Q340A
Thermocouple
INSTALLATION INSTRUCTIONS
APPLICATION
The Q340A Thermocouple is a single-junction
thermocouple lead which provides a 30 mV electrica l
signal when the pilot is operating. Loss of the pilot
removes the electrical curr ent and shuts off the gas
supply to the burner.
SPECIFICATIONS
Temperature Ratings:
Hot Junction area: 1400°F (760°C).
Cold Junction Area: 780°F (416°C).
Lead Lengths:
18 in. (0.5 m) to 48 in. (1.2 m) are available.
INSTALLATION
When Installing This Product…
Read these instructions carefully. Failure to follow
1.
them could damage the product or cause a
hazardous condition.
Check the ratings given in the instructions and on
2.
the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced technician.
3.
After installation is complete, check out product
4.
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage , seri ous
injury or death.
Make sure the gas supply to the burner is turned
off before removing or installing the
thermocouple.
Replacement Installation
Disconnect and remove the old thermocouple.
1.
Determine the type of thermocouple mount :
2.
a. Screw-in type.
b. Clamp type.
c. Push-in type.
Follow the applicable installation instru ctions in
3.
Fig. 1.
SCREW-IN TYPE CLAMP TYPE
Insert
thermocouple
in pilot
burner
Tighten nut
M629
Fig. 1. Q340 Thermocouple inst allation.
Slip nut
off adapter
and clamp
thermocouple
in pilot burner
with shoulder
above clamp,
as shown
PUSH-IN TYPE
thermocouple
New Installation
Determine the type of thermocouple mount (see
1.
step 2 in Replacement Installation).
Follow the applicable instructions in Fig. 1.
2.
Completing the Connection
Connect the other end of the thermocouple to the
1.
safety control. Do not use thread compound; the
connection must be clean and dry.
CAUTION
Equipment Damage Hazard.
Too much torque will damage the connection.
Tighten connector only 1/4 in. turn beyond
finger-tight for good electrical continu ity. Further
tightening can result in damage.
Remove
adapter,
insert
in pilot
burner
® U.S. Registered Trademark
Copyright © 2001 Honeywell • All Rights Reserved
95-6794-1
Q340A THERMOCOUPLE
Make sure to tighten all connection screws
2.
securely.
Connect the limit control wires to the thermocouple
3.
junction block terminals. If no limit control is used,
jumper the terminals on the junction block with
heavy gauge wire.
Turn on the gas supply and light the pilot light.
4.
Wait one minute and turn on the main burner.
5.
Home and Building Control Home and Building Control
Honeywell Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
95-6794—1 G.R. Rev. 4-01 www.honeywell.com
M1V 4Z9
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.