Honeywell EC7850A1072, EC7850A1080, EC7850A1122, RM7830A1029, RM7830A1003 Instruction Manual

...
EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES Relay Modules
INSTALLATION INSTRUCTIONS
The Honeywell EC/RM7830A and EC/RM7850A are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single burner full modulation (EC/RM7850A) or on/off (EC/RM7830A) applications. The EC/RM7830A; EC/RM7850A system consists of a relay module, subbase, amplifier, and purge card. Options include keyboard display module (KDM), Personal Computer Interface, Data ControlBus™ Module, remote display mounting and Combustion System Manager Software.
Functions provided by the EC/RM7830A and EC/RM7850A include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. Text readout on the Keyboard Display Module is available in English, Spanish, Portuguese, Katakana (Japanese), French, German, and Italian languages.
This document provides installation and static checkout instructions. Other applicable publications are: 63-2278:Q7700 Network Interface Unit Product Data.
65-0084:Q7800A,B 22-Terminal Wiring Subbase
Product Data.
65-0090:S7800A Keyboard Display Module Product Data.
65-0091:S7810A Data ControlBus™ Module Product Data.
65-0095:S7820 Remote Reset Module Product Data.
65-0097:221729C Dust Cover Packing Instructions.
65-0102:ZM7850A Combustion System Manager
Operating Instructions.
65-0109:R7824, R7847, R7848, R7849, R7861, R7886 Flame
Amplifiers for the 7800 SERIES Product Data.
65-0131:221818A Extension Cable Assembly Product Data.
65-0228:S7810B Multi-Drop Switch Module Product Data.
65-0229:7800 SERIES Relay Modules Checkout and
Troubleshooting Product Data.
65-0249:S7810M ModBus Network Protocol.
®
®
SPECIFICATIONS
Electrical Ratings (See Tables 3A, 3B, 3C and 3D):
Voltage and Frequency:
RM7830A and RM7850A:
120 Vac (+10/-15%), 50/60 Hz (±10%).
EC7830A and EC7850A:
220/240 Vac (+10%/-15%), 50/60 Hz (±10%) Power Dissipation: 10W maximum. Maximum Total Connected Load: 2000 VA. Fusing Total Connected Load: 15A maximum, Fast Blow, type
SC or equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C). Humidity: 85% relative humidity continuous, noncondensing. Vibration: 0.5G environment.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form 65-0312 for Certificate Agreement
Approvals:
RM7830A and RM7850A:
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
Swiss Re (formerly Industrial Risk Insurers): Acceptable.
Federal Communications Commission: Part 15,
Class B, Emissions. EC7830A and EC7850A: Factory Mutual Approved. These products also comply with the following European
directives: Gas Appliance Directive: 90/396/EEC. Low Voltage Directive: 73/23/EEC. EMC Directive: 89/336/EEC. GASTEC: CE-63AP3070/1. Lloyds Register Approval.
Oil appliances:
EC7830A: DIN-5F 106/96.
EC7850A: DIN-5F 107/96. These products are approved according to EN298, “Automatic gas burner systems for gas burners and gas burning appliances with or without fans.”
Please note the following to comply with EN60730 for remote mounting of the KDM and/or remote reset module. It is necessary to provide electrical separation using insulation at
SIL
Capable
3
66-1092-06
EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES
WARNING
WARNING
least equivalent to double or reinforced insulation. This can be accomplished by either:
1. Optically isolating the communication and/or remote reset lines from the control cabinet or
2. Providing physical separation from the communication and/or remote reset lines using electrical conduit and a 204718A Remote Display Cover Assembly or other suitable enclosure that meets ip40 class of protection.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safeguard service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Carefully follow safety requirements when installing a burner control.
Electrical Shock Hazard or Equipment Damage Hazard. Can cause severe injury, death or equipment damage.
Disconnect power supply before beginning installation. More than one disconnect may be involved.
Location
Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85% relative humidity continuous, noncondensing, moisture environment. Condensing moisture can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors, protect the relay module in an approved weather-tight enclosure.
IMPORTANT
1. Wiring connections for the relay modules are unique;
refer to Fig. 3 and 4 or the appropriate Specifications for individual subbase wiring.
2. Wiring must comply with all applicable codes, ordi­nances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. Loads connected to the EC/RM7830A and EC/RM7850A must not exceed those listed on the relay module label or the Specifications; see Table 1.
5. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component-recognized by authorities who have proper jurisdiction.
7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two flame detectors can be connected in parallel with the exception of C7015 Infrared Flame Detectors.
9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, can cause interference with radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area can cause interference, in which case, the users, at their own expense, may be required to take whatever measures are required to correct this interference.
10. This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Mounting Wiring Subbase
1. Mount the subbase in any position except horizontally
with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel. The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for service, installation, access or removal of the relay module, expanded annunciator, KDM, flame amplifier, flame amplifier signal voltage probes, run/test switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark the four screw locations, then drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws (not provided).
66-1092—06 2
EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES
WARNING
Wiring Subbase
Electrical Shock Hazard or Equipment Damage Hazard. Can cause sever injury, death or equipment damage.
Disconnect the power supply before beginning installation. More than one disconnect may be involved.
The internal block diagram of the EC/RM7830A is shown in Fig. 1 and the internal block diagram of the EC/RM7850A is shown in Fig. 2.
1. For subbase wiring and sequence charts, refer to Fig. 3 and 4.
2. For remote wiring of the KDM, refer to the Specifications for the KDM (65-0090), Network Interface Unit (63-2278), Data ControlBus™ Module (65-0091), S7810M ModBus Module (65-0249) or Extension Cable Assembly (65-0131).
3. Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect can be required.
4. All wiring must comply with all applicable electrical codes, ordinances and regulations. Wiring, where required, must comply with NEC Class 1 (Line Voltage) wiring.
5. For recommended wire size and type, see Table 1.
6. Recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer wires in
the same conduit with the flame detector, Data ControlBus™ Module, or Remote Reset Module wiring.
b. Do not route flame detector, Data ControlBus™
Module, or Remote Reset Module leadwires in conduit with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector, Data Control-
Bus™ Module, or Remote Reset Module Instruc­tions.
7. For recommended grounding practices, see Table 2.
8. The KDM is powered from a low voltage, energy limited
source. Mount the KDM outside of a control panel when it is protected from mechanical damage.
IMPORTANT
A 13 Vdc power supply must be used any time more than one KDM is used. A maximum of two KDM, Data ControlBus™ Modules or S7810B Multi-Drop Switch Modules are allowed in any combination.
9. Maximum wire lengths: a. EC/RM7830A and EC/RM7850A leadwires: The
maximum leadwire length is 300 feet (91 meters) to terminal inputs (Control, Running/Lockout Interlock).
b. Flame Detector leadwires: The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires: The maximum length of
wire is 1000 feet (305 meters) to a Remote Reset pushbutton.
d. Data ControlBus™ Module: The maximum Data
ControlBus™ Module cable length depends on the number of system modules connected, the noise conditions and the cable used. The maximum length of all Data ControlBus™ Module interconnecting wire is 4000 feet (1219 meters).
10. Be sure loads do not exceed the terminal ratings. Refer to the label on the relay module or to the terminal ratings in Tables 3A, 3B, 3C and 3D.
3 66-1092—06
EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES
L1 HOT
N
1
5
2
CONFIGURATION JUMPERS
PLUG-IN PURGE TIMER CARD
F
G
22
PLUG-IN FLAME AMPLIFIER
MICROCOMPUTER
RUN/TEST SWITCH
RESET PUSHBUTTON
FLAME SIGNAL
TEST JACK
RELAY DRIVE CIRCUIT
1K
2K
3K 4K
5K
6K 7K
CONTROL POWER
POWER SUPPLY
17
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
10
8
21
9
4
3
OPTIONAL KEYBOARD DISPLAY MODULE
RS485
16
1K1
2K2 5K1
4K1
7K1
2K1
PV1
PV2
MV
3K1
6K1
7
ES2
3K2
SAFETY RELAY CIRCUIT
20 6
FAN
AL
IGN
AL
DDL
REMOTE RESET
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLTAGE INPUTS
RELAY CONTACT OPEN
INTERNAL WIRING
FIELD WIRING
RELAY COIL
RELAY CONTACT CLOSED
DDL COMMUNICATIONS
1
2
3
5
USER TERMINALS
1
2
2
120 VAC, 50/60 Hz POWER SUPPLY, RM7830A; 220-240 VAC, 50/60 Hz POWER SUPPLY, EC7830A. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
M15183B
STATUS LEDS
RTLOS
LD2
SHUTTER
SAFETY RELAY CIRCUIT
F
G
...
22
66-1092—06 4
Fig. 1. Internal block diagram of EC/RM7830A (see Fig. 3 for detailed wiring instructions).
L1 HOT
N
1
4
2
19
CONFIGURATION JUMPERS
PLUG-IN PURGE TIMER CARD
F
G
22
PLUG-IN FLAME AMPLIFIER
MICROCOMPUTER
RUN/TEST SWITCH
RESET PUSHBUTTON
FLAME SIGNAL
TEST JACK
RELAY DRIVE CIRCUIT
1K
2K
3K
4K
5K
6K
7K
8K
9K
CONTROL POWER
POWER SUPPLY
18
17
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
10
8
21
9
5
3
OPTIONAL KEYBOARD DISPLAY MODULE
RS485
16
1K1
2K2 5K1
4K1
7K1
2K1
PV1
PV2
MV
3K1
6K1
7
ES1
ES3
ES2
3K2
SAFETY RELAY CIRCUIT
20 6
FAN
AL
IGN
AL
DDL
13
15
14
12
HIGH FIRE
COMMON
LOW FIRE
MODULATE
REMOTE RESET
8K1
8K2
9K2
9K1
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLTAGE INPUTS
RELAY CONTACT OPEN
INTERNAL WIRING
FIELD WIRING
RELAY COIL
RELAY CONTACT CLOSED
DDL COMMUNICATIONS
1
2
3
5
USER TERMINALS
1
2
2
120 VAC, 50/60 Hz POWER SUPPLY, RM7850A; 220-240 VAC, 50/60 Hz POWER SUPPLY, EC7850A. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
M15184B
STATUS LEDS
RTLOS
LD2
SHUTTER
FG
...
22
Fig. 2. Internal block diagram of EC/RM7850A (see Fig. 4 for detailed wiring instructions).
EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES
5 66-1092—06