Honeywell RA89 Installation Manual

R182J, R482J, YHR845A,R847A, RA89A, RA832A Switching Relays
INSTALLATION INSTRUCTIONS
These relays can be used for a variety of switching applications. Typically they provide control of line- or low-voltage devices by a low voltage controller. See Table 1.
Models Application
R182J For 24V thermostat control of
R482J Controlled by a line voltage
YHR845A For hot water zone control
R847A Provides switching for high-
RA89A For switching one line
RA832A For switching two line load
a
line voltage devices.
controller.
systems or spst control of two separate loads.
current loads such as cooling compressors.
voltage load.
voltage loads with a common power source.
The transformer on the R182 can overheat when used with a series 20 thermostat if the total resistance of the thermostat circuit exceeds 2.5 ohms. If the measured resistance of the thermostat (including thermostat wire and thermostat contact resistance) exceeds 2.5 ohms, add a 100 ohm, 10 watt resistor between the W and R terminals. Table 2 gives maximum thermostat wire runs; if longer runs are neces­sary, measure the resistance or add a 100 ohm, 10 watt resistor across terminals W and R.
Table 1. Switching Relay Specifications.
Coil
Wire Size
Vol tag e
(Vac at
50/60 Hz)
Table 2. Length of Wire.
Relay Coil
Current (A)
a
0.40
Tot al W ire
Length
Feet Meters Feet Meters
Length of Run to
Thermostat
Vol tag e
(50/60 Hz)
120 Dpdt 3-wire 24
240 3.7 22.2
120 2-wire 120 0.08 7.4 44.4
208/240 208/240 0.04 3.7 22.2
120 Dpst 24 0.40 7.4 44.4
120 22 100
240 10 50
120 Spst 10.2 61.2
120 Dpst 7.4 44.4
240 3.7 22.2
Switch
Control
Action
Circuit
AWG
(Number)
22 120 38.0 60 18.0
20 200 61.0 100 30.5
18 300 91.5 150 45.5
16 500 152.5 250 76.0
14 800 244.0 400 122.0
Contact
Ratings (A)
AFL ALR
7.4 44.4
(Wires)
69-2041
R182J, R482J, YHR845A,R847A, RA89A, RA832A SWITCHING RELAYS
INSTALLATION
When Installing this Product
1. Read these instructions carefully. Failure to follow instructions can damage product or cause a haz­ardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Make sure installer is a trained, experienced service technician.
4. After completing installation, use these instructions to check out product operation.
WARNING
Electrocution Hazard. Can cause property damage, severe injury, or death.
Transformer core not bonded.
Disconnect power supply before wiring to prevent electrical shock or equipment damage.
Mounting
For replacement, mount the relay in the same location as the old relay. If this is a new installation, locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled. Select a location that is easily accessible for installation and service.
NOTE: To reduce the possible transformer hum and
relay noise that is sometimes amplified by mounting surfaces such as sheet metal, plaster­board, and similar materials, place rubber or felt washers between the case and the mounting surface.
1. Position the relay and mark the mounting holes. See Fig. 1.
2. Start a screw for the keyhole type mounting hole in the upper right corner. Screw it down within about 1/ 8 in. (3 mm) of the surface.
3. Hang the relay on the screw, position the case, and start the bottom screw.
4. Tighten both screws.
Wiring
All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow any instructions furnished with the controlled equipment.
The switching relay terminals are approved for use with copper wires only.
See Fig. 2 through 9 for hookup diagrams for these relays. When two or more devices are to be controlled in parallel, the total current must not exceed the relay load rating. Fig. 10 is an internal view of the RA832A showing terminal locations and barriers.
Never connect load terminals to a load that takes more current than the amount listed in the electrical ratings on the relay.
1
4 (108)
3
(2) DIAMETER
32
(13) DIAMETER
1
3 (89)
2
3
1 (35)
8
4
7
1
8
(48)
7
(22) DIAMETER
8
KEYHOLE TYPE MOUNTING HOLE
3
(10)
8
2
(75)
7
1
8
(48)
KNOCKOUT FOR 1/2 (13) CONDUIT (3)
4
(114)
15 16
1 2
1
5
4
(133)
3
(10)
8
M3823B
5
1 (29)
32
1 2
7
(6) DIAMETER MOUNTING HOLE
32
25
(20)
32
Fig. 1. Approximate mounting dimensions in in. (mm).
LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT
RA89A (SPST)
TT
JUMPER
21 34
L2
1
2
TO LOAD
L1
1
HOT
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.
COMPLETE WIRING AS SHOWN ABOVE.
Fig. 2. Internal schematic and typical hookup for
2
21 34
L2
1
CONTROLLER (IF USED)
RA89A.
RA89A
JUMPER REMOVED
L1 HOT
1
TO LOAD
M3819A
69-2041 2
Loading...
+ 2 hidden pages