Honeywell RM7800, RM7823, RM7830, RM7838, RM7840 User Manual

...
SIL
3
RM/EC 7800 Burner Controller
SAFETY MANUAL
Edition 11.19 · 320023101 · EN
1 Scope and Purpose of the
Document
ities for installation and operation of the Honey well 780 0 Series Relay Modules in order to maintain the designed safety level. Items that will be addressed are proof testing, repair and replacement of the device, reliability data, lifetime, environ­mental and application limits, and parameter settings.
This Safety Manual is limited to Models: RM7800, RM7823,
RM7830, RM7838, RM7840, RM7845, RM7850, RM7865, RM7885, RM7888, RM7890, RM7895, RM7896, RM7897, RM7898, EC7820, EC7823, EC7830, EC784 0, EC7850, EC7890, EC7895 with one of the following Flame Detectors and Flame Amplifiers:
Table 1. 7800 Series Burner Controller Models and Series
MODEL SERIES MODEL SERIES MODEL SERIES MODEL SERIES
RM780 0
RM7823
RM7830
RM7838
RM784 0*
RM7845
*NOTE: RM7840E1016, RM78 40L1018 and RM7840L1026
MODEL SERIES
R78 47B 5
R7852B 1
R78 47C 5
R7851C 2
R7861A 2
R7886A 2
9
6
5
9
8
3
RM7850
RM7865
RM7885
RM7888
RM7890
5
4
5
5
9
RM7895
RM7896
RM7897
RM7898
6
EC7820
6
EC7823
6
EC7830
6
EC784 0
EC7850
EC7890
EC7895
are Series 5
Table 2. R78xx Flame Amplifier Models and Series
7
4
6
5
6
5
5
Table 3. C7xxx Flame Sensor Models and Series
MODEL SERIES
C7008A 1
C7009A 1
C7915A 1
C7012E 1
C7012F 1
C7061A 1
C7061F 1
C7076A 1
C7076D 1
C7961E 1
C7961F 1
CONTENTS
1 Scope and Purpose of the Document ....................1
2 Using the Honey well 7800 Series Relay Modules ........2
2.1 Safety Function .............................................2
2.2 Fail Safe State ...............................................2
2.3 Safety Response Time ......................................2
2.4 Diagnostic Response Time .................................2
2.5 Maximum Achievable SIL ...................................2
2.6 Model Selection and Specification of Honeywell 7800
Series Relay Modules .......................................2
2.7 Installation .................................................3
2.8 Required configuration settings........................... 3
2.9 Reliabilit y data .............................................3
2.10 Lifetime limits.............................................. 4
2.11 Proof Testing ...............................................4
2.12 Repair and replacement ................................... 4
2.13 Firmware update ........................................... 4
2.14 Environmental and EMC based limits ..................... 4
3 Definitions and Abbreviations ...........................5
3.1 Definitions ................................................. 5
3.2 Abbreviations .............................................. 5
4 Status of the document ..................................5
4.1 Releases ................................................... 5
4.2 Open issues ................................................6
4.3 Future enhancements of the document .................. 6
Capable
RM/EC 7800 Burner Controller Safety Manual
2 Using the Honeywell 7800 Series
Relay Modules

2.1 Safety Function

The 7800 Series provides automatic burner flame sequencing and flame supervision with protection against loss of flame.

2.2 Fail Safe State

The Safety Shutdown (Lockout) mode is the failsafe state for the Honey well 780 0 Series Relay Modules where all safety critical terminals (main and pilot valves, and ignition trans­former) are de-energized and a manual reset is required to return to normal operation.

2.3 Safety Response Time

The Honeywell 780 0 Series Relay Modules (all models ex­cept of EC7823 and RM7823) will respond to loss of flame by means of shutting of f all safety outputs and transitioning to the Safety Shutdown (Lockout) state within the published Flame Failure Response Time (FFRT) for the selected Flame Amplifier and Flame Sensor.
EC7823 and RM7823 will respond to loss of flame by means of shutting off the safet y outputs and transitioning to the Idle state within the published Flame Failure Response Time (FFRT) for the selected Flame Amplifier and Flame Sensor. Safety Shutdown (Lockout) state is not entered and manual reset action is not needed in this case.
2.6 Model Selection and Specification of Honeywell 7800 Series Relay Modules
The Honeywell 780 0 Series Relay Modules and optional com­ponents for certified SIL applications shall only be selected and specified for applications consistent with the guidelines presented in the Installation Instructions document and ad­ditional technical literature released for the specific model available at web site https: //customer.honeywell.com and further restricted to the certified Flame Amplifiers and Flame Detectors identified in section 1 of this Safety Manual.

2.4 Diagnostic Response Time

The Honeywell 780 0 Series Relay Modules will report a de­tectable internal failure within 3 seconds for faults to the main
7800 Relay Module and within 15 seconds for faults to the
Flame Detector / Flame Amplifier.

2.5 Maximum Achievable SIL

The 7800 Relay Modules, Flame Amplifiers and Flame De-
tectors covered by this safety manual are suitable for use in both high and low demand mode of operation Safety Integrity Functions (SIF) up to SIL 3 in simplex (1oo1) configurations.
The achieved SIL for a particular SIF needs to be verified by
PFH or PFDavg calculation for the entire SIF including the failure rates of the associated sensors and actuators that are also part of the SIF.
Use of the Honeywell 7800 Series Relay Modules in a redun­dant (1ooN) configurations is not supported.
The 7800 Series Burner Controller System is classified as a
1
Type B
fault tolerance of 0.
1 Type B element: “Complex” element (using micro controllers or
element according to IEC 61508, having a hardware
programmable logic); for details see 7.4.4.1. 3 of IEC 61508-2, ed, 2010
32-00231-01 2
RM/EC 7800 Burner Controller Safety Manual
Q7800
SELECTABLE CONFIGURATION JUMPERS

2.7 Installation

The Honeywell 780 0 Series Relay Module sub-base must be
installed, wired and the “Final Wiring Check” and “Static Checkout” procedures successfully completed according to the guidelines published in the Installation Instructions document for the specific model available at web site https://customer.honeywell.com. The Static Checkout proce­dure must be successfully per formed prior to installation of the relay module on the sub-base.
For RM7823 and EC7823 models, in SIL 3 applications, both sets of COMN.O. outputs (terminals 8, 9 and 13, 15) must be wired in series, i.e. terminal 9 must be tied to terminal 13.
The N.C. outputs (terminals 10 and 14) can’t be used in SIL 3
applications.
G
L2
3
4
5
(L1)1314
12
15
16
COMMON
6
NORMALLY OPEN
33
2.8 Required configuration settings
The following user settable options need to be properly con­figured for the individual application in order to provide the designed safety integrity for that application. Jumpers JR1 through JR3 site-configurable jumpers come factor y installed for one configuration and must be selectively clipped out to select the actual desired configurations as documented on the warning label adjacent to the jumper positions as shown in Figure 1 below. Note that the actual jumper configuration setting may differ by product model number.
RUNTEST SWITCH
5
3
COMMON
NORMALLY OPEN
6
FLAME DETECTOR
4
120V, 50/60 HZ (RM7823); 220-240V, 50/60 Hz (EC 7823) POWER SUPPLY. PROVIDE
1
DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS
2
OUTPUTS SHOWN ARE WHEN THE DEVICE DOES NOT SEE FLAME.
3
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS FOR CORRECT WIRING.
4
TERMINALS 9 AND 13 MUST BE WIRED TOGETHER
5
(BOTH COM-N.O. RELAY OUTPUTS ARE WIRED IN SERIES)
TERMINALS 10 AND 14 MUST NOT BE USED.
6
NOTE: FOR EC7823, A 220/240V TO 120V,
10 VA, STEP-DOWN TRANSFORMER IS REQUIRED.
Fig. 1. RM7823 and EC7823 wiring for SIL 3 applications
6
7
8
9
10
F
17
2
18
19
20
21
22
L1 (HOT)
MASTER SWITCH
L2
1
NOTE: CONFIGURATION JUMPERS SHOWN FOR RM7800G/7840G
Fig. 2. Site-configurable jumpers
Note that the cut jumper condition is the safest setting so that failure to cut a jumper during installation can result in a con­figuration that does not meet the requirements for the partic­ular application.
In addition, many models require the use of a factory pre­set Purge Timer Card configures the 7800 Module for the required purge time (between 2 seconds and 30 minutes). These cards are preset to a par ticular purge time at the factory and must be ordered according to the needs of the particular application.

2.9 Reliability data

A detailed Failure Mode, Effects, and Diagnostics Analysis (FMEDA) report is available from Honeywell Thermal Solu­tions with all failure rates and failure modes for use in SIL ver­ification.
Note that the failure rates of the associated sensors and actu­ators need to be accounted for in the SIF level PFH / PFDavg calculation.
3 32-00231-01
RM/EC 7800 Burner Controller Safety Manual

2.10 Lifetime limits

The expected lifetime of the Honeywell 7800 Series Relay
Modules is approximately 10 years. The reliability data listed in the FMEDA report is only valid for this period. The failure rates of the Honey well 7800 Series Relay Modules may in­crease sometime after this period. Reliability calculations based on the data listed in the FMEDA repor t for lifetimes be­yond 10 years may yield results that are too optimistic, i.e. the calculated Safety Integrity Level may not be achieved.

2.11 Proof Testing

The objective of proof testing when used in low demand mode
of operation is to detect failures within Honeywell 7800 Series Relay Module and its associated sensors and actuators that may not be detected by the normal self-diagnostics. Of main concern are undetected failures that prevent the safety in­strumented function from performing its intended function.
The frequency of the proof tests (or the proof test interval ) is
to be determined in the reliability calculations for the safety instrumented functions for which the Honeywell 7800 Series Relay Modules is applied. The actual proof tests must be per­formed at least as frequently as specified in the calculation in order to maintain required safety integrity of the safety instru­mented function.
The following tools may be needed to be available to perform
proof testing
• Voltmeter (1M Ohm minimum input impedance) set on the 0300 Vac scale.
• Two jumper wires; no. 14 wire, insulated, 12 inches (304.8 mm) long with insulated alligator clips at both ends.
The person(s) performing the proof test of the Honey well 7800 Series Relay Modules should be a trained, experienced,
flame safeguard service technician, trained in Honeywell
7800 Series Relay Modules maintenance and company man-
agement of change procedures.
The following tests need to be specifically executed when a
proof test is performed. The results of the proof test need to be documented and this documentation should be part of a plant safety management system. Failures that are detected should be reported to Honey well Thermal Solutions.
7. Remove any remaining bypasses and restore normal oper­ation.
8. Press reset and verify return to normal operation..
When all the tests listed above are executed a proof test cov­erage of 36% can be claimed.
2.11.2 Test (7823 models only)
Functional test:
1. Remove the 7823 Module from the wiring sub-base
2. Perform the “Static Checkout” procedure documented in
the Installation Instructions and verify proper response to all test conditions
3. Reinstall the 7823 Module to the wiring sub-base.
4. While in “Run” sequence interrupt the flame signal by
either manually blocking the fuel supply or blocking the sensor input from “seeing” the flame and verify unit goes to Standby state and all safety critical terminals become de-energized.
5. Restore fuel supply or visibility of flame sensor to the flame and verify return to the normal operation.
When all the tests listed above are executed a proof test cov­erage of 13% can be claimed.

2.12 Repair and replacement

In the unlikely event that the Honeywell 7800 Series Relay Modules has a failure, the failures that are detected should be reported to Honeywell Thermal Solutions.
When replacing the Honeywell 7800 Series Relay Modules power should be removed and the procedure in the installa­tion manual should be followed.
The person(s) performing the repair and / or replacement of the Honey well 780 0 Series Relay Modules should be a trained, experienced, flame safeguard service technician.

2.13 Firmware update

In case firmware updates are required they will only be per­formed at factory where proper replacement procedures are in place. The user is not permitted to perform any firmware updates.
2.11.1 Test (except 7823 models)
Functional test:
1. Remove the 7800 Module from the wiring sub-base
2. Perform the “Static Checkout” procedure documented in
the Installation Instructions and verify proper response to all test conditions
3. Reinstall the 7800 Module to the wiring sub-base.
4. While in “Run” sequence interrupt the flame signal by
either manually blocking the fuel supply or blocking the sensor input from “seeing” the flame and verify unit goes to Safety Shutdown (Lockout) state.
5. Restore fuel supply or visibility of flame sensor to the flame.
6. Power cycle the unit and verify unit returns to Safety Shut­down (Lockout) state upon reapplication of power.
32-00231-01 4

2.14 Environmental and EMC based limits

The environmental and EMC based limits of the Honey well 7800 Series Relay Modules are specified in the user installa­tion manual [32 00143 Rev 1217].
RM/EC 7800 Burner Controller Safety Manual
3 Definitions and Abbreviations
3.1 Definitions
Safety Freedom from unacceptable risk of
harm
Functional Safety The abilit y of a system to carry out
the actions necessary to achieve or to maintain a defined safe state for the equipment / machinery / plant / appa­ratus under control of the system
Basic Safety The equipment must be designed and
manufactured such that it protects against risk of damage to persons by electrical shock and other hazards and against resulting fire and explosion.
The protection must be effective under
all conditions of the nominal operation and under single fault condition
Verification The demonstration for each phase of
the life-cycle that the (output) deliver­ables of the phase meet the objectives and requirements specified by the inputs to the phase. The verification is usually executed by analysis and / or testing
Validation The demonstration that the safety-re-
lated system(s) or the combination of safety-related system(s) and external risk reduction facilities meet, in all respects, the Safety Requirements
Specification. The validation is usually
executed by testing
Safety Assessment The investigation to arrive at a judg-
ment - based on evidence - of the safe­ty achieved by safety-related systems
Further definitions of terms used for safety techniques and measures and the description of safety related systems are given in IEC 615084.

3.2 Abbreviations

FMEDA Failure Mode, Effects and Diagnostic Analysis
BPCS Basic Process Control System
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
SLC Safety Lifecycle

4 Status of the document

4.1 Releases

Version: V3
Revision: R4
Version History:
V3, R4 Dec 6,
V3, R3 Nov 15,
V3, R2 Oct 2,
V3, R1 Oct 2,
V3, R0 Sep 24,
V2, R0 Nov 14,
V1, R0 June 2,
V0, R3 May 28,
V0, R2 May 27,
V0, R1: April 3,
V0, R0: March 15,
Review: V0, R3 reviewed by Michael Medoff (exida)
Release status: Reviewed and released
Date Author Changes
Radomir
2019
2019
2019
2019
2019
2019
2019
2019
2019
2019
2019
V0, R1: review by client and Michael
Svoboda
Radomir Svoboda
Radomir Svoboda
Radomir Svoboda
Radomir Svoboda
John Grebe Updated OS models,
John Grebe Added Safety Func-
John Grebe Update Diagnostic
John Grebe Make client re-
John Grebe Clean up to more
John Grebe Draft
Medoff (exida)
Series numbers of R78xx Flame Am­plifier corrected
Document title up­dated to show 7823 Flame switch sepa­rately. Model table split to three tables to list modules, am­plifiers and sensors separately. Safety function split to address 7823 flame switch differences.
Remaining refer­ences to 7824 sys­tem removed (not in scope)
Added a proof test specific to 7823
Added RM7823 and EC7823 models (flame switch)
company name, and changed to released status
tion section 2.1 and changed to released status
Response Time based on Fault In­jection Tests
quested changes to product model numbers
clearly represent products
5 32-00231-01
RM/EC 7800 Burner Controller Safety Manual

4.2 Open issues

None

4.3 Future enhancements of the document

None anticipated
For More Information
The Honeywell Thermal Solutions family of products includes Honeywell
Combustion Safety, Eclipse, Exothermics, Hauck, Kromschröder and Maxon. To learn more about our products, visit ThermalSolutions. honeywell.com or contact your Honeywell Sales Engineer.
Honeywell Process Solutions
Honeywell Thermal Solutions (HTS)
1250 West Sam Houston Parkway
South Houston, TX 77042
ThermalSolutions.honeywell.com
® U.S. Registered Trademark
© 2019 Honeywell International Inc. 32-00231-01 Edition 11.19 Printed in United States
Loading...