Honeywell RA89A, R847A, R845A, R182J, RA832A User Manual

...
®
R182J, R482J, R845A,
R847A, RA89A, RA832A
Switching Relays
Application
These relays can be used for a variety of switching applications. Typically they provide control of line- or low-voltage
devices by a low voltage controller. See Table 1.
TABLE 1—SWITCHING RELAY SPECIFICATIONS.
Models Application
R182J
R482J
R845A For hot water zone control
R847A
RA89A For switching one line
RA832A
For 24V thermostat control of line voltage devices.
Controlled by a line voltage controller
systems or spst control of two separate loads.
Provides switching for high-current loads such as cooling compressors.
voltage load.
For switching two line voltage loads with a common power source.
Coil
Voltage Switch Control
(50/60 Hz) Action Circuit 50/60 Hz) (A)
120 Dpdt 3-wire 24 0.40 240 3.7 22.2
120 2-wire 120 0.08 7.4 44.4
208/240 208/240 0.04 3.7 22.2
120 Dpst 24 0.40 7.4 44.4
120 22 100 240 10 50
120 Spst 10.2 61.2
120 Dpst 7.4 44.4 240 3.7 22.2
Voltage
(Vac at
Relay Coil
Current
a
Contact
Ratings (A) AFL ALR
7.4 44.4
a
IMPORTANT: The transformer on the R182 can over-
heat when used with a series 20 thermostat if the total resistance of the thermostat circuit exceeds
2.5 ohms. If the measured resistance of the thermo­stat (including thermostat wire and thermostat con­tact resistance) exceeds 2.5 ohms, add a 100 ohm, 10 watt resistor between the W and R terminals. Table 2 gives maximum thermostat wire runs; if longer runs are necessary, measure the resistance or add a 100 ohm, 10 watt resistor across terminals W and R.
TABLE 2LENGTH OF WIRE.
AWG
Wire
Size
(Number)
22 120 38.0 60 18.0 20 200 61.0 100 30.5 18 300 91.5 150 45.5 16 500 152.5 250 76.0 14 800 244.0 400 122.0
1 69-0791—3J.H. • Rev. 10-94 • ©Honeywell Inc. 1994 • Form Number 69-0791—3
Total Wire
Length
Feet Meters Feet Meters
Length of Run to Thermostat
(Wires)
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow instructions can damage product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Make sure installer is a trained, experienced service technician.
4. After completing installation, use these instructions to check out product operation.
WARNING
ELECTROCUTION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.
Transformer core not bonded. Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.
MOUNTING
For replacement, mount the relay in the same location as the old relay. If this is a new installation, locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled. Select a location that is easily accessible for installation and service.
NOTE: To reduce the possible transformer hum and relay
noise that is sometimes amplified by mounting surfaces
such as sheetmetal, plasterboard, and similar materials,
place rubber or felt washers between the case and the
mounting surface.
1. Position the relay and mark the mounting holes. See
Fig. 1.
2. Start a screw for the keyhole type mounting hole in the upper right corner. Screw it down within about 1/8 in. [3 mm] of the surface.
3. Hang the relay on the screw, position the case, and start the bottom screw.
4. Tighten both screws.
WIRING
All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow any instructions furnished with the controlled equipment.
IMPORTANT: The switching relay terminals are ap-
proved for use with copper wires only.
See Figs. 2 through 9 for hookup diagrams for these relays. When two or more devices are to be controlled in parallel, the total current must not exceed the relay load rating. Fig. 11 is an internal view of the RA832A showing terminal locations and barriers.
Never connect load terminals to a load that takes more current than the amount listed in the electrical ratings on the relay.
Fig. 1Approximate mounting dimensions in in. [mm].
1
4 [108]
5
1 [29]
32
1 2
7
[6] DIAMETER MOUNTING HOLE
32
25
[20]
32
Fig. 2Internal schematic and typical hookup for RA89A.
TT
JUMPER
21 34
L2
L1
1
HOT
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
COMPLETE WIRING AS SHOWN ABOVE.
2
4
3
[2] DIAMETER
32
[13] DIAMETER
1
3 [89]
2
3
1 [35]
8
LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT
RA89A (SPST)
TO LOAD
7
1
8
[48]
7
[22] DIAMETER
8
KEYHOLE TYPE MOUNTING HOLE
1
4
2
[114]
3
[10]
8
3 8
15
2
16
[75]
7
1
8
[48]
KNOCKOUT FOR 1/2 (13) CONDUIT (3)
2
JUMPER REMOVED
21 34
L1
L2
1
HOT
CONTROLLER (IF USED)
5 [133]
[10]
M3823
RA89A
1
1 4
TO LOAD
M3819
69-079132
Fig. 3Internal schematic and typical hookup
for RA832A.
LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT
TT
XX
AUXILIARY TO LOW OR MILLIVOLTAGE (POWERPILE) LOAD
RA832A
Fig. 6Internal schematics and typical hookup for R482J.
R482J
21 34
L2
L1
1
HOT
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
Fig. 4Internal schematic and typical hookup
for R182J.
WX RB
3 OHMS
L1
L2
L1
L2
(HOT)
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND
1
DISCONNECT MEANS AS REQUIRED.
N.O. CONTACTS MAKE BEFORE N.C CONTACTS BREAK,
2
AND N.C. CONTACTS MAKE BEFORE N.O. CONTACTS BREAK.
LOAD 1
1
LOAD 2 (OPTIONAL)
K1
N.O.
4
LOAD
K1
37
N.C.
M3821
R182J
K1
K2
K2
6
LOAD
N.C.
N.O.
Fig. 5Thermostat connections for R182J.
THREE-WIRE LOW VOLTAGE (SERIES 10) THERMOSTAT
RRB
W
W
R182J
MAKES CONTACT ON TEMPERATURE FALL ONLY.
1
MAKES CONTACT ON BOTH A TEMPERATURE RISE AND FALL.
2
1
BX
THREE-WIRE LOW VOLTAGE (SERIES 20) THERMOSTAT
W
W
RB
R
R182J
JUMPER
2
BX
TWO-WIRE LOW VOLTAGE (SERIES 80) THERMOSTAT
W
R182J
R
M8233A
2
M8232
3
5
421
N.O.
N.C.
COM. COM.
TO LOAD
RA845A RELAY
2
1
4
3
5
6
1
37
L1 HOT
L2
CONTROLLER
HYDRONIC HEATING CONTROL TERMINALS
BURNER
BX
2
1
L1 (HOT)
L2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
CONTROLLER (IF USED) MUST BE SNAP ACTION OR
2
MERCURY SWITCH TYPE.
N.O. CONTACTS MAKE BEFORE N.C CONTACTS BREAK,
3
AND N.C. CONTACTS MAKE BEFORE N.O. CONTACTS BREAK.
Fig. 7Schematic diagram showing R845A in multizone, forced hydronic heating system. This arrangement is suitable for any number of additional zones.
TO ADDITIONAL R845A RELAYS FOR OTHER ZONES
T
THERMOSTAT
THERM.
ZONE 1
T
ZC
ZP
B1
BURNER CONTROL
B2
C1
CIRCULATOR
CIRC.
ZONE 1
C2
1
LINE
2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
2
IF CONTROLLING TWO LOADS, USE: 3 AND 4 FOR LINE VOLTAGE LOAD 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD
3
IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER.
8
N.O.
N.C.
TO LOAD
THERMOSTAT ZONE 2
CIRCULATOR ZONE 2
2
3
3
6
M8234
M3822
3 69-0791—3
Fig. 8R845A hookup for controlling two loads.
LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT
TT
R845A
Fig. 10Internal view of RA832A Switching Relay.
T
X
T
X
RELAY
21 34
1
TO
L1
POWER
HOTL2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED.
WHEN CONTROLLING TWO LOADS, USE 3 AND 4
2
FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD.
IF USING LOW VOLTAGE, USE A SEPARATE
3
TRANSFORMER.
Fig. 9Internal schematics and hookup for
R847A.
LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT
TT
L2 L1 34
1
TO
L1
L2
1
2
3
4
POWER
(HOT)
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.
WHEN CONTROLLING TWO LOADS, USE 3 AND 4 FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD.
IF USING LOW VOLTAGE, USE A SEPARATE TRANSFORMER.
10 AMP CONTACT RATING OR 20 AMP WHEN POLES ARE CONNECTED IN PARALLEL.
2
1 1
LOAD 1
2
1 1
LOAD 1
TO POWER
TO POWER
3
44
3
65
LOAD 2
M3820
R847A
67
LOAD 2
M8231B
24V TRANSFORMER
12
34
M3824
Service and Checkout
1. Never use oil on any part of the relay coil or contacts.
2. Keep the cover on the relay during normal operation
and remove only for service and checkout.
3. Relay contacts require no cleaning; they are arranged so they close with a wiping action and are self-cleaning. The contacts may turn black after being in service for some time; this discoloration does not prevent proper operation.
4. After installation is complete, operate system through at least one cycle from the controller to make certain the relay controls the equipment as intended.
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell LimitedHoneywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9
69-079134
Printed in U.S.A.