Honeywell RM7800L1087 Installation Instructions Manual

RM7800L1087; RM7840G1022,L1075; EC7840L1014 Relay Modules with Valve Proving
INSTALLATION INSTRUCTIONS

APPLICATION

The Honeywell RM7800L/40L and EC7840L Relay Modules are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single burner applications. The RM7800L/40L and EC7840L Relay Modules are used for UL/CSA Modulating and FM/IRI Modulating burner applications. The consists of a Relay Module. Keyboard Display Modules (standard with RM7800), Dust Cover (standard with RM7840/ EC7840L), Subbase, Amplifier, and Purge Card. Options include Personal Computer Interface, DATA CONTROLBUS MODULE™, Remote Display Mounting, First-Out Expanded Annunciator and Combustion System Manager™ Software.
Functions provided by the RM7800L/40L, EC7840L include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
RM7800L1087/RM7840G1022,L1075; EC7840L1014 offer the Valve Proving test feature.
Using the S7800A1142 Keyboard Display (standard on RM7800L1087) the following features can be set up:
• Post Purge time—Up to 66 minutes—Device shipped with 15 seconds Post purge.
• Valve Proving features including:
— VPS test time — When (Never, Before, After, Split or Both)
See S7800A1142 Instructions (65-0288) for its features. Series 5 can be programmed for Modbus communication.
At commissioning time, the Valve Proving System may be scheduled to occur at one of five different times:
• Never—Device default as received—Valve proving does not occur.
Before—Valve proving before run concurrent with Pre-Purge.
• After—Valve proving occurs after the Run state, before the device goes to Standby (Concurrent with Post­Purge, if selected.)
• Both—Valve proving occurs at both times Before and After, noted above.
• Split—The main valve 2 (MV2) (high pressure) seat test is performed at the Before time and the main valve 1 (MV1) (low pressure) seat test is performed during the After time.
RM7800L/40L, EC7840L
system
The following assumptions apply when using the RM7840G,L, RM7800L, EC7840L:
MV1
VP
SW.
INLET
1
CAUTION: VALVE ENERGIZING TIMING IS BASED ON HONEYWELL VALVE
1
OPENING TIMES OF 13 SECONDS MAXIMUM.
MV1—Wired to terminal 9. It is located in the most upstream position of the main gas valve train.
VPS—Valve Proving Switch: Setpoint at 1/2 of Main Valve inlet pressure.
MV2—Wired to terminal 21. It is the main valve located closest to the burner.
The PII—Pre-Ignition Interlock (or Proof of Closure Switch) for terminal 20 can be installed on MV1, MV2, or as a series connection through both valves.
Appendix B lists many wiring options for single and dual fuel along with the Valve Proving options.
− FOR VALVES WITH TIMINGS GREATER THAN 13 SECONDS OR THOSE THAT DO NOT OPEN THE ACTIVE VALVE WITHIN THE ENERGIZED TIME, A BYPASS SOLENOID VALVE (1/4”, 120 VAC) IS REQUIRED TO OBTAIN THE PROPER TEST PRESSURES.
− THE BYPASS VALVE WILL BE WIRED IN PARALLEL TO THE VALVE IT IS BYPASSING (TERMINAL 9 FOR MV1 OR TERMINAL 21 FOR MV2).
Fig. 1. The valve proving system.
MV2
OUTLET
M24161

SPECIFICATIONS

Electrical Ratings, see Table 3:
Voltage and Frequency:
RM78xx—120 Vac (+10/-15%), 50 or 60 Hz (±10%).
EC78xx—220–240 Vac (+10/-15%), 50 or 60 Hz (±10%). Power Dissipation: RM7800/RM7840/EC7840L: 10W maximum in the Run mode.
66-1162-2
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Maximum Total Connected Load: 2000 VA.
Fusing: 15A maximum, Type SC or equivalent Fast Blow.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C). Humidity: 85% relative humidity continuous, noncondensing. Vibration: 0.5G environment.
Approvals: RM7800L/40G,L:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ. Canadian Standards Association Certified: LR9S329-3. Factory Mutual Approved: Report No. J.I.1V9A0.AF. IRI Acceptable. Federal Communications Commission, Part 15,
Class B—Emissions.
Approvals: EC7840L:
Factory Mutual Approved: Report No. J.I.1V9A0.AF. IRI Acceptable. Federal Communications Commission, Part 15,
Class B—Emissions.
This document provides installation and static checkout instructions. Other applicable publications are:
Publication
No. Product
63-2278 Q7700 Network Interface Unit Product Data 65-0084 Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0288 S7800A1142 Keyboard Display Module
Product Data
65-0091 S7810A Data ControlBus™ Module Product
Data 65-0095 S7820 Remote Reset Module Product Data 65-0097 221729C Dust Cover Installation
Instructions 65-0101 S7830 Expanded Annunciator Product Data 65-0102 ZM7850A Combustion System Manager™
Operating Instructions 65-0109 R7824, R7847, R7848, R7849, R7851,
R7861, R7886 Flame Amplifiers for the
7800 SERIES Product Data 65-0131 221818A Extension Cable Assembly
Product Data 65-0229 7800 SERIES Relay Modules Checkout and
Troubleshooting Product Data 65-0092 QS7800A ControlBus™ Module, Standard 65-0227 QS7800B ControlBus™ Module, Multidrop 65-0249 S7810M ModBus Module

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safeguard service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause property damage, severe injury, or death.
To prevent possible hazardous burner operation, verify safety requirements each time a control is installed on a burner.
WARNING
Electrical Shock Hazard. Can cause serious injury or death.
Disconnect the power supply before beginning installation. More than one power supply disconnect may be required.
IMPORTANT
1. Wiring connections for the relay modules are unique;
therefore, refer to Figs. 3, 4, 6, 7, or Appendix B for proper subbase wiring.
2. Wiring must comply with all applicable codes,
ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage)
wiring.
4. Loads connected to the RM7800L/40L, EC7840L must
not exceed those listed on the RM7800L/40L, EC7840L label or the Specifications, see Table 3.
5. Limits and interlocks must be rated to simultaneously
carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component
recognized by authorities who have jurisdiction for the specific purpose for which they are used.
7. For on-off gas-fired systems, some authorities who
have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two Flame Detectors can be connected in parallel with
the exception of Infrared Flame Detectors (C7015, C7915), Ultraviolet (C7927, C7961), or Visible (C7962).
9. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference; in which case, the users at their own expense may be required to take whatever measures are required to correct this interference.
10.This digital apparatus does not exceed the Class B
limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
66-1162—2 2
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING

Location

Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85 percent relative humidity continuous, noncondensing, moisture environment. Condensing moisture may cause a safety shutdown.
Vibration
Do not install the relay module where it could be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors, protect the relay module using an approved weather-tight enclosure.

Mounting Wiring Subbase

1.
Mount the subbase in any position except horizontally with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating.
2.
Select a location on a wall, burner or electrical panel. The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for servicing, installation, access or removal of the EC7840L Module, flame amplifier, flame amplifier signal voltage probes, Run/Test Switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark the four screw locations. Drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
, Expanded Annunciator, Keyboard Display
RM7800L/40L,

Wiring Subbase

WARNING
Electrical Shock Hazard. Can cause serious injury, death or equipment damage.
Disconnect the power supply before beginning installation to prevent electrical shock, equipment and control damage. More than one power supply disconnect may be required.
1. For proper subbase wiring, refer to Figs. 3, 4, 6, 7, or Appendix B.
2. For proper remote wiring of the Keyboard Display Module, through a 203541 5-wire Connector, refer to the Specifications for the Keyboard Display Module (65-0288), Network Interface Unit (63-2278), Data ControlBus Module™ (65-0091) or Extension Cable Assembly (65-0131).
3. Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be required.
4. All wiring must comply with all applicable electrical codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Voltage) wiring.
5. Recommended wire size and type: see Table 1.
6. Recommended grounding practices: see Table 2.
The Keyboard Display Module, Data ControlBus Module™ (for remote mounting or communications), through a 203541 5-wire Connector, or Communication Interface ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors, for connections over 100 feet.
7. Recommended wire routing of leadwires: a. Do not run high voltage ignition transformer wires in
the same conduit with the flame detector, Data Controlbus Module™, or Remote Reset Module wiring.
b. Do not route flame detector, Data Controlbus
Module™, or Remote Reset Module leadwires in conduit with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector, Data Controlbus
Module™, or Remote Reset Module Instructions.
8. Keyboard Display Module (KDM): Because the KDM is powered from a low voltage, energy limited source, it can be mounted outside of a control panel if it is protected from mechanical damage.
NOTE: A 13 Vdc power supply must be used any time more
than one Keyboard Display Module is used.
9. Maximum wire lengths follow: a. RM7800L/40L, EC7840L leadwires—The maximum
length of leadwire is 300 feet to terminal inputs (Con­trol, Pre-Ignition Interlock, Running/Lockout Inter­lock, High Fire Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires—The maximum length of
wire is 1000 feet to a Remote Reset pushbutton.
d. Data Controlbus Module™—The maximum Data
Controlbus Module™ cable length depends on the number of system modules connected, the noise conditions and the cable used. The maximum length of all Data Controlbus Module™ interconnecting wire is 1000 feet.
10. Make sure loads do not exceed the terminal ratings. Refer to the label on the RM7800/RM7840/EC7840L or to the ratings in Tables 3, 4 and 5.

Final Wiring Check

1. Check the power supply circuit. The voltage and fre­quency tolerance must match those of the RM7800L/40L, EC7840L. A separate power supply cir­cuit may be required for the RM7800/RM7840/ EC7840L. Add the required disconnect means and overload protection.
2. Check all wiring circuits and complete the Static Checkout, see Table 9, before installing the RM7800L/40L, EC7840L on the subbase.
3. Install all electrical connectors.
4. Restore power to the panel.
3 66-1162—2
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
2
L1 (HOT) L2
DEMAND
6
17
16
20
F
G
INTERNAL ELECTRONICS
DEMAND (VALVE PROVING)
7
1K
PLUG IN FLAME AMPLIFIER
3K
6K
4K
2K
2K
5K
7K
HIGH FIRE
COMMON
MODULATE
LOW FIRE
L2
3
5
LOW FIRE
SWITCH
HIGH FIRE
SWITCH
8
9
10
21
22
12
13
15
14
ALARM
BLOWER
18
19
PILOT VALV E
MAIN VALV E 1
IGNITION
1
DETECTOR SHUTTER
M24162
4
LIMITS
VALVE PROVING SWITCH
PRE-IGNITION INTERLOCK
FLAME DETECTOR
1
2
CONTROLLER
AIR FLOW SWITCH
INTERNAL RELAY OPTO FEEDBACK FIELD WIRING INTERNAL WIRING
15 SECOND INTERRUPTED OR MV2 IF VALVE PROVING DEMAND (T17) USED.
RM7800L/RM7840L 120 VAC 50/60 HZ EC7840L 220-240 VAC 50/60 HZ
Fig. 2. Internal block diagram of the RM7800L/40L, EC7840L (See Figs. 3, 4, 6 or 7 for individual detailed wiring
instructions).
Table 1. Recommended Wire Sizes and Part Numbers.
Application Recommended Wire Size Recommended Part Number(s)
Line voltage terminals 14, 16 or 18 AWG copper conductor, 600
volt insulation, moisture-resistant wire.
Keyboard Display Module (KDM) 22 AWG two-wire twisted pair with ground,
or five wire.
Data ControlBus Module™ 22 AWG two-wire twisted pair with ground,
or five wire.
Remote Reset Module 22 AWG two-wire twisted pair, insulated for
low voltage.
Communications Interface ControlBus™
22 AWG two-wire twisted pair with ground. Belden 8723 shielded cable or
Module
13 Vdc full-wave rectified transformer power input.
66-1162—2 4
18 AWG wire insulated for voltages and temperatures for given application.
TTW60C, THW75C, THHN90C.
Belden 8723 shielded cable or equivalent.
Belden 8723 shielded cable or equivalent.
equivalent.
TTW60C, THW75C, THHN90C.
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Table 2. Recommended Grounding Practices.
Ground Type Recommended Practice
Earth ground (subbase and relay module).
1. Use to provide a connection between the subbase and the control panel of the equipment. Earth ground must be capable of conducting enough current to blow the 15A fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length, maximum surface area ground conductors. If a leadwire must be used, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground path are free of nonconductive coatings and protected against corrosion on mating surfaces.
Signal ground (KDM, Data ControlBus Module™, Communications Interface
Use the shield of the signal wire to ground the device to the signal ground terminals [3(c)] of each device. Connect the shield at both ends of the chain to earth ground.
ControlBus™ Module).
Table 3. Terminal Ratings.
Ratings
Terminal No. Description
G
Flame Sensor Ground
a
120 Vac 220/230/240 Vac
——
Earth G Earth Ground
L2(N) Line Voltage Common
3 Alarm 1A pilot duty
4
Line Voltage Supply (L1)
b
120 Vac (+10%/-15%), 50 or 60 Hz (±10%)
220-240 Vac (+10%/-15%), 50 or 60 Hz (±10%)
5 Burner Motor 9.8 AFL, 58.8 ALR (inrush) 4A at PF = 0.5, 20A Inrush
6 Burner Controller and Limits Demand (NOT Valve Proving) 1 mA 1 mA
7 Lockout/Running Interlock 8A run, 43A inrush 8A run, 43A inrush
8 Pilot Valve/Ignition
9 Main Fuel Valve
10 Ignition
F(11) Flame Sensor 60 to 220 Vac,
current limited
c
c
c
4A at PF = 0.5, 20A Inrush
4A at PF = 0.5, 20A Inrush
2A at PF = 0.2
60 to 220 Vac, current limited
12 Firing Rate High Fire 75 VA pilot duty 0.5A at PF = 0.5
13 Firing Rate Common 75 VA pilot duty 0.5A at PF = 0.5
14 Firing Rate Low Fire 75 VA pilot duty 0.5A at PF = 0.5
15 Firing Rate Modulate 75 VA pilot duty 0.5A at PF = 0.5
16 Valve Proving Switch 1 mA 1 mA
17 Demand — Valve Proving 1 mA 1 mA
18 Low Fire Switch Input 1 mA 1 mA
19 High Fire Switch Input (7800/40L only) 1 mA 1 mA
20 Pre-Ignition Interlock Input 1 mA 1 mA
21 Interrupted/Intermittent Pilot Valve/First Stage Oil Valve
c
4A at PF = 0.5, 20A Inrush
or MV2
22 Shutter 0.5A
a
The relay module must have an earth ground providing a connection between the subbase and the control panel or the
d
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event of an internal short circuit. The relay module requires a low impedance ground connection to the equipment frame, which, in turn, requires a low impedance connection to earth ground.
b
2000 VA maximum connected load to relay module assembly.
c
See Tables 4 and 5.
d
220/240 Vac to 120 Vac, 10 VA (minimum) stepdown transformer (not provided) must be used to drive the shutter.
5 66-1162—2
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Combination No. Pilot Fuel 8 Main 9 Ignition 10 Valve 21
1 C F No Load No Load
2 B F No Load No Load
3 No Load F No Load B
4 F F A No Load
5 No Load F A F
6 D F A No Load
7 No Load D A D
8 D D A No Load
9 No Load D A D
Table 5. Explanation of Each Combination.
AB CD F
4.5A ignition.
50 VA Pilot Duty
4.5A ignition.
a
Pilot Duty refers to solenoid-type valves.
a
plus
180 VA ignition plus motor valve with: 660 VA inrush, 360 VA open, 260 VA hold.
2A Pilot Duty.
a
64 VA Pilot Dutya plus motor valves with: 3850 VA inrush, 700 VA open, 250 VA hold.

Mounting RM7800L/40L, EC7840L Relay Module (Fig. 9)

1. Mount the RM7800L/40L, EC7840L vertically on the Q7800 Subbase, or mount horizontally with the knifeblade terminals pointing downward. When mounted on the Q7800A, the RM7800L/40L, EC7840L must be in an electrical enclosure.
2. When mounting in an electrical enclosure, provide adequate clearance for servicing, installation and removal of the RM7800L/40L, EC7840L, Keyboard Display Module, flame amplifier, flame amplifier signal voltage probes, electrical signal voltage probes, and electrical connections.
a. Allow an additional two inches below the
RM7800L/40L, EC7840L for the flame amplifier mounting.
b. Allow an optional three-inch minimum to both sides
of the RM7800L/40L, EC7840L for electrical signal voltage probes.
3. Make sure no subbase wiring is projecting beyond the terminal blocks. Tuck in wiring against the back of the subbase so it does not interfere with the knifeblade terminals or bifurcated contacts.
IMPORTANT
The RM7800L/40L, EC7840L must be installed with a plug-in motion rather than a hinge action.
4. Mount the RM7800L/40L, EC7840L by aligning the four L-shaped corner guides and knifeblade terminals with the bifurcated contacts on the wiring subbase and securely tighten the two screws without deforming the plastic.
66-1162—2 6
120V ALARM
A
BURNER MOTOR (BLOWER)
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
SERIES 90
L2
G
3
4
5
Q7800
(L1)
12
13
14
15
16
HIGH FIRE
COMMON
LOW FIRE
MODULATE
FIRING RATE MOTOR
B
R
W
SERIES 90 CONTROLLER
B
R
W
FOR DIRECT SPARK IGNITION (OIL OR GAS)
IGNITION
10
TRANSFORMER
8
2ND STAGE
9
FUEL VALVE (OPTIONAL)
L2
BURNER CONTROLLER/LIMITS
LOCKOUT INTERLOCKS (INC. AIR FLOW SWITCH)
10 SEC. INTERRUPTED PILOT/IGNITION
MAIN FUEL VALVE(S)
5 SECOND IGNITION (EARLY SPARK TERMINATION)
FLAME DETECTOR
3
10
17
6
7
8
9
F
18
19
20
21
22
2
LOW FIRE START SWITCH
HIGH FIRE PURGE SWITCH
PREIGNITION INTERLOCK
15 SEC. INTERRUPTED PILOT VALVE
MASTER SWITCH
L1 (HOT)
L2
1
120V, 50/60 Hz (EC7840L 220-240 VAC) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
DO NOT WIRE TO ANY UNUSED TERMINALS.
3
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS FOR CORRECT WIRING.
1
M23158
RM7800/RM7840L/EC7840L
INITIATE (INITIAL POWERUP ONLY)
POWER
LED DISPLAY
BURNER
OPERATING CONTROLS
ND
INTERLOCKS
FLAME SIGNAL
FIRING RATE MOTOR
INTERLOCK. CHECK
STANDBY
POWER
PREIGNITION INTERLOCK CLOSED
PREPURGE HOLD
00
DRIVE TO HIGH FIRE
SAFE START CHECK
SWITCHING
00 00 10 25 00 1520
POWER
LIMITS AND BURNER CONTROLLER CLOSED
19TO
5
TIMED PREPURGE
POWER
PILOT
FLAME
MAIN
LOCKOUT INTERLOCKS CLOSED
HIGH FIRE SW.
13 12
MOTOR ACTION
PREPURGE HOLD DRIVE TO LOW FIRE
POWER
PILOT
FLAME
MAIN
BURNER/BLOWER MOTOR
10
20TO
4
TO
PFEP 10 SEC.
00
(4 SEC. IF JR1
CLIPPED
POWER
PILOT
FLAME
MAIN
IGN.
5 SEC.
10 SEC. IGN./PILOT
15 SEC. PILOT
LOW FIRE SW.
MFEP
POWER
PILOT
FLAME
MAIN
ALARMALARMALARMALARM
8
21
MAIN VALVE
TO
L1
6
18
5
TO
FLAME PROVING
13 14
TO
RUN
POWER
PILOT
FLAME
MAIN
ALARM
5
6
7TO
13 15
TO
POSTPURGE
9
POWER
TO
13 14
STANDBY
POWER
IC
PII
SSC
NOTE: SEE APPENDIX FOR APPLICATION OPTIONS.
M24091
Fig. 3. Typical wiring subbase and sequence for RM7800L/40L, EC7840L without enabled Valve Proving.
7 66-1162—2
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
A
SERIES 90
120V ALARM
BURNER MOTOR (BLOWER)
LIMITS
BURNER CONTROL
LOCKOUT INTERLOCKS (INC. AIR FLOW SWITCH)
10 SEC. INTERRUPTED PILOT/IGNITION
MAIN FUEL VALVE 1
5 SECOND IGNITION (EARLY SPARK TERMINATION)
FLAME DETECTOR
3
L2
10
G
3
4
5
6
7
8
9
F
Q7800
(L1)
12
13
14
15
16
17
18
19
20
21
22
HIGH FIRE
COMMON
LOW FIRE
MODULATE
VALVE PROVING SWITCH
2
LOW FIRE START SWITCH
HIGH FIRE PURGE SWITCH
PREIGNITION INTERLOCK
MV2 VALVE
MASTER SWITCH
FIRING RATE MOTOR
B
R
W
SERIES 90 CONTROLLER
L1 (HOT)
L2
B
R
W
1
120V, 50/60 Hz (EC7840L 220-240 VAC) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
DO NOT WIRE TO ANY UNUSED TERMINALS.
3
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS FOR CORRECT WIRING.
4
JR2 INTACT ON RM7800L/40L FOR DSI FUNCTION.
1
FOR DIRECT SPARK IGNITION (OIL OR GAS)
IGNITION
10
TRANSFORMER
MAIN VALVE 1
9
MAIN VALVE 2
21
17
BURNER CONTROLLER
L2
M24092
RM7800/RM7840L/EC7840L
INITIATE (INITIAL POWERUP ONLY)
POWER
LED DISPLAY
BURNER
OPERATING CONTROLS
ND
INTERLOCKS
FLAME SIGNAL
FIRING RATE MOTOR
INTERLOCK. CHECK
STANDBY
PREIGNITION INTERLOCK CLOSED
PREPURGE HOLD
00
DRIVE TO HIGH FIRE
POWER
SAFE START CHECK FLAME PROVING
SWITCHING
00 00 10 25 00 1520
TIMED PREPURGE
POWER
5
POWER
PILOT
FLAME
MAIN
LIMITS AND BURNER CONTROLLER CLOSED
LOCKOUT INTERLOCKS CLOSED
HIGH FIRE SW.
19TO
13 12
MOTOR ACTION
PREPURGE HOLD DRIVE TO LOW FIRE
BURNER/BLOWER MOTOR
TO
POWER
PILOT
FLAME
MAIN
4
00
10
20TO
PFEP 10 SEC. (4 SEC. IF JR1
CLIPPED
POWER
PILOT
FLAME
MAIN
IGN.
5 SEC.
10 SEC. IGN./PILOT
LOW FIRE SW.
5
13 14
MFEP
POWER
PILOT
FLAME
MAIN
ALARMALARMALARMALARM
8
21
MV2
MAIN VALVE
TO
L1
18
TO
TO
RUN
POWER
PILOT
FLAME
MAIN
ALARM
5
2
6
7
13 15
TO
POSTPURGE
1
9
POWER
TO
13 14
STANDBY
POWER
IC
PII
SSC
1
MV2 IS MAIN VALVE CLOSEST TO THE BURNER.
Fig. 4. Wiring subbase and sequence for RM7800L/40L, EC7840L with Valve Proving feature enabled.
66-1162—2 8
JR2 REMOVED FOR PILOT SEQUENCE.
2
M24093
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
BEFORE
HF T19
5
CLOSED
4 SEC.
CONTROLLER
AIRFLOW
CONTROLLER
CONTROLLER LOCKOUT INTERLOCKS
LOCKOUT IF ON, MV1 LEAKING (LOW PRESSURE TEST).
1
LOCKOUT IF OFF, MV2 LEAKING (HIGH PRESSURE TEST).
2
L1-17
17-7
PII (20)
AFTER
RUN
L1-17
L1-7
HF T19 CLOSED
SPLIT
L1-17
L1-7
MV2 (21)
POST PURGE
4 SEC.
MV2 (21)
4 SEC. 4 SEC.
MV1 (9)
3
3 SEC.
3 SEC.
3
3 SEC.
TEST TIME
VPS (16)
PII (20)
4
TEST TIME
VPS (16)
PII (20)
TEST TIME
VPS (16)
PII (20)
FINISH PURGE
4 SEC.
3 SEC.
MV1 (9)
1
3 SEC.
4 SEC.
MV1 (9)
1
BURNER RUN TIME
2
TEST IS RUN CONCURRENT WITH PRE PURGE TIME.
3
TEST IS RUN CONCURRENT WITH POSTPURGE, IF POSTPURGE TIME IS ENABLED.
4
5
RM7800/40L/EC7840L ONLY.
TEST TIME
VPS (16)
PII (20)
TEST TIME
VPS (16)
PII (20)
POST PURGE
MV2 (21)
4
2
2
3 SEC.
IGNITION TRIALS
FINISH POST PURGE
TEST TIME
STANDBY
VPS (16)
PII (20)
FINISH POST PURGE
1
STANDBY
M24094A
Fig. 5. RM7800L/40G,L and EC7840L Relay Module operation, Valve Proving test options.
9 66-1162—2
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
SERIES 90
G
Q7800
12
HIGH FIRE
FIRING RATE MOTOR
B
SERIES 90 CONTROLLER
B
120V ALARM
BURNER MOTOR (BLOWER)
BURNER CONTROLLER/LIMITS
RUNNING INTERLOCKS (INC. AIR FLOW SWITCH)
10 SEC. INTERRUPTED PILOT/IGNITION
MAIN FUEL VALVE(S)
5 SECOND IGNITION (EARLY SPARK TERMINATION)
FLAME DETECTOR
4
INITIATE (INITIAL POWERUP ONLY)
POWER
LED DISPLAY
BURNER
OPERATING CONTROLS AND INTERLOCKS
FLAME SIGNAL
FIRING RATE MOTOR
INTERLOCK. CHECK
COMMON
13
LOW FIRE
14
MODULATE
15
16
17
4
18
19
20
21
22
POWER
PILOT
FLAME
MAIN
LOW FIRE START SWITCH
JUMPER WIRE FOR 30s MFEP
PREIGNITION INTERLOCK
15 OR 30 SEC. INTERRUPTED/ INTERMITTENT PILOT VALVE
PREPURGE HOLD DRIVE TO LOW FIRE
POWER
PILOT
FLAME
MAIN
STANDBY
POWER
L2
3
4
(L1)
5
6
7
8
9
10
F
00 00 10 25 00 1520
TIMED PREPURGE
BURNER/BLOWER MOTOR
LIMITS AND BURNER CONTROLLER CLOSED
RUNNING INTERLOCKS CLOSED
PREIGNITION INTERLOCK CLOSED
SAFE START CHECK
RM7840G SWITCHING
13 12
TO
MOTOR ACTION
R
W
MASTER SWITCH
00
10
10 SEC. IGN./PILOT
LOW FIRE SW.
13 14
2
L1 (HOT)
L2
1
RM7840G
PFEP 10 SEC. (4 SEC. IF JR1
CLIPPED
POWER
PILOT
FLAME
MAIN
ALARMALARMALARM
IGN.
5 SEC.
1
20TO
4
TO
R
W
3
1
120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ADD JUMPER FOR 30 SECOND MAIN FLAME ESTABLISHING PERIOD (MFEP).
3
DO NOT WIRE TO ANY UNUSED TERMINALS.
4
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS FOR CORRECT WIRING.
MFEP
POWER
PILOT
FLAME
MAIN
ALARM
FOR DIRECT SPARK IGNITION (OIL OR GAS)
IGNITION
10
TRANSFORMER
1ST STAGE
21
FUEL VALVE
2ND STAGE
9
FUEL VALVE (OPTIONAL)
RUN
POSTPURGE
POWER
POWER
PILOT
FLAME
MAIN
ALARM
STANDBY
POWER
5
8
21
MAIN VALVE
TO
L1
6
9
6
7TO
PII
18
5
TO
FLAME PROVING
13 15
TO
TO
13 14
SSC
L2
M12260C
IC
1
15/30 SEC. INTERRUPTED/INTERMITTENT PILOT VALVE
Fig. 6. Typical wiring subbase and sequence for RM7840G without Valve Proving enabled.
66-1162—2 10
M24169B
Loading...
+ 22 hidden pages