These relays can be used for a variety of switching applications. Typically they provide control of line- or low-voltage
devices by a low voltage controller. See Table 1.
TABLE 1—SWITCHING RELAY SPECIFICATIONS.
ModelsApplication
R182J
R482J
R845AFor hot water zone control
R847A
RA89AFor switching one line
RA832A
For 24V thermostat
control of line voltage
devices.
Controlled by a line
voltage controller
systems or spst control of
two separate loads.
Provides switching for
high-current loads such as
cooling compressors.
voltage load.
For switching two line
voltage loads with a
common power source.
Coil
Voltage Switch Control
(50/60 Hz) Action Circuit50/60 Hz)(A)
120 Dpdt3-wire240.40
2403.722.2
120 2-wire120 0.08 7.444.4
208/240208/2400.043.722.2
120Dpst240.407.444.4
12022100
2401050
120Spst10.2 61.2
120 Dpst7.444.4
2403.722.2
Voltage
(Vac at
Relay Coil
Current
a
Contact
Ratings (A)
AFL ALR
7.444.4
a
IMPORTANT: The transformer on the R182 can over-
heat when used with a series 20 thermostat if the
total resistance of the thermostat circuit exceeds
2.5 ohms. If the measured resistance of the thermostat (including thermostat wire and thermostat contact resistance) exceeds 2.5 ohms, add a 100 ohm,
10 watt resistor between the W and R terminals.
Table 2 gives maximum thermostat wire runs; if
longer runs are necessary, measure the resistance or
add a 100 ohm, 10 watt resistor across terminals W
and R.
1. Read these instructions carefully. Failure to follow
instructions can damage product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Make sure installer is a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out product operation.
WARNING
ELECTROCUTION HAZARD CAN
CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH.
Transformer core not bonded.
Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.
MOUNTING
For replacement, mount the relay in the same location as
the old relay. If this is a new installation, locate the relay
vertically on a solid wall or partition as close as possible to
the device to be controlled. Select a location that is easily
accessible for installation and service.
NOTE: To reduce the possible transformer hum and relay
noise that is sometimes amplified by mounting surfaces
such as sheetmetal, plasterboard, and similar materials,
place rubber or felt washers between the case and the
mounting surface.
1. Position the relay and mark the mounting holes. See
Fig. 1.
2. Start a screw for the keyhole type mounting hole in
the upper right corner. Screw it down within about 1/8 in.
[3 mm] of the surface.
3. Hang the relay on the screw, position the case, and
start the bottom screw.
4. Tighten both screws.
WIRING
All wiring must comply with all applicable electrical
codes, ordinances, and regulations. Follow any instructions
furnished with the controlled equipment.
IMPORTANT: The switching relay terminals are ap-
proved for use with copper wires only.
See Figs. 2 through 9 for hookup diagrams for these
relays. When two or more devices are to be controlled in
parallel, the total current must not exceed the relay load
rating. Fig. 11 is an internal view of the RA832A showing
terminal locations and barriers.
Never connect load terminals to a load that takes more
current than the amount listed in the electrical ratings on the
relay.
Fig. 1—Approximate mounting dimensions in
in. [mm].
1
4 [108]
5
1 [29]
32
1
2
7
[6] DIAMETER MOUNTING HOLE
32
25
[20]
32
Fig. 2—Internal schematic and typical hookup
for RA89A.
TT
JUMPER
21 34
L2
L1
1
HOT
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
COMPLETE WIRING AS SHOWN ABOVE.
2
4
3
[2] DIAMETER
32
[13] DIAMETER
1
3 [89]
2
3
1 [35]
8
LOW VOLTAGE (CLASS 2)
2-WIRE THERMOSTAT
RA89A (SPST)
TO LOAD
7
1
8
[48]
7
[22] DIAMETER
8
KEYHOLE TYPE
MOUNTING HOLE
1
4
2
[114]
3
[10]
8
3
8
15
2
16
[75]
7
1
8
[48]
KNOCKOUT FOR
1/2 (13) CONDUIT (3)
2
JUMPER REMOVED
21 34
L1
L2
1
HOT
CONTROLLER
(IF USED)
5
[133]
[10]
M3823
RA89A
1
1
4
TO LOAD
M3819
69-0791—32
Fig. 3—Internal schematic and typical hookup
for RA832A.
LOW VOLTAGE (CLASS 2)
2-WIRE THERMOSTAT
TT
XX
AUXILIARY TO LOW
OR MILLIVOLTAGE
(POWERPILE) LOAD
RA832A
Fig. 6—Internal schematics and typical hookup
for R482J.
R482J
2134
L2
L1
1
HOT
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
Fig. 4—Internal schematic and typical hookup
for R182J.
WX RB
3
OHMS
L1
L2
L1
L2
(HOT)
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND
1
DISCONNECT MEANS AS REQUIRED.
N.O. CONTACTS MAKE BEFORE N.C CONTACTS BREAK,
2
AND N.C. CONTACTS MAKE BEFORE N.O. CONTACTS BREAK.
LOAD 1
1
LOAD 2
(OPTIONAL)
K1
N.O.
4
LOAD
K1
37
N.C.
M3821
R182J
K1
K2
K2
6
LOAD
N.C.
N.O.
Fig. 5—Thermostat connections for R182J.
THREE-WIRE
LOW VOLTAGE
(SERIES 10)
THERMOSTAT
RRB
W
W
R182J
MAKES CONTACT ON TEMPERATURE FALL ONLY.
1
MAKES CONTACT ON BOTH A TEMPERATURE RISE AND FALL.
2
1
BX
THREE-WIRE
LOW VOLTAGE
(SERIES 20)
THERMOSTAT
W
W
RB
R
R182J
JUMPER
2
BX
TWO-WIRE
LOW VOLTAGE
(SERIES 80)
THERMOSTAT
W
R182J
R
M8233A
2
M8232
3
5
421
N.O.
N.C.
COM.COM.
TO LOAD
RA845A RELAY
2
1
4
3
5
6
1
37
L1
HOT
L2
CONTROLLER
HYDRONIC HEATING
CONTROL TERMINALS
BURNER
BX
2
1
L1
(HOT)
L2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
CONTROLLER (IF USED) MUST BE SNAP ACTION OR
2
MERCURY SWITCH TYPE.
N.O. CONTACTS MAKE BEFORE N.C CONTACTS BREAK,
3
AND N.C. CONTACTS MAKE BEFORE N.O. CONTACTS BREAK.
Fig. 7—Schematic diagram showing R845A in
multizone, forced hydronic heating system.
This arrangement is suitable for any number of
additional zones.
TO ADDITIONAL R845A
RELAYS FOR OTHER ZONES
T
THERMOSTAT
THERM.
ZONE 1
T
ZC
ZP
B1
BURNER
CONTROL
B2
C1
CIRCULATOR
CIRC.
ZONE 1
C2
1
LINE
2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
2
IF CONTROLLING TWO LOADS, USE:
3 AND 4 FOR LINE VOLTAGE LOAD
5 AND 6 FOR LINE OR LOW VOLTAGE LOAD
3
IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER.
8
N.O.
N.C.
TO LOAD
THERMOSTAT
ZONE 2
CIRCULATOR
ZONE 2
2
3
3
6
M8234
M3822
369-0791—3
Fig. 8—R845A hookup for controlling two loads.
LOW VOLTAGE (CLASS 2)
2-WIRE THERMOSTAT
TT
R845A
Fig. 10—Internal view of RA832A Switching
Relay.
T
X
T
X
RELAY
2134
1
TO
L1
POWER
HOTL2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
WHEN CONTROLLING TWO LOADS, USE 3 AND 4
2
FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE
OR LOW VOLTAGE LOAD.
IF USING LOW VOLTAGE, USE A SEPARATE
3
TRANSFORMER.
Fig. 9—Internal schematics and hookup for
R847A.
LOW VOLTAGE (CLASS 2)
2-WIRE THERMOSTAT
TT
L2 L134
1
TO
L1
L2
1
2
3
4
POWER
(HOT)
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
AND DISCONNECT MEANS AS REQUIRED.
WHEN CONTROLLING TWO LOADS, USE 3 AND 4
FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE
OR LOW VOLTAGE LOAD.
IF USING LOW VOLTAGE, USE A SEPARATE
TRANSFORMER.
10 AMP CONTACT RATING OR 20 AMP WHEN POLES
ARE CONNECTED IN PARALLEL.
2
11
LOAD 1
2
11
LOAD 1
TO
POWER
TO
POWER
3
44
3
65
LOAD 2
M3820
R847A
67
LOAD 2
M8231B
24V TRANSFORMER
12
34
M3824
Service and Checkout
1. Never use oil on any part of the relay coil or contacts.
2. Keep the cover on the relay during normal operation
and remove only for service and checkout.
3. Relay contacts require no cleaning; they are arranged
so they close with a wiping action and are self-cleaning.
The contacts may turn black after being in service for some
time; this discoloration does not prevent proper operation.
4. After installation is complete, operate system through
at least one cycle from the controller to make certain the
relay controls the equipment as intended.
Home and Building ControlHome and Building ControlHelping You Control Your World
Honeywell Inc.Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North740 Ellesmere Road
Golden Valley, MN 55422Scarborough, Ontario
M1P 2V9
69-0791—34
Printed in U.S.A.