR4), 492 ft. (MR5 and MR6) and 656 ft. (MR7 to MR9).
The motor cables should cross other cables at an angle of 90 degrees.
If cable insulation checks are needed, see chapter Cable and motor insulation checks.
Start the cable installation according to the instructions below:
4.3.1 Frames MR4 to MR7
1
Strip the motor and mains cables as advised below.
Figure 17. Stripping of cables
Page 26
POWER CABLING Honeywell • 24
M4x55
Frame A1 B1 C1 D1 C2 D2 E
MR4 .59 1.38 .39 .79 .28 1.38
MR5 .79 1.57 .39 1.18 .39 1.57
MR6 .79 3.54 .59 2.36 .59 2.36
MR7 .79 3.15 .79 3.15 .79 3.15
Table 10. Cables stripping lengths [in]
Leave
as short
as pos-
sible
2
Open the cover of the drive.
Figure 18.
4
Page 27
Honeywell • 25 POWER CABLING
M4x8
9022.emf
11457_00
3
Remove the screws of the cable protection plate. Do not open the cover of the
power unit!
4
Figure 19.
Insert the cable grommets (included in the delivery) in the openings of the cable entry plate (included) as shown in the picture.
Figure 20.
Page 28
POWER CABLING Honeywell • 26
9217.emf
Insert the cables - supply cable, motor cable - in the openings of the cable entry plate. Then cut the rubber grommets open to slide the cables through. Do not cut the grommet openings wider than what is necessary for the cables you are using.
5
IMPORTANT NOTE FOR NEMA12 INSTALLATION:
To meet the requirements of the enclosure class NEMA12, the connection between the grommet and the cable must be tight. Therefore, lead the first bit of the cable out of the grommet straight before letting it bend. If this is not possible, the tightness
of the connection must be ensured with insulation
tape or a
cable
tie
.
Figure 21.
4
Page 29
Honeywell • 27 POWER CABLING
M4x16 (2.2 Nm)
9024.emf
11458 00
6
Detach the cable clamps and the grounding clamps (Figure 22) and place the cable entry plate with the cables in the groove on the drive frame (Figure 23).
Figure 22.
Figure 23.
Page 30
POWER CABLING Honeywell • 28
1
2
3
3
11459_uk
Connect the stripped cables (see Figure 17 and Table 10) as shown in Figure 24.
Expose the shield of all three cables in order to make a 360-degree con­nection with the cable clamp (1).
7
Connect the (phase) conductors of the supply and motor cables into their respective terminals (2).
Form the rest of the cable shield of all three cables into “pigtails” and make a grounding connection with a clamp as shown in Figure 24 (3). Make the pigtails just long enough to reach and be fixed to the terminal ­not longer.
Tightening torques of cable terminals:
Tightening torque
Frame Type
A 0007-A 0040 C 0015-C 0075
A 0050-A 0100 C 0100-C 0200 D 0030-D 0100
A 0150-A 0200 C 0250-C 0400 D 0150-D 0300
A 0250-A 0400 C 0500-C 0750 D 0400-D 0600
*. Cable clamping (Ouneva Pressure Terminal Connector)
MR4
MR5
MR6
MR7
[Nm]/[lb-in.]
Power and motor
terminals
[Nm] lb-in. [Nm] lb-in. [Nm] lb-in.
0.5—0.6 4.5—5.3 1.5 13.3 2.0 17.7
1.2—1.5 10.6—13.3 1.5 13.3 2.0 17.7
10 88.5 1.5 13.3 2.0 17.7
*
8/15
Table 11. Tightening torques of terminals
70.8/132.8* 1.5 13.3 8/15* 70.8/132.8*
Figure 24.
Tightening torque
[Nm]/[lb-in.]
EMC grounding
clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
4
Page 31
Honeywell • 29 POWER CABLING
11460_00
9220.emf
Check the connection of the grounding cable to the motor and the drive terminals marked with .
8
NOTE: Two protective conductors are required according to standard EN61800-
5-1. See Figure 25 and chapter Grounding and ground fault protection. Use an M5 size screw and tighten it to 2.0 Nm (17.7 lb-in.).
= M5; 2Nm
9
Figure 25. Additional protective grounding connector
Re-mount the cable protection plate (Figure 26) and the cover of the drive.
1
,
5
1
,
5
N
m
Figure 26. Re-mounting of cover components
N
m
Page 32
POWER CABLING Honeywell • 30
9019.emf
D1
B1
C1
A1
D2
C2
E
Earth conductor
Earth conductor
4.3.2 Frames MR8 and MR9
1
Strip the motor and mains cables as advised below.
Figure 27. Stripping of cables
Frame A1 B1 C1 D1 C2 D2 E
MR8 1.57 7.09 .98 11.81 .98 11.81
Leave as
short as
MR9 1.57 7.09 .98 11.81 .98 11.81
Table 12. Cables stripping lengths [in]
possible
4
Page 33
Honeywell • 31 POWER CABLING
9046.emf
M4 x 10
1
2
11461_00
2
MR9 only: Remove the main cover of the AC drive.
3
Figure 28.
Remove the cable cover (1) and the cable fitting plate (2).
MR9
Figure 29.
Page 34
POWER CABLING Honeywell • 32
4
MR9 only: Loosen the screws and remove the sealing plate.
MR9
11462_00
Figure 30.
5
Locate the terminals. OBSERVE the exceptional placement of motor cable ter­minals in MR8!
11463_00
Figure 31.
4
Page 35
Honeywell • 33 POWER CABLING
11464_00
11465_00
Cut the rubber grommets open to slide the cables through. Should the grommets
6
fold in while inserting the cable, just draw the cable back a bit to straighten the grommets up. Do not cut the grommet openings wider than what is necessary for the cables you are using.
Figure 32.
7
Place the grommet with the cable so that the frame end plate fits in the groove on the grommet, see Figure 33. To meet the requirements of the enclosure class NEMA12, the connection between the grommet and the cable must be tight. Therefore, lead the first bit of the cable out of the grommet straight before letting it bend. If this is not possible, the tightness As an example,see Figure 21.
of the connection must be ensured with insulation
tape or a
cable
tie.
Figure 33.
Page 36
POWER CABLING Honeywell • 34
11466_00
8
9
If you use thick cables insert the cable separators in between the terminals in order to avoid contact between the cables.
Figure 34.
Connect the cables stripped as shown in Figure 27.
Connect the (phase) conductors of the supply and motor cables into their respective terminals (a).
Form the rest of the cable shield of all cables into “pigtails” and make a grounding connection as shown in Figure 35 (b) using the clamp from the
Accessories bag.
Note also correct position of the ferrite holder (c) AFTER the cable strip­ping (in MR8 and EMC class C2 only).
Note: If you use several cables on one connector observe the position of cable lugs on top of each other. See Figure 36 below.
4
Page 37
Honeywell • 35 POWER CABLING
L1 L2 L3
DC-
DC+
R+
R-
b
a
MR8
c
UWV
11467_00
Cable lug
Cable lug
Connector
Figure 35.
Figure 36. Placing two cable lugs on top of each other
Tightening torques of cable terminals:
Tightening torque
Frame Type
A 0500-A 0750
MR8
MR9
C 1000-C 1500 D 0750-D 1250
A 1000-A 1250 C 2000-C 2500 D 1500-D 2000
*. Cable clamping (Ouneva Pressure Terminal Connector)
[Nm]/[lb-in.]
Power and motor
terminals
[Nm] lb-in. [Nm] lb-in. [Nm] lb-in.
*
20/40
20/40* 177/354* 1.5 13.3 20 177
Table 13. Tightening torques of terminals
177/354* 1.5 13.3 20 177
Tightening torque
[Nm]/[lb-in.]
EMC grounding
clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
Page 38
POWER CABLING Honeywell • 36
9035.emf
M4x8
M4x8
9223.emf
10
Expose the shield of all three cables in order to make a 360-degree connection with the cable clamp.
Figure 37.
11
Re-attach first the cable fitting plate and then the cable cover.
Figure 38.
4
Page 39
Honeywell • 37 POWER CABLING
11468_00
12
MR9 only: Now re-mount the main cover (unless you want to make the control
connections first).
13
Figure 39.
Check the connection of the earth cable to the motor and the AC drive terminals marked with .
NOTE: Two protective conductors are required according to standard EN61800­5-1. See chapter Grounding and ground fault protection.
Connect the protective conductor using a cable shoe and an M8 screw (included in the
Accessories bag) on either of the screw connectors as advised in
Figure 40.
Page 40
POWER CABLING Honeywell • 38
11469_00
Figure 40.
4.3.3 Cable and motor insulation checks
1. Motor cable insulation checks Disconnect the motor cable from terminals U, V and W of the drive and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insula­tion resistance must be >1MΩ at ambient temperature of 68°F.
2. Mains cable insulation checks Disconnect the mains cable from terminals L1, L2 and L3 of the drive and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insula­tion resistance must be >1MΩ at ambient temperature of 68°F.
3. Motor insulation checks Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1MΩ at ambient temperature of 68°F.
4.4 Installation in corner-grounded network
Corner grounding is allowed for the drive types rating from 72 A to 310 A at 380...480 V supply and from 75 A to 310 A at 208...240 V supply.
In these circumstances the EMC protection class must be changed to level C4 following the instructions in Chapter 5.2 of this manual.
Corner grounding is not allowed for the drive types with rating from 3.4 A to 61 A at 380...480 V supply and 3.7 A to 62 A with 208...240 V supply.
4
Page 41
Honeywell • 39 COMMISSIONING
5. COMMISSIONING
Before commissioning, note the following directions and warnings:
Internal components and circuit boards of the drive (except for the galvanically isolated I/O terminals) are live when it is connected to mains potential. Coming
into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals B-/B+ are live when the drive is connected to mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when the drive is disconnected from mains.
Do not make any connections to or from the drive when it is connected to the mains.
After disconnecting the drive from the mains, wait until the fan stops and the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of the drive. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present.
Always ensure abscence of voltage before electrical work! Before connecting the frequency converter to mains make sure that the front
and cable covers of the drive are closed.
Page 42
COMMISSIONING Honeywell • 40
5.1 Commissioning of the SmartVFD HVAC
1
2
3 4 5
6
7
Read carefully the safety instructions in Chapter 1 and above and follow them.
After the installation, make sure that:
both the drive and the motor are grounded.
the mains and motor cables comply with the requirements given in chapter
4.1.1.
the control cables are located as far as possible from the power cables, see chapter 4.3.
the shields of the shielded cables are connected to protective ground
marked with .
check the tightening torques of all terminals
the wires do not touch the electrical components of the drive.
the common inputs of digital input groups are connected to +24V or ground of the I/O terminal or the external supply.
Check the quality and quantity of cooling air (chapter 3.2 and Table 6).
Check the inside of the drive for condensation.
Check that all Start/Stop switches connected to the I/O terminals are in Stop-position.
Before connecting the AC drive to mains:
check mounting and condition of all fuses and other protective devices
Run the Startup Wizard (see the Application Manual).
5
Page 43
Honeywell • 41 COMMISSIONING
MR4
9064.emf
MR5
MR6
5.2 Changing EMC protection class
I
f your supply network is an IT (impedance-grounded) system but your AC drive is EMC-protected accord­ing to class C2 you need to modify the EMC protection of the AC drive to EMC-level T. This is done by removing the built-in EMC jumpers with a simple procedure described b
Warning! Do not perform any modifications on the drive when it is con­nected to mains.
5.2.1 Frames MR4 to MR6
elow:
1
connecting the built-in RFI-filters to ground. See Figure 41. and Figure 42.
NOTE: The locations of the EMC-jumpers have changed in frames MR5 and MR6. Figure 41. shows the old locations and Figure 42. the new locations in frames MR5 and MR6.
Remove the main cover of the drive (see pages 24 and 31) and locate the jumpers
Figure 41. Current locations of the EMC-jumpers in frame MR4, old locations in frames MR5 and MR6
Page 44
COMMISSIONING Honeywell • 42
9099.emf
MR 5
MR 6
Figure 42.Current locations of the EMC-jumpers in frames MR5 and MR6
2
Figure 43. Removing the jumper, MR5 as example
Disconnect the RFI-filters from ground by removing the EMC-jumpers using long­nose pliers or similar. See Figure 43.
5
Page 45
Honeywell • 43 COMMISSIONING
9066.emf
9065.emf
5.2.2 Frames MR7 and MR8
Follow the procedure described above to modify the EMC protection of the drive of frames MR7 and MR8 to EMC-level C4.
1
Figure 44.
2
Remove the main cover of the drive and locate the jumper. MR8 only: Push down the grounding arm. See Figure 44.
MR7 and MR8: Locate the EMC box under the cover. Remove the screws of the box cover to expose the EMC-jumper. Detach the jumper and re-fix the box cover.
Figure 45.
Page 46
COMMISSIONING Honeywell • 44
9062.emf
3
Figure 46. MR7: Detaching the DC grounding busbar from frame
MR7 only: locate the DC grounding busbar between connectors R- and U and detach the busbar from the frame by undoing the M4 screw.
5
Page 47
Honeywell • 45 COMMISSIONING
11470_00
5.2.3 Frame MR9
Follow the procedure described above to modify the EMC protection of the AC drive of frame MR9 to EMC-level T.
Find the Molex connector in the accessories bag. Remove the main cover of the
1
Molex connector
AC drive and locate the place for the connector next to the fan. Push the Molex connector in its place. See Figure 47.
2
Figure 47.
Further remove the extension box cover (1), the touch shield (2) the I/O plate (4) with I/O grommet plate (3). Locate the EMC jumper on the EMC board (see mag­nification below) and remove it.
Figure 48.
11471_00
Page 48
COMMISSIONING Honeywell • 46
CAUTION! Before connecting the AC drive to mains make sure that the EMC pro­tection class settings of the drive are appropriately made.
NOTE! After having performed the change write ‘EMC level modified’ on the stick- er included with the drive delivery (see below) and note the date. Unless already done, attach the sticker close to the name plate of the drive.
5
Page 49
Honeywell • 47 CONTROL UNIT
STO JMP
L
I
M
K
H
G
F
J
E
D
A
B
C
6. CONTROL UNIT
The control unit of the AC drive contains the standard boards and the option boards. The option boards are connected to the slots of the control board (see 6.3 Installation of Option Boards).
Figure 49.The components of the control unit
A. The control terminals for the standard I/O
B. The Ethernet connection
connections
C. The relay board terminals for 3 relay out-
D. The option boards
puts or 2 relay outputs and a thermistor
E. A DIP switch for the RS485 bus termina-
tion
G. A DIP switch for the isolation of the digital
inputs from ground
I. A DIP switch for the signal selection of
Analogue Input 1
K. A fan (only in IP54 of MR4 and of MR5) L. The battery for the RTC
F. A DIP switch for the signal selection of
Analogue Output
H. A DIP switch for the signal selection of
Analogue Input 2
J. The status indicator of the Ethernet con-
nection
M. The location and the default position of
the Safe Torque Off (STO) jumper (feature not available, do not touch)
Page 50
CONTROL UNIT Honeywell • 48
When you receive the AC drive, the control unit contains the standard control interface. If you included special options in your order, the AC drive will be as in your order. On the next pages, you will find information on the terminals and general wiring examples.
It is possible to use the drive with an external power source with these properties: +24 VDC ±10%, minimum 1000 mA. Connect the external power source to terminal 30. This voltage is sufficient to keep the control unit on and for you to set the parameters. The measurements of the main circuit (for example, the DC link voltage, and the unit temperature) are not available when the drive is not connected to mains.
The status LED of the drive shows the status of the drive. The status LED is located in the con­trol panel, below the keypad, and it can show 5 different statuses.
Colour of the LED light Status of the drive
Blinking slowly Ready Green Run Red Fault Orange Alarm Blinking fast Downloading software
Table 14. The statuses of the status LED of the drive
6.1 Control Unit Cabling
The standard I/O board has 22 fixed control terminals and 8 relay board terminals. You can see the standard connections of the control unit and the descriptions of signals in Fig. 39.
6.1.1 Selection of the Control Cables
The control cables must be a minimum of 20 AWG (0.5 mm more on the cable types in Table 7 on page 19. The terminal wires must be a maximum of 12 AWG (2.5 mm
The terminal The terminal screw
All the terminals of the I/O board and the relay board
6.1.2 Control Terminals and Dip Switches
Here you see the basic description of the terminals of the standard I/O board and the relay board. For more information, see 8.2.1 Technical information on control connections.
2
) for the relay board terminals and other terminals.
M3 0.5 4.5
Table 15. Control cable tightening torques
2
) screened multicore cables. See
Tightening torque
Nm lb-in.
Some terminals are assigned for signals that have optional functions that you can use with the DIP switches. See more in 6.1.2.1 Selection of terminal functions with DIP switches.
6
Page 51
Honeywell • 49 CONTROL UNIT
RUN
FAULT
READY
*)
*)
Reference output
+10 Vref
Terminal
Standard I/O board
Signal
1
24V auxiliary voltage
24Vout6
Analogue input, voltage or current
Reference
potentiometer
1...10kΩ
Actual value
2-wire transmitter
I = (0)4...20mA
AI1+2
Analogue input common, (current)
AI1-3
Analogue input, voltage or current
AI2+4
Analogue input common, (current)
AI2-5
Analogue signal (+output)
AO1+
RUN
18
Analogue output common / I/O ground
AO1-/GND19
24V auxiliary input voltage
+24Vin30
24V auxiliary voltage
24Vout
12
I/O ground
GND7
I/O ground
GND13
Digital input 1
DI18
Digital input 2
DI29
Digital input 3
DI310
Digital input 4
DI414
Digital input 5
DI515
Digital input 6
DI616
Relay output 1
RO1 NC21
22
RO1 CM
RO1 NO23
Common for DI1-DI6
CM11
Common for DI1-DI6
CM
17
Serial bus, negative
RS485A
Serial bus, positive
RS485
B
Relay output 2
Relay output 3
RO2 NC24
25
RO2 CM
RO2 NO26
32
RO3 CM
RO3 NO33
Description
Frequency reference
Frequency reference
Start forward
Start reverse
External fault
DI4 DI5 Freq. ref. Open Closed
Open Closed
Open Open Closed Closed
Analog input 1 Preset Freq. 1 Preset Freq. 2 Preset Freq. 3
Fault reset
Output frequency
Modbus RTU BACnet, N2
mA
Figure 50.The signals of the control terminals on the standard I/O board, and a connection
example. If you include the optional code +SBF4 in your order, the relay output 3 is re-
placed with a thermistor input.
Page 52
CONTROL UNIT Honeywell • 50
RO1 NC RO1 CM RO1 NO
RO2 NC
RO2 CM
RO2 NO
RO3 CM
RO3 NO
21 22
23 24
25
26
32
33
RUN
RUN
FAULT
READY
Relay output 1
Relay output 2
Relay output 3
From Standard I/O board
Terminal Signal
Default
Relay board 1
From term.
#6 or 12
From term.
#13
Figure 51.The standard relay board
6.1.2.1 Selection of terminal functions with DIP switches
You can make 2 selections with the DIP switches for specified terminals. The switches have 2 positions: up and down. You can see the location of the DIP switches and the possible selec­tions in Figure 52.
6
Page 53
Honeywell • 51 CONTROL UNIT
A B
A
B
C
D
E
AI2
U I
AI1
U I
RS-485
OFF ON
AO1
U I
Figure 52.The selections of the DIP switches
A. The voltage signal (U), 0-10 V input B. The current signal (I), 0-20 mA input C. OFF D. ON E. The RS-485 bus termination
The DIP switch The default position
AI1 U AI2 I AO1 I RS485 bus termination OFF
Table 16. The default positions of the DIP switches
Page 54
CONTROL UNIT Honeywell • 52
C
D
B
A
6.1.2.2 Isolation of digital inputs from ground
It is possible to isolate from ground the digital inputs (terminals 8-10 and 14-16) on the standard I/O board. To do this, change the position of a DIP switch on the control board.
A
B
C
Figure 53.Change the position of this switch to isolate the digital inputs from ground
A. The digital inputs B. Floating C. Connected to GND (default)
6.2 Fieldbus Connection
You can connect the drive to fieldbus with an RS485 or an Ethernet cable. If you use an RS485 cable, connect it to terminal A and B of the standard I/O board. If you use an Ethernet cable, connect it to the Ethernet terminal below the cover of the drive.
A. RS485 terminal A = Data - B. RS485 terminal B = Data + C. The Ethernet terminal D. The control terminals
Figure 54.The Ethernet and RS485 connections
6
Page 55
Honeywell • 53 CONTROL UNIT
IP54
6.2.1 Using Fieldbus Through an Ethernet Cable
Item Description
The plug type A shielded RJ45 plug, maximum length 40 mm (1.57 in) The cable type CAT5e STP The cable length Maximum 100 m (328 ft)
Table 17. Ethernet cable data
6.2.1.1 ETHERNET CABLING
1
2
Connect the Ethernet cable to its terminal.
In IP21, cut free the opening on the cover of the AC drive for the Ethernet cable. In IP54, cut a hole in a grommet and move the cable through it.
a. If the grommet folds in when you
put the cable, pull the cable back to make the grommet straight.
b. The hole in the grommet must
not be wider than your cable.
c. Pull the first bit of the cable out
of the grommet so that it stays straight. If this is not possible, make the connection tight with some insulation tape or a cable tie.
IP21
Page 56
CONTROL UNIT Honeywell • 54
A
A. The Ethernet cable in IP21
A
A. The Ethernet cable in IP54
Put the cover of the drive back. Keep the distance between the Ethernet cable and the motor cable at a minimum of 30 cm (11.81 in).
See more in the Installation Manual of the fieldbus that you have.
3
6
Page 57
Honeywell • 55 CONTROL UNIT
10
5
15 mm
6.2.2 Using Fieldbus Through an RS485 Cable
Item Description
The plug type The cable type STP (shielded twisted pair), Belden 9841 or almost the same
The cable length So that it agrees with the fieldbus. See the fieldbus manual.
RS485 CABLING
Remove approximately 15 mm (0.59 in) of the grey shield of the RS485 cable. Do this for the 2 fieldbus cables.
a. Strip the cables for approxi-
mately 5 mm (0.20 in) to put them in the terminals. Do not keep more than 10 mm (0.39 in) of the cable outside the termi-
1
nals.
b. Strip the cable at such a dis-
tance from the terminal that you can attach it to the frame with the grounding clamp for control cable. Strip the cable at a maxi­mum length of 15 mm (0.59 in). Do not remove the aluminium shield of the cable.
2.5 mm
2
Table 18. RS485 cable data
Page 58
CONTROL UNIT Honeywell • 56
Connect the cable to the standard I/O board of the drive, in terminals A and B.
A = negative
B = positive
2
3
Attach the shield of the cable to the frame of the drive with a grounding clamp for control cable to make a grounding connection.
6
Page 59
Honeywell • 57 CONTROL UNIT
If the drive is the last device on the field­bus line, set the bus termination.
a. Find the DIP switches on the left
side of the control unit of the drive.
b. Set the DIP switch of the RS485
bus termination to the ON posi­tion.
c. Biasing is built in the bus termi-
nation resistor. The termination resistance is 220 ȍ.
4
5
In IP21, unless you have cut the openings for other cables, cut an opening on the cover of the drive for the RS485 cable.
Page 60
CONTROL UNIT Honeywell • 58
A
A. The fieldbus cables
Put the cover of the drive back. Pull the RS485 cables to the side.
a. Keep the distance of the Ether-
net, I/O and Fieldbus cables from the motor cable at a mini­mum of 30 cm (11.81 in).
b. Move the fieldbus cables away
from the motor cable.
6
7
Set the bus termination for the first and the last device of the fieldbus line. We rec­ommend that the first device on the fieldbus is the master device.
D
A
D
E
A. The termination is activated B. The termination is deactivated C. The termination is activated with a
DIP switch
E. The fieldbus
B
D. The bus termination. The resistance
is 220 ȍ.
C
6
Page 61
Honeywell • 59 CONTROL UNIT
M4x55
Note: If you do power-down to the last device, there is no bus termination.
6.3 Installation of Option Boards
CAUTION!
Do not install, remove, or replace option boards on the drive when the power is on. Doing this can cause damage to the boards.
Install the option boards into the option board slots of the drive. Refer to Table 19.
Type of the option board
HVFDSDOPT6DI HVFDSDOPT2RO1T The Thermistor relay board C, D, E
HVFDSDOPT1AI2AO The I/O expander board C, D, E HVFDSDOPT3RO The Relay board C, D, E HVFDSDOPT1RO5DI The I/O expander board C, D, E
HVFDOPTTMP
32006630-001 The LonWorks fieldbus board D, E
Table 19. The option boards and their correct option board slots
THE INSTALLATION PROCEDURE
Open the cover of the AC drive.
WARNING
Do not touch the control terminals. They can have a dangerous volt­age also when the drive is discon-
1
nected from mains.
Description of the option board The correct slot or slots
The I/O expander board
The Temperature measurement board
C, D, E
C, D, E
Page 62
CONTROL UNIT Honeywell • 60
A. The slot coding
If you have an HVFDSDOPT or an 32006630-001 option board, make sure that the label on it says "dv" (dual volt­age). This shows that the option board is
2
compatible with the drive.
Note: It is not possible to install option boards that are not compatible with the drive.
To get access to the option board slots, open the cover of the control unit.
dv
OPT
A
3
6
Page 63
Honeywell • 61 CONTROL UNIT
A. The slot coding B. The option board slots
Install the option board into the correct slot: C, D or E. See Table 19.
a. The option board has a slot cod-
ing, because of which it is not possible to install the option board in an incorrect slot.
A
4
B
5
6.4 Installation of a Battery for the Real Time Clock (RTC)
To use the Real Time Clock (RTC), you must install a battery in the drive.
1
2
The battery will last approximately 10 years. See more about the functions of the RTC in the Application Manual.
Close the cover of the control unit. Put the cover of the AC drive back.
Use a ½ AA battery with 3.6 V and a capacity of 1000-1200 mAh. You can use, for example, a Panasonic BR-1/2 AA or a Vitzrocell SB-AA02.
Install the battery on the left side of the control panel. See Figure 49 on page 47.
Page 64
CONTROL UNIT Honeywell • 62
6.5 Galvanic Isolation Barriers
The control connections are isolated from mains. The GND terminals are permanently connect­ed to I/O ground.
The digital inputs on the standard I/O board can be galvanically isolated from the I/O ground. To isolate the digital inputs, use the DIP switch that has the positions FLOAT and GND.
A
10Vref GND +24V GND AI1+ AI1-
AI2+ AI2­DI1... DI6 CM AO1+ AO1­+24Vin
RS485
RO1/1 RO1/2 RO1/3 RO2/1 RO2/2 RO2/3 TI1+ TI1-
L1
L2
L3
DC- DC+/R+ R-
Table 20. The galvanic isolation barriers
A. The control unit B. The power unit
B
U
V
W
6
Page 65
Honeywell • 63 MAINTENANCE
7. MAINTENANCE
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is rec­ommended to ensure a trouble-free operation and a long lifetime of the drive. We recommend to follow the table below for maintenance intervals.
NOTE: Because of capacitor type (thin film capacitors), reforming of capacitors is not neces­sary.
Maintenance interval Maintenance action
Regularly and according to gen­eral maintenance interval
6–24 months (depending on environment)
24 months Clean heatsink and cooling tunnel 3–6 years Change internal IP54 fan 6–10 years Change main fan
• Check tightening torques of terminals
• Check input and output terminals and control I/O terminals.
• Check operation of cooling fan
• Check for corrosion on terminals, busbars and other surfaces
Table 1. Maintenance
Page 66
Honeywell • 64 PRODUCT DATA
8. PRODUCT DATA
8.1 Power ratings
8.1.1 Mains voltage 208-240 V
Mains voltage 208-240V, 50-60 Hz, 3~
Loadability Motor shaft power
*
[A]
Low
L
10% overload
current
[A]
Converter
type
Rated continuous
current I
A 0007 3.7 4.1 0.55 0.75
A 0010 4.8 5.3 0.75 1.0
A 0015 6.6 7.3 1.1 1.5
A 0020 8.0 8.8 1.5 2.0
MR4
A 0030 11.0 12.1 2.2 3.0
A 0040 12.5 13.8 3.0 4.0
A 0050 18.0 19.8 4.0 5.0
A 0075 24.2 26.4 5.5 7.5
MR5
A 0100
**
31.0 34.1 7.5 10.0
A 0150 48.0 52.8 11.0 15.0
230 supply 208-240V supply
10% overload
40°C [kW]
10% overload
40°C
[hp]
A 0200** 62.0 68.2 15.0 20.0
MR6
A 0250 75.0 82.5 18.5 25.0
A 0300 88.0 96.8 22.0 30.0
MR7
A 0400 105.0 115.5 30.0 40.0
A 0500 143.0 154.0 37.0 50.0
A 0600 170.0 187.0 45.0 60.0
MR8
A 0750 208.0 225.5 55.0 75.0
A 1000 261.0 287.1 75.0 100.0
A 1250 310.0 341.0 90.0 125.0
MR9
*
See chapter 8.1.4.
**
Given low loadabilities valid for 230V drives at a switching frequency of
4kHz
Table 20. Power ratings, supply voltage 208-240V.
NOTE: The rated currents in given ambient temperatures (in Table 3) are achieved only when the switching frequency is equal to or less than the fac­tory default.
Page 67
PRODUCT DATA Honeywell • 65
8.1.2 Mains voltage 380-480V
Mains voltage 380-480V, 50-60 Hz, 3~
Loadability Motor shaft power
*
[A]
Low
L
10% overload
current
[A]
Converter
type
Rated continuous
current I
C 0015 3.4 3.7 1.1 1.5
C 0020 4.8 5.3 1.5 2.0
C 0030 5.6 6.2 2.2 3.0
C 0040 8.0 8.8 3.0 4.0
MR4
C 0050 9.6 10.6 4.0 5.0
C 0075
**
12.0 13.2 5.5 7.5
C 0100 16.0 17.6 7.5 10
C 0150 23.0 25.3 11.0 15.0
MR5
C 0200** 31.0 34.1 15.0 20.0
C 0250 38.0 41.8 18.5 25.0
C 0300 46.0 50.6 22.0 30.0
MR6
C 0400** 61.0 67.1 30.0 40.0
C 0500 72.0 79.2 37.0 50.0
C 0600 87.0 95.7 45.0 60.0
MR7
C 0750 105.0 115.5 55.0 75.0
C 1000 140.0 154.0 75 100
C 1250 170.0 187.0 90 125
MR8
C 1500 205.0 225.5 110 150
C 2000 261.0 287.1 132 200
400V supply 480V supply
10% overload
104°F
[kW]
10% overload
104°F
[HP]
C 2500 310.0 341.0 160 250
MR9
*
See chapter 8.1.4
**
Given low loadabilities valid for 480V drives at a switching frequency of
4kHz
Table 1. Power ratings, supply voltage 380-480V.
NOTE: The rated currents in given ambient temperatures (in Table 3) are achieved only when the switching frequency is equal to or less than the factory default.
8
Page 68
Honeywell • 66 PRODUCT DATA
8.1.3 Mains voltage 525-600V
Mains voltage 525-600V, 50-60 Hz, 3~
Loadability
Converter
type
Rated continuous
current I
[A]
Low
L
*
10% overload
current
[A]
D0030 3.9 4.3 3.0
D0050 6.1 6.7 5.0
D0075 9.0 9.9 7.5
MR5
D0100 11.0 12.1 10.0
D0150 18.0 19.8 15.0
D0200 22.0 24.2 20.0
D0250 27.0 29.7 25.0
MR6
D0300 34.0 37.4 30.0
D0400 41.0 45.3 40.0
D0500 52.0 57.2 50.0
MR7
D0600 62.0 68.2 60.0
D0750 88.0 154.0 75.0
D1000 110.0 187.0 100.0
MR8
D1250 137.5 225.5 125.0
D1500 144.0 158.4 150.0
Motor shaft
power
600V supply
10% overload
104°F
[HP]
D2000 208.0 228.8 200.0
MR9
*
See chapter 8.1.4
Table 2. Power ratings, supply voltage 525-600V.
Page 69
PRODUCT DATA Honeywell • 67
I
L
I
L* 11 0%
1 min 9 min
I
L*11 0%
Current
Time
8.1.4 Definitions of overloadability
Low overload
Example: If the duty cycle requires 110% rated current I
=Following continuous operation at rated output current IL, the converter is fed with
110% * I
9 min must be at rated current or less.
for 1 min, followed by a period of IL.
L
Figure 1. Low overload
for 1 min in every 10 min, the remaining
L
11481_uk
8
Page 70
Honeywell • 68 PRODUCT DATA
8.2 SmartVFD HVAC - technical data
Mains connection
Motor connection
Control
characteristics
Input voltage U
in
208...240V; 380…480V; 525…600V;
-10%…+10%
Input frequency 47…66 Hz
Connection to mains Once per minute or less
Starting delay 4 s (MR4 to MR6); 6 s (MR7 to MR9)
Output voltage
Continuous output current
Starting current
0-U
in
IL:Ambient temperature max. +104°F, overload 1.1 x I
(1 min./10 min.)
L
IS for 2 s every 20 s
Output frequency 0…320 Hz (standard)
Frequency resolution 0.01 Hz
200-500 V
• MR4-MR6:
• 1.5-10 kHz
• Default: 6 kHz (except for A 0040, A 0100, A 0200, C 0075, C 0200 and C 0400: 4 kHz)
• MR7-MR9:
•1.5-6 kHz
• Default: MR7: 4 kHz, MR8: 3 kHz, MR9:
Switching frequency
2kHz
(see parameter M3.1.2.1)
600 V
• MR5-MR9:
•1.5-6 kHz
• Default: 2 kHz
• For a product that is configured for a C4 installation on IT network the maximum switching frequency is limited to default 2kHz.
Automatic switching frequency derating in case of overload.
Frequency reference Analogue input Panel reference
Resolution 0.1% (10-bit), accuracy ±1% Resolution 0.01 Hz
Field weakening point 8…320 Hz
Acceleration time 0.1…3000 sec
Deceleration time 0.1…3000 sec
Page 71
PRODUCT DATA Honeywell • 69
IL : -10°C (no frost)…+40°C, Ambient operating temperature
14 (no frost) ... 104 F
Up to 50 °C with derating (1.5%/1°C)
Ambient conditions
Ambient conditions
(cont.)
Storage temperature
Relative humidity
Air quality: chemical vapours mechanical particles
Altitude
Vibration EN61800-5-1/ EN60068-2-6
Shock EN61800-5-1 EN60068-2-27
-40°C ... +70°C
-40°F…+158°F
0 to 95% RH, non-condensing, non-corro-
sive
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to
1,000 m / 3280 ft
1-% derating for each 100m/328ft above
1,000m/3280ft
Max. altitudes:
208...240V: 4,500m/14763 ft
tems)
380...480V:
tems)
525...690 V: 2,000m/6562 ft (TN and IT
systems, no corner grounding)
Voltage for I/O signals:
Up to 2,000m/6561ft : Allowed up to 240V
2,000m...4,500m / 6561...14763ft: Allowed
up to 120V
5…150 Hz
Displacement amplitude 1 mm (peak) at
5…15.8 Hz (MR4…MR9)
Max acceleration amplitude 1 G at
15.8…150 Hz (MR4…MR9)
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in
package)
4,500m/14763 ft (TN and IT sys-
(TN and IT sys-
Enclosure class
IP21/NEMA 1 standard in entire kW/HP range
IP54/NEMA12 option
Note! Keypad required for IP54/NEMA12
8
Page 72
Honeywell • 70 PRODUCT DATA
EMC (at default
settings)
Emissions
Safety
Immunity
Emissions
Average noise level (cooling fan) sound power level in dB(A)
Fulfils EN61800-3 (2004), first and second
environment
Depend on EMC level.
+EMC2: EN61800-3 (2004), Category C2
Honeywell Smart VFD HVAC will be deliv-
ered with class C2 EMC filtering, if not oth-
erwise specified.
Honeywell Smart VFD HVAC can be modi-
fied for IT-networks. See chapter 5.2.
• 200-500 V: EN 61800-3 (2004), category C2.
• 600 V: EN 61800-3 (2004), category C3.
• All: The product is configurable to cate­gory C4 for installation on IT networks. The drive can be modified for IT type mains. See chapter 7.6 Installation in an IT system. The IP00 / UL Open Type drive has by default category C4.
MR4: 65 MR7: 77 MR5: 70 MR8: 86 MR6: 77 MR9: 87
EN 61800-5-1 (2007), CE, cUL; (see unit nameplate for more detailed approvals)
Control connections See chapter 8.2.1.
Protections
Overvoltage trip limit Undervoltage trip limit
Ground fault protection
Mains supervision Ye s
Motor phase supervision
Yes Yes
In case of ground fault in motor or motor cable, only the drive is protected
Trips if any of the output phases is missing
Overcurrent protection Yes
Unit overtemperature protection
Motor overload protection
Yes
Yes
Motor stall protection Yes
Protections (cont.)
Motor underload protection
Yes
Short-circuit protection of +24V and +10V
Yes
reference voltages
Table 3. Smart VFD HVAC technical data
Page 73
PRODUCT DATA Honeywell • 71
8.2.1 Technical information on control connections
Basic I/O board
Terminal Signal Technical information
Reference output +10V, +3%; Maximum current 10 mA
1
Analogue input channel 1 0- +10V (Ri = 200 kΩ) 4-20 mA (Ri =250 Ω) Resolution 0.1 %, accuracy ±1 % Selection V/mA with dip-switches (see page 50)
Differential input if not connected to ground; Allows ±20V differential mode voltage to GND
Analogue input channel 1 Defauit:4-20 mA (Ri =250 Ω) 0-10 V (Ri=200kΩ) Resolution 0.1 %, accuracy ±1 % Selection V/mA with dip-switches (see page 50)
Differential input if not connected to ground; Allows 20V differential mode voltage to GND
+24VDC, ±10%, max volt. ripple < 100mVrms; max. 250mA Dimensioning: max. 1000mA/control box. Short-circuit protected
Ground for reference and controls (connected internally to frame ground through 1MΩ)
Positive or negative logic Ri = min. 5kΩ 18…30V = "1"
Digital inputs can be disconnected from ground, see chapter
6.1.2.2. +24VDC, ±10%, max volt. ripple < 100mVrms; max. 250mA
Dimensioning: max. 1000mA/control box. Short-circuit protected
Ground for reference and controls (connected internally to frame ground through 1MΩ)
Positive or negative logic Ri = min. 5kΩ 18…30V = "1"
Digital inputs can be disconnected from ground, see chapter
6.1.2.2. Analogue output channel 1, selection 0 -20mA,
load <500 Ω Default:0-20 mA 0-10V Resolution 0.1 %, accuracy ±2 % Selection V/mA with dip-switches (see page 50)
Can be used as external power backup for the control unit (and fieldbus)
Differential receiver/transmitter Set bus termination with dip switches (see page 50)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
30
A
B
Analogue input, voltage or current
Analogue input common (cur­rent)
Analogue input, voltage or current
Analogue input common (cur­rent)
24V aux. voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Common A for DIN1-DIN6
24V aux. voltage
I/O ground
Digital input 4
Digital input 5
Digital input 6
Common A for DIN1-DIN6
Analogue signal (+output)
Analogue output common
24V auxiliary input voltage
RS485
RS485
Table 4. Technical information on basic I/O board
8
Page 74
Honeywell • 72 PRODUCT DATA
Relay board with two Type 8A/STST and one Type 8A/STDT relays.
Relay
board 1
Terminal Signal Technical information
5,5 mm isolation between channels. External interface connector See chapter 6.
21
22
Relay output 1
23
24
25
Relay output 2*
26
32
33
Relay output 3*
*
If 230VAC is used as control voltage from the output relays, the control
Switching capacity24VDC/8A 250VAC/8A
*
125VDC/0.4A Min.switching load5V/10mA
Switching capacity24VDC/8A 250VAC/8A 125VDC/0.4A Min.switching load5V/10mA
Switching capacity24VDC/8A 250VAC/8A 125VDC/0.4A Min.switching load5V/10mA
circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent welding on the relay contacts. Refer to standard EN 60204-1, section 7.2.9
Table 5. Technical information on Relay board 1
Page 75
Page 76
+RPHDQG%XLOGLQJ7HFKQRORJLHV
,QWKH86
+RQH\ZHOO
3HDFKWUHH6WUHHW1(
$WODQWD*$
FXVWRPHUKRQH\ZHOOFRP
® U.S. Registered Trademark © 2018 Honeywell International Inc. 38-00007—03 M.S. Rev. 01-18 Printed in U.S.A.
Subject to change without notice
Loading...