Honeywell RM7890A1015, RM7890B2014, RM7890A1031, RM7890A2015, RM7890A1064 User manual

...
32-00157-03
RM7890A,B/EC7890A,B 7800 SERIES Relay Modules
INSTALLATION INSTRUCTIONS

APPLICATION

The Honeywell RM7890A,B,C/EC7890A,B Relay Modules are microprocessor based integrated burner controls for on/off automatically fired gas, oil, or combination fuel single burner applications. The RM/EC7890 Relay Module is intended to replace the RA890F,G, H Protectorelay® Primary Control. The RM/EC7890 System consists of a relay module, subbase, and amplifier. Options include: 2­line VFD (see document 65-0090) or 4-line LCD (see document 32-00110) Keyboard Display Module, and remote display mounting.
Functions the RM/EC7890 provides include automatic burner on/off sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
This document provides installation and static checkout instructions. Other applicable publications are:
Publication
No. Product
32-00110 S7800A2142 4-line LCD Keyboard Display
Module Product Data
32-0167 Q7800A/B Wiring Subbase Product Data
32-0166 204729A/C KDM NEMA4 Covers for 4-line
LCD KDM
65-0090 S7800A 2-line Keyboard Display Module
Product Data.
65-0091 S7810A Data ControlBus Module™ Product
Data.
65-0095 S7820 Remote Reset Module Product Data.
65-0097 221729C Dust Cover Packing Instructions.
65-0109 Flame Amplifiers for the 7800 SERIES
Product Data.
65-0131 221818A,C Extension Cable Assembly
Product Data.
65-0229 7800 SERIES Relay Modules Checkout and
Troubleshooting.
65-0249 S7810M ModBus Module.
This document covers the following 7800 Series Relay Modules:
1000-Series 2000-Series
• RM7890A1015 • RM7890B2014
• RM7890A1031 • RM7890A2015
• RM7890A1064 • RM7890B2030
• RM7890B1014 • RM7890A2031
• RM7890B1030 • RM7890B2055
• RM7890B1055 • RM7890A2064
• EC7890B1028

SPECIFICATIONS

Electrical Ratings (See Table 3):
Voltage and Frequency: RM7890: 120 Vac (+10/-15%), 50/60 Hz (±10%). EC7890: 220-240 Vac (+10%/-15%), 50/60 Hz (±10%).
Power Dissipation: 10W maximum. Maximum Total Connected Load: 2000 VA. Fusing Total Connected Load: 15A maximum, type SC
or equivalent, fast blow.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C). Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
SIL 3 Capable
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate Agreement.
SIL
3
EC7890B1028, RM7890A1064, RM7890B1055, RM7890A2064, or RM7890B2055 only.
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
WARNING
WARNING
Approvals:
RM7890A,B:
Underwriters Laboratories Inc. Listed: File No. MP268.
ANSI/UL 60730-2-5 / CSA C22.2 No. 60730-2-5 ­Automatic Electrical Controls for Household and Similar
Use, Part 2-5: Particular Requirements for Automatic
Electrical Burner Control Systems Factory Mutual Approved: Report No. 1V9A0.AF. CE approved - only RM7890A1064, RM7890B1055,
RM7890A2064, RM7890B2055 EAC: TC N RU д-US.Aи3O.B.04013 Federal Communications Commission: Part 15, Class B,
Emissions.
EC7890:
CE approved EAC: TC N RU д-US.Aи3O.B.04013 Federal Communications Commission: Part 15,
Class B, Emissions.
CE approvals cover: Gas Appliances Regulation: 2016/426/EU GAR Low Voltage Directive: 2014/35/EU LVD. EMC Directive: 2014/30/EU EMC (Immunity Emission
conformity can only be verified in combination with
the appliance). KIWA: certificate # 18GR0996/00, PIN 0063CT1466 Applicable Standards: EN 298:2012 Automatic burner controls EN 60335-2-102 Household and similar electrical
appliances EN 746-2 Industrial thermoprocessing - fuel handling
systems
NOTE:
RM7890A1064, RM7890B1055, RM7890A2064 and RM7890B2055
are rated cULus and CE.

INSTALLATION

Fire or Explosion Hazard. Can cause property damage, serious injury, or death.
To prevent possible hazardous burner operation, verify safety requirements each time a control is installed on a burner.
Electrical Shock Hazard. Can cause personal injury, death or equipment damage. Disconnect the power supply before beginning installation.

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
IMPORTANT
1.
Wiring connections for the relay modules are unique; refer to Fig. 2 or the appropriate Specifications for indi­vidual subbase wiring.
2. Wiring must comply with all applicable codes, ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. Loads connected to the RM/EC7890 must not exceed those listed on the RM/EC7890 label or the Specifica­tions; see Tables 3, 4, and 5.
5. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component­recognized by authorities who have proper jurisdiction.
7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two flame detectors can be connected in parallel with the following exceptions:
•C7927 Ultraviolet Detector
•C7915 Infrared Detector
9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, can cause interference with radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area can cause interference, in which case, the users, at their own expense, may be required to take whatever measures are required to correct this interference.
10.This digital apparatus does not exceed the Class B lim­its for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

Location

Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85% relative humidity continuous, noncondensing, moisture environment. Condensing moisture can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors, protect the relay module in an approved weather-tight enclosure.
32-00157-03 2
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
WARNING

Mounting Wiring Subbase

1. Mount the subbase in any position except horizon-
tally with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel.
The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for ser­vicing, installation, access or removal of the relay module, Expanded Annunciator, Keyboard Display Module, flame amplifier, flame amplifier signal volt­age probes, Run/Test Switch, electrical signal volt­age probes and electrical field connections.
3. For surface mounting, use the back of the subbase
as a template to mark the four screw locations. Drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.

Wiring Subbase

NOTE: There are several different subbase models that
can be purchased. It is important to note which subbase is compatible with the relay module when purchasing repair or replacement parts.
Series 1000 Subbase
All relay product codes that start with a 1 (example: RM7840G1 Q7800A1005/U. These relays can also be used on the Series 2000 subbase noted below.
Series 2000 Subbase
All relay product codes that start with a 2 (example: RM7840G2 Q7800A2005/U.
Subbase Compatibility
Any relay module in the 1000 series is fully backward compatible with any subbase already installed in the field (Q7800A1005/U, Q7800B1003/U, Q7800A2005/U, Q7800B2003/U).
Any relay module in the new 2000 series will only be able to be installed on subbase Q7800A2005/U, Q7800B2003/U and will not be backward compatible with any Q7800A1005/U legacy subbases already installed in the field.
IMPORTANT
014/U) can be used with existing subbase
014/U) can be used with subbase
Make sure to check the relay model number and check the subbase compatibly prior to ordering or attempting a new installation or field upgrade.
If you attempt to place a 2000 series relay on a non-compatible 1000 series subbase, you will receive an error code of 101. This indicates that you must a) change out the subbase to a Q7800A2005/U or b) choose a compatible 1000 series relay module.

Wiring

Electrical Shock Hazard. Can cause personal injury or equipment damage. Disconnect the power supply before beginning installation.
1. For proper subbase wiring and sequence chart, refer
to Fig. 2.
2. For proper remote wiring of the KDM, refer to the
Specifications for the 2-line VDF KDM (65-0090), the 4-line LCD KDM (32-00110) Data ControlBus Module™ (65-0091) or Extension Cable Assembly (65-0131).
3. Disconnect the power supply from the main discon-
nect before beginning installation to prevent electri­cal shock and equipment damage. More than one disconnect can be required.
4. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Volt­age) wiring.
5. Use recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer
wires in the same conduit with the flame detector, Data ControlBus Module™, or Remote Reset Module wiring.
b. Do not route flame detector, KDM, Data
ControlBus Module™, or Remote Reset Module leadwires in conduit with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector, KDM, Data
ControlBus Module™, or Remote Reset Module Instructions.
6. For KDM (KDM), because the KDM is powered from a
low voltage, energy limited source, it can be mounted outside of a control panel if it is protected from mechanical damage.
NOTE: Use 13 Vdc power supply any time more than one
KDM is used.
7. Use maximum wire lengths:
a. RM/EC7890 leadwires: The maximum leadwire
length is 300 feet (91 meters) to terminal inputs (Control, Running/Lockout Interlock).
b. Flame Detector leadwires: The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires: The maximum length of
wire is 1000 feet (305 meters) to a Remote Reset pushbutton.
d. Data ControlBus Module™: The maximum Data
ControlBus Module™ cable length depends on the number of system modules connected, the noise conditions and the cable used. The maximum length of all Data ControlBus Module™ interconnecting wire is 4000 feet (1219 meters).
8. For recommended wire size and type, see Table 1.
3 32-00157-03
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
9. The KDM, or Data ControlBus Module™ (for remote
mounting) must be wired in a daisy chain configuration, 1(a)-1(a), 2(b)-2(b), 3(c)-3(c). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string
termination across terminals 1 and 2 of the electrical connectors for connections over 100 feet (31 meters).
10. For recommended grounding practices, see Table 2.
11. Be sure loads do not exceed the terminal ratings.
Refer to the label on the RM/EC7890 or to the termi­nal ratings in Table 3.
require a 120 ohm (1/4 watt minimum) resistor
Table 1. Recommended Wire Sizes and Part Numbers.
Application Recommended Wire Size Recommended Part Numbers
Line Voltage Terminals
14, 16, or 18 AWG (0.75, 1.5 or 2.5 mm
2
) copper
TTW60C, THW75C, THHN90C.
conductor, 600 volt insulation, moisture-resistant wire.
Keyboard Display Module KDM
a
22 AWG (0.34 mm2) two-wire twisted pair with ground, or five-wire.
Belden 8723 shielded cable or equivalent.
Data ControlBus™ Module
Remote Reset Module
22 AWG (0.34 mm2) two-wire twisted pair, insulated
for low voltage.
Communications Interface ControlBus™ Module
13 Vdc full wave rectified transformer power input
a
The KDM, Data ControlBus™ Module (for remote mounting or communications) or Communication Interface Control-
22 AWG (0.34 mm2) two-wire twisted pair with ground.
18 AWG (0.75 mm
2
) wire insulated for voltages and
temperatures for given application.
Belden 8723 shielded cable or equivalent.
TTW60C, THW75C, THHN90C.
Bus™ Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electri­cal connectors for connections over 100 feet (30.5 meters).
Table 2. Recommended Grounding Practices.
Ground Type Recommended Practice
Earth ground (subbase and relay module).
1. Use to provide a connection between the subbase and the control panel of the equip-
ment. Earth ground must be capable of conducting enough current to blow the 15A fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length, maximum surface area ground
conductors. If a leadwire is required, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground path are free of non-
conductive coatings and protected against corrosion on mating surfaces.
Signal ground (Keyboard Display Module, Data
Use the shield of the signal wire to ground the device to the signal ground terminals—3(c)—of each device. Connect the shield at both ends of the daisy chain to earth ground.
ControlBus Module™
32-00157-03 4
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
Table 3. Terminal Ratings.
Terminal Number Description Ratings (RM7890A,B,C) Ratings (EC7890A,B)
G Flame Sensor Ground
Earth G
Earth Ground
a
——
L2(N) Line Voltage Common
3 Line Voltage Supply (L1) 120 Vac (+10%/-15%), 50 or
60 Hz (±10%).
b
220-240 Vac (=10%/-15%), 50 or 60 Hz (±10%).
4 Alarm 120 Vac, 1A pilot duty. 220-240 Vac, 1A pilot duty.
5Unused
6 Burner Controller and Limits 120 Vac, 8A run, 43A inrush. 220-240 Vac, 5A (maximum).
7Unused
8 Pilot Valve/Ignition.
9Main Fuel Valve.
10 Ignition
120 Vac.
120 Vac.
120 Vac, 4.5A ignition.
c
220-240 Vac, 4A at P.F. = 0.5, 20A inrush.
c
220-240 Vac, 4A at P.F. = 0.5, 20A inrush.
c
220-240 Vac, 4A at P.F. = 0.2.
F(11) Flame Sensor 60 to 220 Vac, current limited. 60 to 220 Vac, current limited.
12 to 21 Unused.
22 Shutter 120 Vac, 0.5A (RM7890B).
a
The RM/EC7890 must have an earth ground providing a connection between the subbase and the control panel or the
220-240 Vac (EC7890B only).
d
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event of an internal short circuit. The RM/EC7890 needs a low impedance ground connection to the equipment frame which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be made with minimum length conductors having maximum surface areas. Wide straps or brackets rather than leadwires are preferred. Be careful to verify that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and are protected against mating surface corrosion.
b
2000 VA maximum connected load to the RM/EC7890 Assembly.
c
See Tables 4 and 5 for device load combinations.
d
Requires 220-240 to 120 Vac, 10 Va minimum stepdown transformer to drive the shutter. Not applicable for C7061A1020, C7061A1079 or C7061F1003.
Table 4. Combinations for Terminals 8, 9, and 10.
Pilot Fuel 8 Main 9 Ignition 10
CFNo Load
BFNo Load
FFA
FNo LoadA
DF A
DDA
DNo LoadA
AB C D F
4.5A ignition 50 VA Pilot Duty plus 4.5A ignition.
180 VA ignition plus motor valves with: 660 VA inrush, 360 VA open, 250 VA hold.
5 32-00157-03
2A Pilot Duty. 65 VA Pilot Duty plus motor
valves with: 3850 VA inrush, 700 VA Open, 250 VA hold.
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
WARNING
CAUTION
WARNING

Final Wiring Check

1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the RM/EC7890. A separate power supply circuit can be required for the RM/EC7890. Add the required disconnect means and overload protection.
2. Check all wiring circuits and complete the Static
Checkout in Table 7 before installing the RM/EC7890 on the subbase.
3. Install the relay module.
4. Restore the panel power.

STATIC CHECKOUT

After checking all wiring, perform this checkout before installing the RM/EC7890 on the subbase. These tests verify the Q7800 Wiring Subbase is wired correctly, and the external controllers, limits, interlocks, actuators, valves, transformers, motors and other devices are operating properly.
Explosion Hazard. Can cause serious injury, death or equipment damage.
1. Close all manual fuel shutoff valve(s) before starting these tests.
2. Use extreme care while testing the system. Line voltage is present on most terminal connections when power is on.
3. Open the master switch before installing or removing a jumper on the subbase.
4. Before continuing to the next test, be sure to remove test jumper(s) used in the previous test.
5. Replace all limits and interlocks that are not operating properly. Do not bypass limits and interlocks.

Equipment Recommended

1. Voltmeter (1M ohm/volt minimum sensitivity) set on
the 0 to 300 Vac scale.
2. Two jumper wires, No. 14 wire, insulated, 12 in.
(304.8 mm) long with insulated alligator clips at both ends. Note that an ammeter can be used in place of a jumper to confirm current draw of loads. (ignition, pilot valve and main valve).

General Instructions

1. Perform all applicable tests listed in the Static
Checkout, Table 6, in the order listed.
2. Make sure all manual fuel shutoff valves are closed.
3. For each test, open the master switch and install the
jumper wires between the subbase wiring terminals listed in the Test Jumpers column.
4. Close the master switch before observing the opera-
tion.
5. Read the voltage between the subbase wiring termi-
nals listed in the Voltmeter column.
6. If there is no voltage or the operation is abnormal,
check the circuits and external devices as described in the last column.
7. Check all wiring for proper connections, tight termi-
nal screws, and appropriate wire and wiring tech­niques.
8. Replace all damaged or incorrectly sized wires.
9. Replace faulty controllers, limits, interlocks, actua-
tors, valves, transformers, motors and other devices, as required.
10. Make sure normal operation is obtained for each
required test before continuing the checkout.
11. After completing each test, be sure to remove the
test jumper(s).
Explosion Hazard. Can cause serious injury or death.
Be sure all manual fuel shutoff valves are closed.
Equipment Damage Hazard. Can cause equipment damage or equipment failure.
Do not perform a dielectric test with the RM/EC7890 installed. Internal surge protectors break down and conduct a current, causing the RM/EC7890 to fail the dielectric test or possibly destroy the internal lightning and high current protection.
32-00157-03 6
IMPORTANT
Low fuel pressure limits, if used, could be open. Bypass them with jumpers for the remaining static tests (if required).
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
CAUTION
CONFIGURATION JUMPERS
MICROCOMPUTER RESET PUSH­BUTTON
STATUS LEDs
SAFETY RELAY CIRCUIT
POWER SUPPLY
OPTIONAL KEYBOARD DISPLAY MODULE
PLUG-IN FLAME AMPLIFIER
RELAY DRIVE CIRCUIT
CONTROL POWER
TEST JACK
REMOTE RESET
DDL
DDL COMMUNICATIONS
IGNITION
PILOT
MAIN VALVE
INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS
FIELD WIRING INTERNAL WIRING
1K
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
LIMITS CONTROLLER
1K1
2K2
FLAME SIGNAL
TEST
RS485
1
2
3
L1 (HOT)
L2
N. O.
NUMBERS IN CIRCLES ARE RELAY MODULE TERMINAL NUMBERS.
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 120 VAC, 50/60 HZ (RM7890); 220-240 VAC, 50/60 HZ (EC7890) POWER SUPPLY.
EC7890 REQUIRES A 220/240 VAC TO 120 VAC, 10VA, STEPDOWN TRANSFORMER (NOT SUPPLIED) WHEN USING C7012E, F; C7061A, AND C7076A FLAME DETECTORS. NOT APPLICABLE FOR C7061A1020, C7061A1079, C7061F1003
3
6
5K1
4K1
2K1
10
8
9
4K
3K
2K
F
G
22
ALARM
3K1
4
L2
M11586A
F
RM7890C
1
2
2
1
3
3
Table 5. Sta tic C heckout.
Tes t
No. Test Jumpers Voltmeter Normal Operation
If Operation is Abnormal, Check the Items
Listed Below
1 3-L2 Line Voltage. 1. Master switch.
2. Power connected to the master switch.
3. Overload protection (fuse, circuit breaker, etc.) has not opened the power line.
2 6-L2 Line Voltage. 1. Limits.
2. Burner control.
3 3-10 Ignition spark (if ignition
transformer is connected to terminal 10).
4 3-8 1. Ignition spark (if ignition
transformer is connected to terminal 8).
2. Automatic pilot valve opens (if connected to terminal 8 or main valve if DSI application).
NOTE: Refer to wiring diagram
1. Watch for spark or listen for buzz. a. Ignition electrodes are clean b. Ignition transformer is okay.
1. Watch for spark or listen for buzz: a. Ignition electrodes are clean. b. Ignition transformer is okay.
2. Listen for click or feel head of valve for
activation:
a. Actuator, if used. b. Pilot valve.
of system being tested.
5 3-9 Automatic fuel valve(s) opens. (If
using direct spark ignition, check the second stage fuel valve(s).)
Same as test number 4. If using direct spark ignition, check the first stage fuel valve(s) instead of the pilot valve.
6 3-4 Alarm (if used) turns on. 1. Alarm.
FINAL
Equipment Damage Hazard. Can cause serious equipment damage.
After completing these tests, open the master switch, remove all test jumpers from the subbase terminals, and remove any bypass jumpers from the low fuel pressure limits to prevent equipment damage.
7 32-00157-03
Fig. 1. Internal block diagram of the RM/EC7890.
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
G
L2
3
5
6
7
8
9
10
F
(L1)
13
14
15
16
17
18
19
20
21
22
12
IGNITION
BURNER CONTROLLER/LIMITS
LINE VOLTAGE ALARM
INTERMITTENT PILOT/IGNITION
FLAME DETECTOR
120V, 50/60 HZ (RM7890) 220-240, 50/60 HZ (EC7890) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
INSTALL A LINE VOLTAGE CONTROLLER IN SERIES WITH THE LIMITS. IF USING A LOW VOLTAGE CONTROLLER IS DESIRABLE, INSTALL AN EXTERNAL RELAY WITH THE N.O. CONTACTS IN SERIES WITH THE LIMITS. THE LOW VOLTAGE RELAY COIL WILL BE IN THE LOW VOLTAGE CONTROLLER CIRCUIT. NOTE THAT IT MAY BE NECESSARY TO PROVIDE AN EXTERNAL LOW VOLTAGE TRANSFORMER.
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
TERMINAL 22 IS ONLY ON THE RM/EC7890B.
WHEN USING RM/EC7890A OR B; INSTALL AN EXTERNAL RELAY TO SWITCH THE F LEAD. THE RELAY MUST HAVE GOLD-CLAD OR GOLD-FLASH CONTACTS AND A LINE VOLTAGE COIL. POWER THE RELAY COIL FROM THE Q7800 SUBBASE TERMINAL 8. CONNECT THE RELAY CONTACTS BETWEEN THE F LEAD OF THE DETECTOR AND THE F TERMINAL OF THE Q7800 SUBBASE.
MASTER SWITCH
L1 (HOT)
L2
Q7800
4
POWER
00
LED DISPLAY
OPERATING CONTROLLER AND LIMITS
BURNER START
FLAME SIGNAL
INITIATE
ALARM
POWER
STANDBY
POWER POWER
PILOT FLAME MAIN
PFEP 4 OR 10 SEC
PILOT FLAME MAIN
POWER
RUN
STANDBY
4/10
IGNITION
INTERMITTENT PILOT
MAIN VALVE
LIMITS AND BURNER CONTROL CLOSED
9
8
10
3
6
TO
00
POWER
SAFE-
START
ALARM
S S C
SAFE START CHECK
FLAME PROVING
1
2
5
1
3
4
5
2
7
MAIN FUEL VALVE(S)
3
4
USING EC7890, A 220-240 VAC TO 120 VAC, 10 VA MINIMUM STEP-DOWN TRANSFORMER (NOT PROVIDED) MUST BE USED TO DRIVE THE SHUTTER (C7012E,F; C7061; C7076A,D DETECTORS). NOT APPLICABLE FOR C7061A1020, C7061A1079, C7061F1003
SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING.
RM7890A1031 PFEP IS 30 SECONDS FIXED. RM7890B1030 PFEP IS 10 SECONDS FIXED.
MAIN FUEL VALVE IS ENERGIZED AND IGNITION (TERMINAL 10) IS TURNED OFF DURING PFEP ONCE FLAME IS PROVEN.
POWER PILOT FLAME MAIN ALARM
MFEP
20
6
6
FOR DIRECT SPART IGNITION (OIL OR GAS)
8
9
10
IGNITION TRANSFORMER
MAIN VALVE
L2
9
9
7
8
9
EXCEPTIONS: RM7890A1031/A2031 HAS A FIXED 30 SECOND PFEP RM7890A1031/A2031 HAS A FIXED 30 SECOND PFEP RM7890B1030/B2030 HAS A FIXED 10 SECOND PFEP RM7890A1064/A2064, RM7890B1055/B2055 AND EC7890B1028/B202 JR1 INTACT – 10 SECOND FIXED PFEP, IGNITION (TERMINAL 10) SHUTS OFF AT 6 SECONDS. JR1 CLIPPED – 4 SECONDS FIXED PFEP, IGNITION (TERMINAL 10) SHUTS OFF AT 2 SECONDS.
8
Fig. 2. Wiring subbase and operating sequence chart for RM/EC7890.
32-00157-03 8
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES

Mounting RM/EC7890 Relay Module

1. Mount the RM/EC7890 vertically on the Q7800
Subbase, or mount horizontally with the knife blade terminals pointing down. When mounted on the Q7800A, the RM/EC7890 must be in an electrical enclosure.
2. When mounting in an electrical enclosure, provide
adequate clearance for servicing, installation and removal of the RM/EC7890, KDM, flame amplifier, flame amplifier signal voltage probes, electrical signal voltage probes, and electrical connections. a. Allow an additional two inches (51 mm) below
the RM/EC7890 for flame amplifier mounting.
b. Allow an optional three-inch (76 mm) minimum
to both sides of the RM/EC7890 for electrical signal voltage probes.
RELAY MODULE
WIRING SUBBASE
3. Make sure no subbase wiring is projecting beyond
the terminal blocks. Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts.
IMPORTANT
Install the RM/EC7890 with a plug-in motion rather than a hinge action.
4. Mount the RM/EC7890 by aligning the four L-
shaped corner guides and knife blade terminals with the bifurcated contacts on the wiring subbase and securely tightening the two screws without deforming the plastic.

Mounting Other System Components (Fig. 3)

Refer to the applicable specifications for mounting other system components.
Q7800B2003/U SUBBASE SHOWN
HONEYWELL
DUST COVER
RESET BUTTON
SEQUENCE STATUS LED PANEL
CONFIGURATION JUMPERS
B
URNE
R
CONTROL
POWER
PIL
OT
MAIN
F
L
AME
AL
A
R
RE
S
M
E
T
CAPTIVE MOUNTING SCREW
FLAME AMPLIFIER
Fig. 3. RM/EC7890 Relay Module exploded view.
9 32-00157-03
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES

PRINCIPAL TECHNICAL FEATURES

The RM/EC7890 provides all customary flame safeguard functions as well as significant advancements in safety, annunciation, and system diagnostics.
Safety Shutdown (Lockout) Occurs if:
1. INITIATE PERIOD
a. AC line power errors occurred, see Operation. b. Configuration jumpers have been changed (after
200 hours).
c. Four minute INITIATE period has been exceeded.
2. STANDBY PERIOD
a. Flame signal is present after 240 seconds. b. Ignition/intermittent pilot valve terminal is ener-
gized. c. Internal system fault occurred. d. Main valve terminal is energized. e. 3.0 second (2.0 seconds for RM7890A1064/A2064,
RM7890B1055/B2055 and
EC7890B1028/B2028) Flame Failure Response
Time (FFRT) Amplifier is installed and configuration
jumper is selected for relight (see Table 3).
3. SAFE START CHECK
a. Ignition/intermittent pilot valve terminal is ener-
gized. b. Internal system fault occurred. c. Main valve terminal is energized.
4. PILOT FLAME ESTABLISHING PERIOD (PFEP)
a. Ignition/intermittent pilot valve terminal is not
energized. b. Internal system fault occurred. c. Main valve terminal is energized. d. No flame present at end of PFEP.
5. RUN PERIOD
a. Ignition terminal is energized. b. Internal system fault occurred. c. Main valve terminal is not energized. d. No flame present and configuration jumper is
selected for lockout. e. Pilot valve terminal is not energized.

OPERATION

Sequence of Operation

The RM/EC7890 has the operating sequences listed below; see Fig. 2. The RM/EC7890 LED provide positive visual indication of the program sequence: POWER, PILOT, FLAME, MAIN and ALARM.
Initiate
The RM/EC7890 enters the INITIATE sequence when the relay module is powered. The RM/EC7890 can also enter the INITIATE sequence if the relay module verifies voltage fluctuations of +10/-15% or frequency fluctuations of ±10% during any part of the operating sequence. The INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met. When the tolerances are not met, a hold condition is initiated and is displayed on the optional KDM for at least five seconds.
When the tolerances are met, the INITIATE sequence restarts. If the condition is not corrected and the hold condition exists for four minutes, the RM/EC7890 locks out. Causes for hold conditions in the INITIATE sequence:
a. AC line dropout detection. b. AC line noise that can prevent a sufficient read-
ing of the line voltage inputs.
c. Brownouts caused by a low line voltage.
NOTE: If a 3.0 second flame failure response amplifier is
installed (2.0 seconds for RM7890A1064/A2064, RM7890B1055/B2055 and EC7890B1028/B2028) and configuration jumper JR2 is intact, the RM/EC7890 locks out. JR2 must be clipped.
Standby
The RM/EC7890 is ready to start an operating sequence when the operating control input (terminal 6) recognizes a call for heat. The burner switch, limits, operating limit control and all microcomputer monitored circuits must be in the correct state for the RM/EC7890 to continue into the Safe Start Check.
Normal Start-Up Safe Start Check
The RM/EC7890 verifies that a flame or flame simulating condition does not exist and proceeds into the Ignition Trial. If a flame or flame simulating condition is present, the RM/EC7890 remains in the STANDBY period.
Ignition Trials
a. Pilot Flame Establishing Period (PFEP):
(1) The pilot valve and ignition transformer, ter-
minals 8 and 10, are energized. The RM/EC7890 has an intermittent pilot valve, terminal 8.
(2) Flame must be proven by the end of the four-
or ten-second PFEP (30 seconds for RM7890A1031/A2031) or a safety shutdown occurs.
(3) Once flame is proven, the ignition, terminal
10, is de-energized and the main valve, termi­nal 9, is energized. (a)The RM7890B1030/B2030 finishes the 4-
or 10-second PFEP before the main valve is energized.
(b)The RM7890A1064/A2064 and
RM7890B1055/B2055 with JR1 intact completes 10 second PFEP, shutting off ignition (Terminal 10) at 6 seconds. When the JR1 clipped these devices complete a 4 second PFEP, shutting off ignition (termi­nal 10) at 2 seconds.
Run
The RM/EC7890 is now in RUN and remains in RUN until the controller input, terminal 6, opens, indicating that the demand is satisfied or a limit has opened.
32-00157-03 10
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
SELECTABLE CONFIGURATION JUMPERS
1 2
1
2
JR2 REMOVED FROM RM7890C.
RM7890A1031/A2031 PFEP IS FIXED AT 30 SECONDS, IF JR1 IS INTACT OR CLIPPED.
M11589A

SETTINGS AND ADJUSTMENTS

Selectable Site-Configurable Jumpers

The RM/EC7890 has two site-configurable jumper options, see Fig. 4 and Table 7. If necessary, clip the site­configurable jumpers with side cutters and remove the resistors from the relay module.
Table 6. Site-Configurable Jumper Options.
Jumper
Number Description Intact Clipped
Pilot Flame Establishing Period
a
JR1
(PFEP)
JR2 Flame Failure Action
a
Not Applicable for RM7890A1031/A2031 (30 second
10 seconds
Relight
c
b
4 seconds
Lockout
PFEP). JR1 removed.
b
30 seconds for RM7890A1031/A2031.
c
The Relight feature (JR2 intact) requires a 0.8 second FFRT Flame Amplifier. The EC/RM7890 locks out and indicates a Fault 46 if a 3.0 second (2.0 second for RM7890A1031/B2031, RM7890B1055/B2055 and EC7890B1028/B2028) FFRT is used and jumper JR2 is not clipped and removed.
d
Clipping and removing a site-configurable jumper after 200 hours of operation results in a hard lockout, code
110.
e
For RM7890A1064/B2064, RM7890B1055/B2055 and
EC7890B1028/B2028: Intact—Fixed 10 seconds PFEP , Ignition (terminal 10) shuts off at 6 seconds. Clipped—Fixed 4 seconds PFEP, Ignition (terminal 10) shuts off at 2 seconds.
d
b
Fig. 4. Selectable site-configurable jumpers.
SERVICE NOTE Clipping and removing a site-configurable jumper enhances the level of safety. If using three-second amplifier, site-configurable jumper JR2 must be clipped and removed. If not removed, an F46 Lockout occurs.

SAFETY AND SECURITY

Physical device protection

Device shall be accessible to authorized personnel only – Installation on publicly accessible places is not recommended as this could lead to unwanted and potentially unsafe changes to device (wiring, configuration, etc).
It is recommended to lock the device in an enclosed cabinet with access allowed only to approved and trained personnel. Also, it is strongly advised to keep all the wiring of device physically secure.
Physical protection of the device is applied via Run/Test switch label/seal. It is intended to prevent and detect unauthorized access.

Modbus & DDL Interface security

Any conducts critical to device functionality (DDL, Modbus lines etc.) shall be physically protected (installed outside public access) since they could be damaged or tampered-with by unauthorized people, either accidentally or for purpose.
Modbus RS-485 & DDL protocols do not support security features. For DDL interface - only DDL devices shall be connected to the Burner Controller DDL line.

License agreement

Copying and reverse engineering is prohibited by the law.
11 32-00157-03
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
For More Information
The Honeywell Thermal Solutions family of products includes
Honeywell Combustion Safety, Eclipse, Exothermics, Hauck,
Kromschröder and Maxon. To learn more about our products,
visit ThermalSolutions.honeywell.com or contact your
Honeywell Sales Engineer.
Honeywell Process Solutions
Honeywell Thermal Solutions (HTS)
1250 West Sam Houston Parkway
South Houston, TX 77042
ThermalSolutions.honeywell.com
® U.S. Registered Trademark © 2020 Honeywell International Inc. 32-00157-03 M.S. 04-20 Printed in United States
Loading...