Honeywell S8600, S8670, S8660, S8610 User Manual

INTERMITTENT PILOT MODULES
S8600, S8610, S8660, S8670
APPLICATION
These ignition modules provide ignition sequence, flame monitoring and safety shutoff for intermittent pilot central furnaces and heating appliances. S8600 and S8660 mod­els provide up to 1.0 A pilot and 1.0 A main valve current rating. S8610 and S8670 provide up to 1.0 A pilot and 2.0 A main valve current rating. Minimum ambient temperature
IGNITER- 100
MODEL TYPE OF GAS TIMING SHUTOFF TIMING SEQUENCE
S8600A, Separate Natural None No No Spark on until pilot
S8610A lightoff or manual
S8600F, Combination shutoff; pilot valve
S8600B, Separate Natural None Yes, at 15 or 90 Spark on until
S8610B or LP lockout sec. max., lightoff or lockout;
S8600H, Combination as ordered pilot valve closes
S8610H on lockout.
S8600M Combination Natural None Yes, at 90 No, Spark and pilot gas
S8660D, Combination Natural 45 sec. Yes, at 15 or 90 Ignition trial follows
S8670D or LP lockout sec. max., prepurge; spark on
a
If established flame is lost, all models restart ignition trial.
PLANNING THE INSTALLATION
Intermittent pilot systems are used on a wide variety of central heating equipment and on heating appliances such as commercial cookers, agricultural equipment, industrial heating equipment and pool heaters. Some of these appli­cations may make heavy demands on the controls, either because of frequent cycling, or because of moisture, corro­sive chemicals, dust or excessive heat in the environment. In these situations, special steps may be required to pre­vent nuisance shutdowns and premature control failure. These applications require Honeywell Residential Division Engineering review; contact your Honeywell Sales Repre­sentative for assistance.
FREQUENT CYCLING
These controls are designed for use on space heating appliances that typically cycle 3 to 4 times an hour during the heating season and not at all during the cooling season. In an application with significantly greater cycling rates and closer to year-round use, we recommend monthly checkout because the controls may wear out more quickly.
WATER OR STEAM CLEANING
Once a module or gas control has been wet, it may operate unreliably and must be replaced. If the appliance is
SENSOR TYPE PREPURGE PERCENT LOCKOUT IGNITION
TABLE 1—INTERMITTENT PILOT IGNITION MODULES.
or LP sec. max. continuous on until shutoff.
rating is -40° F [-40° C]. Maximum ambient rating is +175° F [+79° C] for S8600, S8660 and for S8610, S8670 used with 1.0 A or less main valve. Maximum ambient rating for S8610, S8670 used with 1.0 to 2.0 A main valve is +165° F [+74° C]. See Table I for a summary of other differences between models.
shutdown.
retry After 5 min. min.
as ordered until lightoff or
likely to be cleaned with water or steam, the controls and associated wiring should be covered so water or steam flow cannot reach them. The controls should be high enough above the bottom of the cabinet so they will not be subject to flooding or splashing during normal cleaning procedures. If necessary, shield the controls to protect them from splashing water. A NEMA 4 enclosure is recommended for the ignition module; see the Electronic Ignition Service Manual, form 70-6604.
HIGH HUMIDITY OR DRIPPING WATER
Over time, dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board, causing the module to fail.
where water can drip on the controls.
In addition, high ambient humidity can cause the gas control to corrode, and finally to fail.
Where the appliance may be installed in a humid atmos­phere, make sure air circulation around the module and gas control is adequate to prevent condensation. Its also im­portant to regularly check out the system. A NEMA 4 enclosure may be needed; see the Electronic Ignition Service Manual, form 70-6604.
(6 min. nom.) delay, ignition starts again. Ignition, wait, retry repeats until pilot lights or system is shut down manually.
lockout; pilot valve closes on lockout.
Never
install an appliance
a
J.A. Form Number 69-0463 11-89 ©Honeywell Inc. 1989.
CORROSIVE CHEMICALS
Corrosive chemicals can also attack the module and gas control and eventually cause a failure. Where chemicals may be used routinely for cleaning, make sure the cleaning solution cannot reach the controls. Where chemicals are likely to be suspended in air, as in some industrial and agricultural applications, protect the ignition module from exposure with a NEMA 4 enclosure; see the Electronic Ignition Service Manual, form 70-6604.
DUST OR GREASE ACCUMULATION
Heavy accumulation of dust or grease may cause the controls to malfunction. Where dust or grease may be a problem, provide covers for the module and the gas control
that will limit environmental contamination. A NEMA 4 enclosure is recommended for the ignition module; see the Electronic Ignition Service Manual, form 70-6604.
HEAT
The controls can be damaged by excessively high temperatures. Make sure the maximum ambient tempera­ture at the control locations will not exceed the rating of the control. If the appliance normally operates at very high temperatures, insulation, shielding, and air circulation may be necessary to protect the controls. Proper insulation or shielding should be provided by the appliance manufac­turer; make sure adequate air circulation is maintained when the appliance is installed.
INSTALLATION
WHEN INSTALLING THIS IGNITION SYSTEM…
1. Read these instructions carefully. Failure to follow them could damage the components or cause a hazardous condition.
2. Check the ratings given in the instructions and on the components to make sure they are suitable for your appli­cation.
3. Installer must be a trained, experienced service tech­nician.
4. After installation is complete, check out component operation as provided in these instructions.
WARNING
FIRE OR EXPLOSION HAZARD. CAN CAUSE SERIOUS INJURY OR DEATH.
1. The ignition module can malfunction if it gets
wet, leading to accumulation of explosive gas.
Never install where water can flood, drip or condense on module.
Never try to use a module that has been wetreplace it.
2. Liquefied petroleum (LP) gas is heavier than air and will not vent upward naturally.
Do not light pilot or operate electric
switches, lights, or appliances until you are sure the appliance area is free of gas.
1. Disconnect power supply before beginning wiring to prevent electrical shock or equipment damage.
2. If a new gas control is to be installed, turn off gas supply before starting installation. Conduct Gas Leak Test according to gas control manufac­turers instructions after the gas control is in­stalled.
3. If module must be mounted near moisture or water, provide suitable waterproof enclosure.
PERFORM PREINSTALLATION SAFETY INSPECTION
The preinstallation checks described in ANSI Standard Z21.71 on page 19 module is installed. If a condition which could result in unsafe operation is detected, the appliance should be shut off and the owner advised of the unsafe condition. Any potentially unsafe condition must be corrected before pro­ceeding with the installation.
Maintenance Requirements in Severe Environments
Regular preventive maintenance is important in any application, but especially so in commercial cooking, agri­cultural, and industrial applications because:
CAUTION
must
be done before the replacement
In many such applications, particularly commercial cooking, the equipment operates 100,000-200,000 cycles per year. Such heavy cycling can wear out the gas control in one to two years. A normal forced air furnace, for which the controls were originally in­tended, typically operates less than 20,000 cycles per year.
Exposure to water, dirt, chemicals, and heat can damage the module or the gas control and shut down the control system. A NEMA 4 enclosure can reduce exposure to environmental contaminants. See Elec­tronic Ignition Service Manual, form 70-6604.
The maintenance program should include regular check-
out of the system as outlined under Checkout, page 11.
WARNING
FIRE OR EXPLOSION HAZARD MAY CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH Do not attempt to take the module apart or to clean it. Improper reassembly and cleaning may cause unreliable operation.
Maintenance frequency must be determined individually
for each application. Some considerations are:
Cycling frequency
than 20,000 times annually should be checked monthly.
Intermittent use
should be checked before shutdown and again be­fore the next use.
Consequence of unexpected shutdown
cost of an unexpected shutdown would be high, the system should be checked more often.
Dusty, wet, or corrosive environment.
environments can cause the controls to deteriorate more rapidly, the system should be checked more often.
Any control should be replaced if it does not perform properly on checkout or troubleshooting. In addition, re­place any module if it is wet or looks like it has ever been wet. Protective enclosures as outlined under Planning the Installation are recommended regardless of checkout fre­quency.
MOUNT IGNITION MODULE
Select a location close enough to the burner to allow a short (3 ft. [0.9 m] max.), direct cable route to the igniter. Ambient temperature at the module must be within the range listed under APPLICATION, page 1. The module must be protected from water, moisture, corrosive chemi­cals and excessive dust and grease.
2
. Appliances that may cycle more
. Appliances that are used seasonally
. Where the
Since these
We recommend mounting the module with the terminals down to protect them from dripping water and dust. It can also be mounted with the terminals on either side. DO NOT MOUNT with terminals pointing up. Fasten securely with four No. 6-32 machine or No. 8 sheetmetal screws.
MOUNT THE SYSTEM CONTROLS
Mount any required controls, such as the gas control, spark igniter, flame sensor, thermostat, limit and trans­former according to manufacturers instructions.
WIRE THE SYSTEM
CAUTION
1. Check the wiring diagram furnished by the appli­ance manufacturer, if available, for circuits differ­ing from the wiring hookups shown. Carefully follow any special instructions affecting the gen­eral procedures outlined below.
2. Disconnect the power supply before making wir­ing connections to prevent electrical shock or equipment damage.
1. As shown in the wiring diagrams, a common ground is required on: a. The pilot burner mounting bracket, and b. The GND(BURNER) terminal on the ignition module. Failure to use the GND(BURNER) termi­nal may result in intermittent loss of spark and/or loss of flame current sensitivity.
2. Make sure the transformer has adequate VA. The ignition module requires at least 0.2 A at 24 Vac. Add the current draws of all other devices in the control circuit, including the pilot and main valves in the gas control, and multiply by 24 to determine the total VA requirement of these components. Add this total to 4.8 VA (for the ignition module). The result is the minimum transformer VA rating. Use a Class II transformer if replacement is re­quired.
Connect Ignition Cable
Use Honeywell ignition cable or construct an ignition cable that conforms to suitable national standards such as Underwriters Laboratories Inc. See Tables 2 and 3.
TABLE 2HONEYWELL PREASSEMBLED IGNITION
CABLE PART MODULE IGNITER NUMBER LENGTH END END
394800-30 30 in. 1/4 in. quick Rajah connec-
394801-30 30 in. 1/4 in. quick Rajah connec-
TABLE 3RECOMMENDED IGNITION CABLE FOR
CABLE VOLTAGE RATING TYPE RATING (rms) C F
UL Style 3217 10,000 150 302 UL Style 3257 10,000 250 484
IMPORTANT
CABLES (UL STYLE 3257).
connect, tor receptacle,
insulated 90 deg. rubber
boot
connect, tor receptacle,
insulated straight rubber
boot
FIELD ASSEMBLY.
TEMPERATURE
Cable must be no longer than 36 in. [0.9 m]. To construct a cable, fit one end of ignition cable with 1/4 in. diameter Rajah connector receptacle and the other with a 1/4 in. female quick connect. Protect both ends with insulated boots.
NOTE: The cable must not run in continuous contact with a
metal surface or spark voltage will be greatly reduced.
Use ceramic or plastic standoff insulators as required.
To install:
1. Connect one end of the cable to the male quick
connect SPARK terminal on the ignition module.
2. Connect the other end of the cable to the igniter or
igniter-sensor stud on the pilot burner/igniter-sensor.
Connect Vent Damper
The D80B Vent Damper can be used with all ignition modules, although the Molex plug provided on some mod­ules simplifies wiring connections when used with the D80D Plug-In Vent Damper.
plug has powered a vent damper circuit, it cannot be used in a gas system without a vent damper
fuse in the module blows on initial power-up. Once this fuse has blown the module wont work unless the vent damper is connected.
To connect the plug-in model to D80D:
1. Remove the plug from the terminal strip on the ignition
module case and discard.
2. Using the wiring harness supplied, insert the matching pin plug into receptacle on case and other end to vent damper.
To connect the D80B, follow the wiring diagrams sup­plied with the vent damper or see Fig. 7 for typical connec­tions.
Connect Ignition Module
1. Connect remaining system components to the ignition module terminals as shown in the appropriate wiring dia­gram, Figs. 1 to 10.
Fig. 1 is a basic circuit for a heating only atmos­pheric burner with S8600F,H,M; S8610F,H; S8660D or S8670D.
Fig. 2 shows S8600F,H,M; S8610F,H with vent damper plug in a heating only atmospheric burner system with D80D vent damper. damper in an LP gas system or in a fan-assisted combustion system.
Figs. 3 and 4 show S8600A,B; S8610A,B with separate sensor and igniter, with and without the D80D vent damper.
Figs. 5-10 show S8600F,H,M; S8610F,H; S8660D; and S8670D in a variety of systems, with alternate connections for modules with vent damper plug. Remember, however, that a vent damper should not be used in an fan-assisted combustion system or an LP gas system and that the vent damper plug must not be removed except to connect the mod­ule to a D80D with the plug-in cable. S8600A,B; S8610A,B can be substituted in these drawings by simply connecting the igniter and sensor as shown in Figs. 3 and 4.
2. Refer to heating appliance manufacturers instruc-
tions for wiring auxiliary controls.
3. Adjust thermostat heat anticipator to match system current draw. The current draw equals the total current required for the ignition module (0.2 A) plus the gas control and any other auxiliary equipment in the control circuit.
Connect Gas Control
Use No 18 gauge solid or stranded wire. Use 1/4 in. female quick connects for module connections. Connect to gas control terminals as shown in wiring diagrams, using terminals appropriate to the gas control.
3 69-0463
Once a module with vent damper
. A non-replaceable
Never
use a vent
Ground Control System
The igniter, flame sensor and ignition module must
share a common ground with the main burner. Use thermo­plastic insulated wire with a minimum rating of 105° C [221° F] for the ground wire; asbestos insulation is not accept­able. If necessary, use a shield to protect the wire from radiant heat generated by the burner. Connect the ground wire as follows:
1. Fit one end of the ground wire with a female 1/4 in. quick-connect terminal and connect it to the male quick­connect GND(BURNER) terminal on the ignition module.
2. Strip the other end of the wire and fasten it under the igniter bracket mounting screw. If necessary, use a shield to protect the ground wire from radiant heat.
3. The burner serves as the common grounding area. If there is not good metal-to-metal contact between the burner and ground, run a lead from the burner to ground.
NOTE: Earth ground is not required.
REPLACING MODULE WITH TH-R, TH-W TERMINALS
On modules that do not have a vent damper plug, the
thermostat must be connected between the transformer
and the 24V terminal on the module. To change out a module with TH-R, TH-W terminals:
1. Remove the wires from the 25V(2) and TH-R termi­nals on the old module. Connect these two wires with a solderless connector.
2. Tag and remove the remaining wires from the old module.
3. Remove the old module and mount the new one in the same location.
4. Reconnect the remaining wires as shown in Table 4.
5. Increase the thermostat anticipator setting by 0.2 A.
TABLE 4TERMINAL CROSS REFERENCE.
TERMINAL ON TERMINAL ON OLD MODULE: NEW MODULE:
25 V (1) 24 V (GND) TH-W 24 V MV MV MV/PV MV/PV PV PV GND (Burner) GND (Burner)
S8600F,H,M; S8610F,H; S8660D; S8670D
MV MV/PV PV
PILOT COM
1ST OPERATOR
DUAL VALVE COMBINATION GAS CONTROL
2ND OPERATOR
Q345, Q346, Q348, Q362, Q381 PILOT BURNER/ IGNITER-SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM CABLE LENGTH 3 ft [0.9 m].
3
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND
4
LEG TO TRANSFORMER.
FOR MODULE WITH TH-W TERMINAL AND VENT DAMPER PLUG, CONNECT THERMOSTAT TO TH-W. LEAVE
5
24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.
MAIN VALVE
GND (BURNER)
PILOT GAS SUPPLY
24V GND
THERMOSTAT
PILOT BURNER GROUND
24V
M1175C
TH-W (OPT)
5
5
VENT DAMPER PLUG (OPT)
2
LIMIT CONTROLLER
SPARK
3
4
L1
L2
(HOT)
1
Fig. 1S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating system with an atmospheric burner.
4
S8600F,H,M; S8610F,H
MV MV/PV PV
GND (BURNER)
24V GND
24V TH-W
5
VENT DAMPER PLUG
SPARK
197516A
THERMO­STAT
LIMIT CONTROLLER
2ND OPERATOR
IGNITER
WIRING HARNESS
D80D VENT DAMPER
S8600A,B; S8610A,B
MV MV/PV PV
MAIN VALVE
PILOT GAS SUPPLY
MAIN
2ND OPERATOR
VALVE
PILOT BURNER GROUND
PILOT GAS SUPPLY
2
4
PILOT COM
1ST OPERATOR
DUAL VALVE COMBINATION GAS CONTROL
PILOT COM
1ST OPERATOR
DUAL VALVE COMBINATION GAS CONTROL
Q345, Q346, Q348, Q362, Q381 PILOT BURNER/ IGNITER-SENSOR
Fig. 2S8600F,H,M; S8610F,H with a vent damper plug in a heating system with an atmospheric burner and a D80D
vent damper.
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM CABLE LENGTH 3 ft [0.9 m].
3
4
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
5
FOR MODULE WITH TH-W TERMINAL AND VENT DAMPER PLUG, CONNECT THERMOSTAT TO TH-W. LEAVE 24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.
M1186C
L1 (HOT)
L2
SENSOR
1
GND (BURNER)
3
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
3
MAXIMUM CABLE LENGTH 3 FEET [0.9 METERS].
4
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
5
REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED; THEN MODULE WILL OPERATE ONLY WHEN VENT DAMPER IS CONNECTED.
VENT
5 TH-W (OPT)
5
THERMOSTAT
2
LIMIT CONTROLLER
DAMPER PLUG (OPT)
GROUND
24V GND
24V
4
1
L2 L1
(HOT)
SENSE
M1176D
SPARK
3
Fig. 3S8600A,B; S8610A,B connections in a heating system with an atmospheric burner.
5 69-0463
S8600A,B; S8610A,B
MV MV/PV PV
GND (BURNER)
24V GND
24V
TH-W
VENT DAMPER PLUG
5
SENSE
SPARK
3
M1177C
TH-W (OPT)
5
AIR PROVING SWITCH
VENT
5
DAMPER PLUG (OPT)
MAIN VALVE
SENSOR
PILOT GAS SUPPLY
THERMOSTAT
4
L1
L2
(HOT)
1
2
LIMIT CONTROLLER
GROUND
SPARK
3
197516A WIRING HARNESS
THERMOSTAT
2
D80D VENT DAMPER
1
4
LIMIT CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
3
MAXIMUM CABLE LENGTH 3 ft [0.9 m].
4
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
FOR MODULE WITH TH-W TERMINAL AND VENT
5
DAMPER PLUG, CONNECT THERMOSTAT TO TH-W. LEAVE 24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.
L2 L1
(HOT)
PILOT COM
2ND
1ST
OPERATOR
OPERATOR
DUAL VALVE COMBINATION GAS CONTROL
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
2
ALTERNATE LIMIT CONTROLLER LOCATION.
3
MAXIMUM CABLE LENGTH 3 FEET [0.9 METERS].
4
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
5
REMOVE PLUG ONLY IF USING VENT DAMPER.
M1185D
Fig. 4S8600A,B; S8610A,B with vent damper plug in an atmospheric burner heating system with a D80D vent
damper.
S8600F,H,M; S8610F,H; S8660D; S8670D
MV MV/PV PV
PILOT COM
2ND
1ST
OPERATOR
OPERATOR
DUAL VALVE COMBINATION GAS CONTROL
Q345, Q346, Q348, Q362, Q381 PILOT BURNER/ IGNITER-SENSOR
MAIN VALVE
GND (BURNER)
PILOT BURNER GROUND
PILOT GAS SUPPLY
24V GND
L1 (HOT)
IGNITER
24V
L2
1
COMBUSTION AIR BLOWER RELAY
COMBUSTION AIR BLOWER MOTOR
Fig. 5S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating system with power-assisted combustion.
6
Loading...
+ 14 hidden pages