Honeywell R882J Installation Manual

R182J, R482J, R845A, R847A, R882J,
RA89A, RA832A Switching Relays
Application
These relays can be used for a variety of switching applications to provide control of line- or low-voltage devices by a low
voltage controller. See Table 1.
TABLE 1—SWITCHING RELAY SPECIFICATIONS.
Models Application
R182J
R482J
R845A For hot water zone control
R847A
R882J For use with separate low
RA89A For switching one line
RA832A
For 24V thermostat control of line voltage devices.
Controlled by a line voltage controller
systems or spst control of two separate loads.
Provides switching for high-current loads such as cooling compressors.
voltage power source.
voltage load. For switching two line
voltage loads with a common power source.
Coil
Voltage Switch Control
(50/60 Hz) Action Circuit 50/60 Hz) (A)
120 Dpdt 3-wire 24 0.40 240 3.7 22.2
120 2-wire 120 0.08 7.4 44.4
208/240 208/240 0.04 3.7 22.2
120 Dpst 24 0.40 7.4 44.4
120 22 100 240 10 50
24 Dpdt 7.4 44.4
120 Spst 10.2 61.2
120 Dpst 7.4 44.4 240 3.7 22.2
Voltage
(Vac at
Relay Coil
Current
a
Contact
Ratings (A) AFL ALR
7.4 44.4
a
heat when used with a series 20 thermostat if the total resistance of the thermostat circuit exceeds
2.5 ohms. If the measured resistance of the thermo­stat (including thermostat wire and thermostat con­tact resistance) exceeds 2.5 ohms, add a 100 ohm, 10 watt resistor between the W and R terminals. Table 2 gives maximum thermostat wire runs; if longer runs are necessary, measure the resistance or add a 100 ohm, 10 watt resistor across terminals W and R.
TABLE 2—LENGTH OF WIRE.
AWG
Wire
Size
(Number)
22 120 38.0 60 18.0 20 200 61.0 100 30.5 18 300 91.5 150 45.5 16 500 152.5 250 76.0 14 800 244.0 400 122.0
1 69-0790—3J.H. • Rev. 10-94 • ©Honeywell Inc. 1994 • Form Number 69-0790—3
Total Wire
Length
Feet Meters Feet Meters
Length of Run to Thermostat
(Wires)
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Make sure installer is a trained, experienced service technician.
4. After completing installation, use these instructions to check out product operation.
W ARNING
ELECTROCUTION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.
Transformer core not bonded. Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.
MOUNTING
For replacement, mount the relay in the same location as the old relay. If this is a new installation, locate the relay vertically on a solid wall or partition as close as possible to the device to be controlled. Select a location that is easily accessible for installation and service.
NOTE: To reduce the possible transformer hum and relay
noise that is sometimes amplified by mounting surfaces
such as sheetmetal, plasterboard, and similar materials,
place rubber or felt washers between the case and the
mounting surface.
1. Position the relay and mark the mounting holes. See
Fig. 1.
2. Start a screw for the keyhole type mounting hole in the upper right corner. Screw it down within about 1/8 in. [3 mm] of the surface.
3. Hang the relay on the screw, position the case, and start the bottom screw.
4. Tighten both screws.
WIRING
All wiring must comply with all applicable electrical codes, ordinances, and regulations. Follow any instructions furnished with the controlled equipment.
IMPORTANT: The switching relay terminals are ap-
proved for use with copper wires only.
See Figs. 2 through 10 for hookup diagrams for these relays. When two or more devices are to be controlled in parallel, the total current must not exceed the relay load rating. Fig. 11 is an internal view of the RA832A and shows terminal locations and barriers.
Never connect load terminals to a load that takes more current than the amount listed in the electrical ratings on the relay.
Fig. 1—Approximate mounting dimensions in in. [mm].
1
4 [108]
3
[2] DIAMETER
32
[13] DIAMETER
1
3 [89]
2
3
1 [35]
8
RA89A (SPST)
TO LOAD
4
KNOCKOUT FOR 1/2 (13) CONDUIT (3)
L2
CONTROLLER (IF USED)
7
1
8
[48]
7
[22] DIAMETER
8
KEYHOLE TYPE MOUNTING HOLE
1
4
2
[114]
1
5
4
[133]
3
[10]
8
3
[10]
8
15
2
16
[75]
7
1
8
[48]
M3823
2
21 34
1
RA89A
JUMPER REMOVED
L1 HOT
1
TO LOAD
5
1 [29]
32
1 2
7
[6] DIAMETER MOUNTING HOLE
32
25
[20]
32
Fig. 2—Internal schematic and typical hookup for RA89A.
LOW VOLTAGE (CLASS 2) 2-WIRE THERMOSTAT
TT
JUMPER
21 34
L2
L1
1
HOT
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION
1
AND DISCONNECT MEANS AS REQUIRED. COMPLETE WIRING AS SHOWN ABOVE.
2
M3819
69-079032
Loading...
+ 2 hidden pages