SPECIFICATIONS
Models: See Table 1.
PRODUCT DATA
APPLICATION
Q5024 globe valve linkages connect a Honeywell direct
coupled actuator (DCA) to a steam or water globe valve.
Q5024 linkages are compatible with 2- and 3-way globe
valves.
FEATURES
• Used with 2-way and 3-way globe valves in modulating
or two-position service.
• Quick and simple installation with no disassembly
required.
Table 1. Models.
Linkage Actuator Qty* Valve Stroke**
Q5024A1116 1 0.63” / 16 mm
Q5024A1123 1 0.91” / 23 mm
Q5024A1130 1 1.18” / 30 mm
Q5024B2230 2 1.18” / 30 mm
Q5024B2240 2 1.57” / 40 mm
* See Table 3 for Linkage and Actuator selection.
** If the exact stroke is not available than round up to the next
higher stroke.
Dimensions: See Fig. 1.
Temperature Range:
Ambient Range: -40°F to 140°F (-40°C to 60°C).
Materials of Construction:
Housing: Cold Rolled Steel
Rack and Pinion Gears: Steel
Bushing and Clip: Brass
Contents
Application .............................................................. 1
Specifications ......................................................... 1
Installation .............................................................. 13
Checkout ................................................................ 14
Special Order Form ................................................. 15

GLOBE VALVE LINKAGES
Q5024A1116/Q5024A1123
E
B
E
B
Q5024B2230/Q5024B2240
E
B
A
D
Q5024A1130
A
D
A
C
C
C
D
M35307
Fig. 1. Q5024 Dimensions.
Table 2. Dimensions in Inches.
Linkage ABCDEShaft Dia.
Q5024A1116
4-3/8” 3-1/2” 6-1/4” 9-1/2” 2-1/2” 16mm
Q5024A1123
Q5024A1130
4-3/8” 4” 6” 11” 2-3/8” 19mm
Q5024B2230
Q5024B2240
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
Golden Valley, Minnesota 55422-4386
3. http:// or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
38-00020—02 2

GLOBE VALVE LINKAGES
LINKAGE SELECTION INSTRUCTION
When selecting your linkage look at the Table 3 for the valve model list. Select the correct valve size to see the recommended
linkage and bonnet adapter. Choose the correct actuator torque based on necessary close-off pressure. If model you are looking
for is not listed fill out the Special Order Form located below.
If you do not have the exact part number or valve size, measure the valve stroke and select the corresponding linkage from Table 1.
Next, select the appropriate bonnet adapter kit from Table 5. This kit includes variety of bonnet adapters for you to choose from at
the job site.
Manufacturer Valve Model Single Actuator Linkage
Honeywell V5011
V5013
VGF Single Actuator Linkage
Table 3. Linkage and Actuator Selection.
Val ve
Connection
Size
(inch)
0.5 Q5024A1123
0.75 130 230
1 80 140 230
1.25 50 90 200
1.5 65 140
2 35 80 140
2.5 55 90
3 35 65
Val ve
Connection
Size
(inch)
2 Q5024B2230
2.5 75 123
3 50 80
4 Q5024B2240
5 12 21
6 10 16
Val ve
Connection
Size
(inch)
2.5 Q5024A1123
3
Val ve
Connection
Size
(inch)
4 Q5024B2240
5 11 18
6
Linkage and
Bonnet Adapter
and
HU5024-001
Dual Actuator Linkage
Linkage and
Bonnet Adapter
and
HU5024-001
and
HU5024-002
Linkage and
Bonnet Adapter
and
HU5024-001
Dual Actuator Linkage
Linkage and
Bonnet Adapter
and
HU5024-002
Actuator Torque (lb-in)
44 88 175 300
Close-Off (psi)
230 230
Actuator Torque (lb-in)
350 (2 x 175) 600 (2 x 300)
Close-Off (psi)
118
18 38
Actuator Torque (lb-in)
44 88 175 300
Close-Off (psi)
52 88
26 42
Actuator Torque (lb-in)
350 (2 x 175) 600 (2 x 300)
Close-Off (psi)
27 47
11 18
3 38-00020—02

GLOBE VALVE LINKAGES
Table 3. Linkage and Actuator Selection. (Continued)
Manufacturer Valve Model Dual Actuator Linkage
Honeywell
(continued)
VGF Pressure Balanced Valve
Connection
Size
Linkage and
Bonnet Adapter
350 (2 x 175) 600 (2 x 300)
(inch)
2.5 Q5024B2230
3 175 175
and
HU5024-002
4 Q5024B2240
5 175 175
and
HU5024-002
175 175
175 175
6 175 175
Johnson
Control
V90AD-1C thru 7C
V90DD-1C thru 7C
Val ve
Connection
Size
Single Actuator Linkage
Linkage and
Bonnet Adapter
44 88 175 300
(inch)
0.5 Q5024A1116
0.75 165 230
and JU5024-005
1 Q5024A1123
1.5 65 140
and JU5024-005
V90CA-1 thru 8 0.5 Q5024A1123
0.75 130 230
and JU5024-005
230 230
80 140
230 230
1 80 140 230
1.25 50 90 200
1.5 65 140
2 35 80 140
2.5 Q5024A1123
and JU5024-002
Dual Actuator Linkage
350 (2 x 175) 600 (2 x 300)
3 Q5024B2230
and JU5024-002
Actuator Torque (lb-in)
Close-Off (psi)
Actuator Torque (lb-in)
Close-Off (psi)
55 90
Actuator Torque (lb-in)
Close-Off (psi)
50 80
38-00020—02 4

Table 3. Linkage and Actuator Selection. (Continued)
Manufacturer Valve Model Single Actuator Linkage
Johnson
Control
(continued)
VG7000/2000 Series Valve
Connection
Size
(inch)
0.5 Q5024A1116
0.75 165 230
1 Q5024A1116
1.25 65 120
Linkage and
Bonnet Adapter
and JU5024-001
and JU5024-003
Actuator Torque (lb-in)
44 88 175 300
Close-Off (psi)
230 230
100 190
1.5 Q5024A1123
2 35 80 140
and JU5024-003
2.5 Q5024A1123
and JU5024-004
Dual Actuator Linkage
Actuator Torque (lb-in)
350 (2 x 175) 600 (2 x 300)
Close-Off (psi)
VTM Series
VB-3752
3 Q5024B2230
4 18 48
and JU5024-004
5 Q5024B2240and
6 10 16
JU5024-004
Single Actuator Linkage
Val ve
Connection
Linkage and
Bonnet Adapter
Size
(inch)
0.5 Q5024A1116
0.75 165 230
and JU5024-005
50 80
12 21
Actuator Torque (lb-in)
44 88 175 300
Close-Off (psi)
230 230
1 100 190
1.25 Q5024A1123
1.5 65 140
and JU5024-005
50 90
2 35 80 140
2.5 Q5024A1123
and JU5024-002
Dual Actuator Linkage
Actuator Torque (lb-in)
350 (2 x 175) 600 (2 x 300)
Close-Off (psi)
3 Q5024B2230
4 18 48
and JU5024-002
5 Q5024B2240
50 80
12 21
and JU5024-006
6 Q5024B2240
10 16
and JU5024-004
GLOBE VALVE LINKAGES
65 140
55 90
55 90
5 38-00020—02