Honeywell RM7838B, RM7838C Installation Instructions Manual

SIL
3
Capable
RM7838B,C
maxon.su
INSTALLATION INSTRUCTIONS

APPLICATION

The Honeywell RM7838B,C is a microprocessor based integrated burner control for industrial process modulating semiautomatically fired gas, oil, coal or combination fuel single burner applications. The RM7838B,C System consists of a relay module, wiring subbase, keyboard display module (KDM), amplifier, and purge card. Options include Data ControlBus Module™, remote display mounting, and first-out expanded annunciator.
Functions provided by the RM7838B,C include automatic modulated High Fire and Low Fire proven Purge, burner pilot startup with pilot valve hold, a special pilot valve hold from the Run condition, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
The RM7838C differs from the RM7838B as follows:
1. Alarms only on Safety Shutdown.
2. Requires ST7800C Purge Timer.
3. C1004 has 15 second MFEP. C1020 has 5 second
MFEP. This document provides installation and static checkout instructions. Other applicable publications are:
65-0084: Q7800A,B 22-Terminal Wiring Subbase
Product Data.
65-0089: ST7800A,C Plug-In Purge Timer
Installation Instructions.
65-0090: S7800A Keyboard Display Module
Product Data.
65-0101: S7830 Expanded Annunciator Product
Data.
65-0109: R7824, R7847, R7848, R7849, R7851,
R7852, R7861, R7886 Flame Amplifiers for the 7800 Series Product Data.
65-0131: 221818A Extension Cable Assembly
Product Data.
65-0229: 7800 Series Relay Modules Checkout and
Troubleshooting Product Data.
65-0249: S7810M ModBus™ Module Product Data.

SPECIFICATIONS

Electrical Ratings (See Table 4):
Voltage and Frequency: 120 Vac (+10/-15%),
50/60 Hz (±10%).
Power Dissipation: RM7838B,C: 10W maximum. Maximum Total Connected Load: 2000 VA. Fusing Total Connected Load: 15A maximum, type SC or
equivalent, fast blow.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C). Humidity: 85% relative humidity continuous, noncondensing. Vibration: 0.5G environment.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate Agree-
ment.
Approvals:
Underwriters Laboratories Inc. Listed: File No. MP268, Guide
No. MCCZ. Canadian Standards Association Certified: LR9S329-3. Factory Mutual Approved: Report No. 1V9A0.AF. Swiss Re (formerly Industrial Risk Insurers): Acceptable. Federal Communications Commission: Part 15, Class B,
Emissions. Gastec: EN298, Report 115679/4 (RM7838C1020 only)
IMPORTANT
A Flame Detection System is required for operation and must be ordered separately. Select the applicable Flame Signal Amplifier and matching Flame Detector in form 65-0109.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safeguard service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
RM7838C1020 only
66-1094-08
RM7838B,C 7800 SERIES RELAY MODULE
WARNING
WARNING
WARNING
maxon.su
Explosion or Fire Hazard. Can cause severe personal injury, death or property damage.
To prevent possible hazardous burner operation, verify safety requirements each time a control is installed on a burner.
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect the power supply before beginning installation. More than one power supply disconnect can be required.

Location

Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85% relative humidity continuous, noncondensing, moisture environment. Condensing moisture can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors, protect the relay module in an approved weather-tight enclosure.

Mounting Wiring Subbase

1. Mount the subbase in any position except horizontally
with the bifurcated contacts pointing down. The standard vertical position is recommended; any other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel. The Q7800 can be mounted directly in the control cabinet; be sure to allow adequate clearance for service, installation, access or removal of the RM7838B,C, Expanded Annunciator, KDM, flame amplifier, flame amplifier signal voltage probes, Run/Test Switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark the four screw locations; then drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
IMPORTANT
1. Wiring connections for the relay modules are unique; refer to Fig. 2 and 3 or the appropriate Specifications for proper subbase wiring.
2. Wiring must comply with all applicable codes, ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. Loads connected to the RM7838B,C must not exceed those listed on the RM7838B,C label or the Specifications; see Table 4.
5. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component recognized by authorities who have proper jurisdiction.
7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two Flame Detectors can be connected in parallel with the exception of Infrared Flame Detectors (C7015 and C7915), UV Flame Detectors C7927, and C7961 and visible light detector C7962.
9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, can cause interference with radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area can cause interference; in which case, the users, at their own expense, may be required to take whatever measures are required to correct this interference.
10. This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
See Fig. 1 for the internal block diagram of the RM7838B,C Relay Module.

Wiring Subbase

Electrical Shock Hazard. Can cause serious personal injury, death or equipment damage.
Disconnect the power supply before beginning installation. More than one power supply disconnect may be required.
1. Refer to Fig. 2 or 3 for proper subbase wiring.
2. For proper remote wiring of the KDM, refer to the KDM
Specifications (65-0090), Data ControlBus Module™ (65-0091) or Extension Cable Assembly (65-0131).
3. Make sure all wiring complies with all applicable electrical codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Voltage) wiring.
66-1094—08 2
4. See Table 1 for recommended wire size and type.
maxon.su
RM7838B,C 7800 SERIES RELAY MODULE
4
DDL COMMUNICATIONS
RECIRCULATING AFS
LOCKOUT INTERLOCKS AND COMBUSTION AIR BLOWER SWITCHES
PILOT VALVE HOLD SWITCH
LOW START SWITCH
HIGH PURGE RATE SWITCH
PREIGNITION INTERLOCK
BURNER CONTROL
RUN/TEST SWITCH
RESET PUSHBUTTON
STATUS LED
KEYBOARD
DDL
MANUAL VALVE OPEN SWITCH
DISPLAY MODULE
LIMITS
START SWITCH
RS485
1
2
3
STOP SWITCH
1/2 OF DPST ALARM SILENCING SWITCH
16
17
18
19
20
21
L1 (HOT) L2
CONFIGURATION JUMPERS
SAFETY RELAY CIRCUIT
REMOTE RESET
1
120 Vac
50/60 HZ
RECIRCULATING BLOWER
MICROCOMPUTER
RELAY DRIVE CIRCUIT
6
7
2
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLT INPUTS
FIELD WIRING INTERNAL WIRING
PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
2
NOT REQUIRED FOR RM7838C.
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
2K
3K
4K
5K
7K
1K
POWER SUPPLY
6K1
1K1 2K1 5K1
4K1
2K2
3K1
TEST
PLUG-IN FLAME AMPLIFIER
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
CONTROL POWER
5
10
8
9
3
1/2 OF DPST ALARM SILENCING SWITCH
8K1
8K2
9K2
TEST JACK
F
G
22
COMBUSTION AIR BLOWER
IGNITION
PILOT
MAIN VALVE
ALARM
2
HIGH PURGE
COMMON
MODULATE
9K1
LOW FIRE
M5195D
L2
12
13
15
14
Fig. 1. Internal block diagram of RM7838B,C (see Fig. 2 for RM7838C1020); see Fig. 3 and 4 for detailed wiring
instructions.
3 66-1094—08
RM7838B,C 7800 SERIES RELAY MODULE
L1 HOT
N
1
4
2
19
CONFIGURATION JUMPERS
PLUG-IN PURGE TIMER CARD
F
G
22
PLUG -IN
FLAM E
A M P L IF IE R
PLUG-IN FLAME AMPLIFIER
MICROCOMPUTER
RUN/TEST SWITCH
RESET PUSHBUTTON
FLAM E SIGNAL
TEST JACK
RELAY DRIVE CIRCUIT
1K
2K
3K
4K
5K
6K
7K
8K
9K
CONTROL POWER
POWER SUPPLY
18
20
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
10
8
9
5
3
OPTIONAL KEYBOARD DISPLAY MODULE
RS485
16
1K
2K2 5K1
4K1
2K1
PV1
MV
3K1
6K1
21
LFS
HFS
PII
3K2
SAFETY RELAY CIRCUIT
7
COMBUSTION BLOWER
AL
IGN
AL
DDL
13
15
14
12
HIGH FIRE
COMMON
LOW FIRE
MODULATE
REMOTE RESET
8K1
8K2
9K2
9K1
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLTAGE INPUTS
RELAY CONTACT OPEN
INTERNAL WIRING
FIELD WIRING
RELAY COIL
RELAY CONTACT CLOSED
DDL COMMUNICATIONS
1
2
3
5
USER TERMINALS
1
120 VAC, 50/60 Hz POWER SUPPLY.
M13959
STATUS LEDS
SHUTTER
FG
...
22
COMBUSTION BLOWER AFS
START
6
RECIRCULATING BLOWER AFS
RECIRCULATING BLOWER
L2
STOP
BURNER CONTROL
maxon.su
Fig. 2. Internal block diagram of RM7838C1020 (see Fig. 5 for detailed wiring instructions).
66-1094—08 4
RM7838B,C 7800 SERIES RELAY MODULE
maxon.su
Table 1. Recommended Wire Sizes and Part Numbers.
Application Recommended Wire Size Recommended Part Numbers
Line voltage terminals 14, 16 or 18 AWG copper conductor, 600 volt
KDM 22 AWG two-wire twisted pair with ground, or five-wire. Belden 8723 shielded cable or equivalent.
Data ControlBus Module™ 22 AWG two-wire twisted pair with ground, or five-wire. Belden 8723 shielded cable or equivalent.
Remote Reset Module 22 AWG two-wire twisted pair, insulated for low voltage. —
13 Vdc full wave rectified transformer power input.
Ground Type Recommended Practice
Earth Ground (Subbase and relay module)
Signal Ground (KDM, Data ControlBus Module™
insulation, moisture-resistant wire.
18 AWG wire insulated for voltages and temperatures for given application.
Table 2. Recommended Grounding Practices.
1. Use to provide a connection between the subbase and the control panel of the
equipment. Earth ground must be capable of conducting enough current to blow the 15A fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length, maximum surface area ground conductors. If a lead wire must be used, use 14 AWG copper wire.
3. Make sure that mechanically-tightened joints along the ground path are free of nonconductive coatings and protected against corrosion on mating surfaces.
Use the shield of the signal wire to ground the device to the signal ground terminal 3(c) of each device. Connect the shield at both ends of the daisy chain to earth ground.
TTW60C, THW75C, THHN90C.
TTW60C, THW75C, THHN90C.
The KDM and Data ControlBus™ Module (for remote mounting or communications) must be wired in a daisy chain configuration, 1(a)-1(a), 2(b)-2(b), 3(c)-3(c). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors, for connections over 100 feet (31 meters).
4. See Table 2 for recommended grounding practices.
5. Use recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer wires in
the same conduit with the flame detector, Data ControlBus Module™, or Remote Reset Module wiring.
b. Do not route flame detector, Data ControlBus
Module™, or Remote Reset Module leadwires in conduit with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector, Data ControlBus
Module™, or Remote Reset Module Instructions.
6. KDM: Because the KDM is powered from a low voltage, energy limited source, mount it outside of a control panel if it can be protected from mechanical damage.
NOTE: Use a separate 13 Vdc power supply any time more
than two Data ControlBus Modules™ or KDM are used or are placed more than 100 feet (31 meters) from the relay module.
7. Use maximum wire lengths: a. RM7838B,C leadwires—300 feet (91 meters) to
terminal inputs (Control, Preignition Interlock, Running/Lockout Interlock, High Purge Switch and Low Fire Switch).
b. Flame Detector leadwires—limited by the flame
signal strength.
c. Remote Reset leadwires—1000 feet (305 meters) to
a Remote Reset push button.
d. Data ControlBus™ Module—depends on the
number of system modules connected, the noise conditions and the cable used. The maximum length of all Data ControlBus™ Module interconnecting wire is 4000 feet (1219 meters).
8. Make sure loads do not exceed the terminal ratings. Refer to the label on the RM7838B,C or to the ratings in Table 4.

FINAL WIRING CHECK

1. Check the power supply circuit. The voltage and fre-
quency tolerance must match those of the RM7838B,C. (A separate power supply may be required for the RM7838B,C.)
2. Add the required disconnect means and overload protection.
3. Check all wiring circuits and complete the static checkout in Table 3 before installing the RM7838B,C on the subbase.
4. Install the relay module.
5. Restore power to the panel.

STATIC CHECKOUT

After checking all wiring, perform this checkout before installing the RM7838B,C on the subbase. These tests verify the Q7800 Wiring Subbase is wired correctly, and the external controllers, limits, interlocks, actuators, valves, transformers, motors and other devices are operating properly.
5 66-1094—08
RM7838B,C 7800 SERIES RELAY MODULE
WARNING
CAUTION
WARNING
maxon.su
Explosion and Electrical Shock Hazards. Can cause serious injury, death or equipment damage.
Close all manual fuel shutoff valve(s) before starting these tests. Use extreme care while testing the system. Line voltage is present on most terminal connections when power is on.
Open the master switch before installing or removing a jumper on the subbase. Before continuing to the next test, be sure to remove test jumper(s) used in the previous test. Replace all limits and interlocks that are not operating properly. Do not bypass limits and interlocks.
Electrical Hazard. Can cause equipment damage.
Do not perform a dielectric test with the RM7838B,C installed. Internal surge protectors break down and conduct current, causing dielectric test failure and destruction of the internal lightning and high current protection.

General Instructions

1. Perform all applicable tests listed in the Static Checkout,
Table 3, in the order listed.
2. Make sure all manual fuel shutoff valve(s) are closed.
3. Perform only those tests designated for the specific
RM7838B,C model being tested.
4. Raise the setpoint of the operating controller to simulate a call for heat.
5. For each test, open the master switch and install the jumper wires between the subbase wiring terminals listed in the Test Jumpers column.
6. Close the master switch before observing operation.
7. Read the voltage between the subbase wiring terminals
listed in the Voltmeter column.
8. If there is no voltage or the operation is abnormal, check the circuits and external devices as described in the last column.
9. Check all wiring for correct connections, tight terminal screws, correct wire, and proper wiring techniques. Replace all damaged or incorrectly sized wires.
10. Replace faulty controllers, limits, interlocks, actuators, valves, transformers, motors and other devices, as required.
11. Make sure normal operation is obtained for each required test before continuing the checkout.
12. After completing each test, be sure to remove the test jumper(s).

Equipment Recommended

Voltmeter (1M ohm/volt minimum sensitivity) set on the 0-300 Vac scale and two jumper wires; using No. 14 wire, insulated, 12 in. (304.8 mm) long with insulated alligator clips at both ends. An ammeter to test the load current can replace one of the recommended jumpers in tests verifying the combustion blower motor, ignition, pilot and main valve operation.
Table 3. Static Checkout.
Test
No.
1 None 4-L2 Line voltage at terminal 4. 1. Master Switch.
2 None 6-L2 Close burner control.
2a None 4-20 Line voltage at terminal 20. Preignition Interlock. 2b None
2c None
Test
Jumpers Voltmeter Normal Operation
Recirculating exhaust blower fan starts, then line voltage at terminal 6.
4-16 Line voltage at terminal 16. Pilot Valve Hold. Close Pilot Val ve Hold
4-17 Line voltage at terminal 17. Manual Open Valve Switch. Close Manual Open Val ve Switch
Explosion Hazard. Can cause serious injury or death.
Make sure all manual fuel shutoff valves are closed.
If Operation is Abnormal, Check These
2. Power Connected to the Master
Switch.
3. Overload protection (fuse, circuit breaker, etc) has not opened the power line.
1. Recirculating/exhaust blower fan.
2. Limits.
3. Stop Switch.
4. Burner Control.
5. Recirculating AFS.
NOTE: C1020 does not have Pilot Valve
Hold.
NOTE: C1020 does not have MOV.
Items
66-1094—08 6
Loading...
+ 14 hidden pages