Pilot burners provide main burner ignition for standing pilot natural and LP gas systems. Used with a thermocouple to provide
automatic pilot safety control. Used with a thermopile in a self-powered system. See Table 1 for model specifications.
TABLE 1—MODEL SPECIFICATIONS.
ModelAeratedOrificeTypeIncludes
Q314ANoInsertTargetIncludes natural and LP gas orifices, 1/4 in.
Q327AYesSpudTargetIncludes natural and LP gas orifices, 1/4 in.
PrimaryType ofPilot Tip
compression fitting, “F,” “K,” or “L” tip styles,
“B” mounting bracket, and “A” mounting bracket
adapter.
compression fitting, and “B” mounting bracket
with screws.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
instructions can damage product or cause a hazardous condition.
2. Check ratings given in instructions and on product to
make sure product is suitable for your application.
3. Make sure installer is a trained, experienced service
technician.
4. After completing installation, use these instructions to
check out product operation.
WARNING
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH
Follow these warnings exactly.
1. Disconnect power supply before wiring to prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at appliance service valve
before starting installation and perform Gas
Leak Test after completion of installation.
3. Do not bend pilot tubing at the control or pilot
after compression nut has been tightened. Gas
leakage at the connection may result.
Follow appliance manufacturer’s instructions if avail-
able; otherwise, use instructions provided below.
LOCATION
1. Position pilot burner for easy access, observation, and
lighting. In replacement applications, replace pilot burner
with an identical unit and position new pilot burner in the
same location and orientation as the original pilot burner.
2. Mount pilot burner on main burner. Mounting surfaces
other than the main burner can shift, bend, or warp as furnace
expands and contracts while operating. See Fig. 1.
3. Mount pilot burner so the ignition flame remains
properly positioned with respect to the main burner flame.
See Fig. 2.
4. Supply pilot flame with ample air free of combustion
products.
5. Do not impinge pilot flame on adjacent parts. Do not
impinge main burner flame on pilot burner.
6. Do not expose pilot flame to falling scale which could
impair ignition of main burner.
7. Do not expose pilot burner to main burner rollout while
igniting or extinguishing.
8. Do not expose pilot flame to drafts that push or pull
pilot flame away from the thermocouple or thermopile.
Fig. 1—Mount pilot burner on main burner.
PILOT
BURNER/GENERATOR
MUST BE RIGIDLY
POSITIONED
RELATIVE TO
MAIN BURNER
1. Insert thermocouple or thermopile tip into hole or
barrel provided beneath pilot burner. See Figs. 4 and 5.
2. Engage attachment nut threads and tighten until thermocouple or thermopile is locked into place.
PILOT BURNER/
IGNITION-
SENSOR
JUST RIGHT
IGNITION
FLAME JUST
MISSES
MAIN BURNER
PILOT BURNER/
IGNITION-
SENSOR
TOO LOW
IGNITION
FLAME WILL
IMPINGE ON
MAIN BURNER
PILOT BURNER/
IGNITION-
SENSOR
TOO HIGH
MAIN BURNER
FLAME WILL
IMPINGE ON
IGNITION-
SENSOR
M3285
CONNECT PILOT GAS TUBING
1. Cut tubing to desired length and bend as necessary for
routing to pilot burner. Do not make sharp bends or deform
tubing. Do not bend tubing at control after compression nut
has been tightened, as this can result in gas leakage at
connection.
2. Square off and remove burrs from end of tubing.
3. Push tubing into compression nut clearance hole until
tubing bottoms.
NOTE: When replacing a pilot burner or orifice, cut off old
compression fitting and replace with new compression
fitting provided with new pilot burner. Never use old
compression fitting as it may not provide a gas-tight seal.
See Fig. 3.
4. While holding tubing all the way in, engage threads
and turn until finger tight.
5. Using a wrench, turn compression nut one turn beyond
finger tight. DO NOT OVERTIGHTEN.
6. Connect other end of tubing to gas control according to
gas control manufacturer instructions.
Fig. 4—Installing thermocouple or thermopile.
PILOT BURNER
ASSEMBLY
THERMOCOUPLE
OR THERMOPILE
PUSH-IN
CLIP
OPTIONAL
ATTACHMENT
M3286
NUT
Fig. 5—Installing Q390 Thermocouple.
SCREW-IN TYPE
PILOT BURNER
ASSEMBLY
THERMOCOUPLE
Fig. 3—Always use new compression fitting.
PILOT BURNER BODY
FITTING BREAKS OFF
AND CLINCHES TUBING
AS NUT IS TIGHTENED
TIGHTEN NUT ONE
TURN BEYOND
FINGER TIGHT
TO GAS CONTROL
M3295
INSTALL THERMOCOUPLE OR THERMOPILE
PUSH-IN DESIGN
1. Insert thermocouple or thermopile tip into hole or
barrel provided beneath pilot burner. See Fig. 4.
2. Push in firmly until thermocouple or thermopile is
locked into place.
ADAPTER
ATTACHMENT NUT
M3269
INSTALL BLEED GAS TUBING (if used):
1. Route bleed gas tubing from bleed tapping on gas
control to the pilot burner.
2. Push clip into place. See Fig. 6.
3. Insert bleed gas tubing until 3/8 inch [10 mm] of tubing
is above pilot burner bracket. Tip of bleed gas tubing must not
extend into pilot flame.
INSTALL “A” MOUNTING BRACKET ADAPTER
(optional)
To convert mounting bracket from “B” mounting bracket
to “A” mounting bracket, install the “A” mounting bracket
adapter to the pilot burner mounting bracket. Then install
pilot burner to main burner.
2
Fig. 6—Bleed gas tube installation.
Fig. 7—Changing spud and insert orifices.
THIS DIMENSION SHOULD BE
MAXIMUM OF 3/8 INCH [9.5 mm]
WHEN BLEED TUBE IS IN FINAL
POSITION.
BLEED TUBE CLIP
1/8 IN. STEEL TUBING
M3284
CHANGE INSERT ORIFICES (See Fig. 7)
1. Disconnect pilot tubing from the pilot burner and
remove insert orifice. Sometimes a light force is required to
remove the orifice.
2. Cut off old compression fitting.
NOTE: When replacing an orifice, cut off old compression
fitting and replace with a new compression fitting. Never
use old compression fitting as it may not provide a gastight seal. See Fig. 3.
3. Square off end of pilot tubing and remove all burrs.
4. Insert new compression nut over pilot tubing and slide
out of the way.
5. Insert new orifice into pilot burner and push pilot
tubing into the pilot burner until it bottoms.
6. While holding tubing all the way in, slide compression
fitting into place and engage threads. Turn until finger tight.
7. Using a wrench, tighten compression fitting one turn
beyond finger tight.
CHANGE SPUD ORIFICES (See Fig. 7)
1. Disconnect pilot tubing from orifice.
2. Unscrew old spud orifice and discard.
3. Cut off old compression fitting.
NOTE: When replacing an orifice, cut off old compression
fitting and replace with a new compression fitting. Never
use old compression fitting as it may not provide a gastight seal. See Fig. 3.
4. Square off end of pilot tubing and remove all burrs.
5. Insert new compression nut over pilot tubing and slide
out of the way.
6. Insert new orifice into pilot burner and tighten securely.
7. Push pilot tubing into orifice until it bottoms.
8. While holding tubing all the way in, slide compression
fitting into place and engage threads. Turn until finger tight.
9. Using a wrench, tighten compression fitting one turn
beyond finger tight.
INSERT
ORIFICE
CROSS SECTION
M27083
SPUD
ORIFICE
INSERT
ORIFICE
Startup and Checkout
PERFORM GAS LEAK TEST
WARNING
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH
Check for gas leaks with soap and water solution
any time work is done on a gas system.
GAS LEAK TEST:
1. Ensure that gas supply is turned on at the appliance
service valve.
2. Paint pipe connections upstream of pilot burner with
rich soap and water solution. Bubbles indicate gas leak.
3. If leak is detected, tighten pipe connections.
4. Stand clear of main burner while lighting to prevent
injury caused from hidden leaks which could cause flashback
in the appliance vestibule. Light main burner.
5. With main burner in operation, paint pipe joints (including adapters) and gas control inlet and outlet with rich
soap and water solution.
6. If another leak is detected, tighten adapter screws,
joints, and pipe connections.
7. Replace part if leak can not be stopped.
ADJUST PILOT FLAME
The pilot flame should envelop 3/8 to 1/2 in. [10 to
13 mm] of the thermocouple or thermopile tip. See Fig. 8. To
adjust pilot flame:
1. Remove pilot adjustment cover screw from gas con-
trol.
2. Turn inner pilot adjustment screw clockwise to
decrease or counterclockwise to increase pilot flame.
3. Always replace pilot adjustment cover screw and
tighten firmly after completing adjustment to ensure proper
operation.
369-0519—3
Fig. 8—Thermocouple or thermopile tip must be
in pilot flame.
PROPER
FLAME
ADJUSTMENT
3/8 TO 1/2 INCH
[10 TO 13 MILLIMETRES]
Fig. 9—Examples of unsatisfactory pilot
flames.
APPEARANCE
SMALL BLUE FLAME
CAUSE
CHECK FOR LACK OF GAS FROM:
• CLOGGED ORIFICE FILTER
• CLOGGED PILOT FILTER
• LOW GAS SUPPLY PRESSURE
• PILOT ADJUSTMENT AT MINIMUM
THERMOCOUPLE
OR THERMOPILE
M1973A
IGNITE PILOT BURNER
1. Before lighting pilot burner, turn thermostat to its
lowest setting. Wait for unburned gas to vent.
NOTE: LP gas is heavier than air and will not vent upward.
Smell for LP gas next to floor. If you smell gas, shut off the
main valve in the gas piping, or, ON LP, AT THE TANK.
Perform Gas Leak Test to recheck all connections.
2. Light pilot burner according to appliance manu-
facturer’s instructions.
Service
WARNING
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH
Perform Gas Leak Test anytime work is done to the
system.
PILOT OUTAGE
1. If pilot flame goes out during normal operation, but is
properly adjusted, recheck Mounting and Location instructions on page 1.
2. If all mounting and location instructions are followed
but pilot continues to go out, construct shielding to protect
pilot flame from main burner ignition and extinction and
drafts. See Fig. 9.
3. Check pilot flame characteristics.
• Check the pilot flame with the main burner operating.
• Ensure the pilot flame continuously covers the tip of
the thermocouple or thermopile, the spark gap and
3/8 to 1/2 in. [10 to 13 mm] of the ground rod. See
Fig. 8.
• Ensure the pilot flame is blue (a yellow tipped flame is
acceptable on LP systems), soft and steady. See Fig. 9
for examples of possible pilot flame problems and their
causes.
• If pilot burner is damaged, replace it with an identical
pilot burner and mount and position in the same
location and orientation.
LAZY YELLOW FLAME
WAVING BLUE FLAME
NOISY LIFTING BLOWING FLAME
HARD SHARP FLAME
CHECK FOR LACK OF AIR FROM:
• LARGE ORIFICE
• DIRTY LINT SCREEN, IF USED
• DIRTY PRIMARY AIR OPENING,
IF THERE IS ONE
• PILOT ADJUSTMENT AT MINIMUM
CHECK FOR:
• EXCESSIVE DRAFT AT PILOT
LOCATION
• RECIRCULATING PRODUCTS
OF COMBUSTION
CHECK FOR:
• HIGH GAS PRESSURE
THIS FLAME IS CHARACTERISTIC
OF MANUFACTURED GAS
CHECK FOR:
• HIGH GAS PRESSURE
• ORIFICE TOO SMALL
M3272
PILOTSTAT SAFETY CONTROL POWER UNIT
FAILURE
1. Ensure pilot flame is properly adjusted.
2. Ensure power unit connections clean and tight.
3. If power unit still fails to hold in, use the W129A
Millivoltmeter to obtain the open and closed circuit voltage
generated by the thermocouple or generator.
4. Compare measured open and closed circuit voltage
values to Acceptable Range Charts in W129A Manual.
5. If W129A Millivoltmeter or other meter is not available, replace thermocouple or thermopile. If this does not
correct the condition, replace power unit.
THERMOCOUPLE OR THERMOPILE
PERFORMANCE
Thermocouples and thermopiles require proper temperature differential between the hot-junction (tip) and coldjunction (base) to provide satisfactory operation of gas controls. Thermocouples and thermopiles perform less effectively when exposed to excessive cold-junction or hotjunction temperatures.
Excessive cold-junction temperatures can be caused by
heat radiation from adjacent surfaces or high ambient air
temperatures. Excessive cold-junction temperatures can be
eliminated by shielding the pilot flame, see Fig. 10, or
constructing a baffle to direct secondary air over the pilot
burner base.
Excessive hot-junction temperatures can be eliminated by
proper pilot flame adjustment. To adjust pilot flame, see
Adjust Pilot Flame section.
4
Fig. 10—Proper shielding of pilot flame.
TYPICAL
SHIELD
M1273
PILOT TURNDOWN TEST
(30 mV safety control systems)
The Pilot Turndown Test assures that the pilot flame
ignites the main burner within four seconds from the time gas
reaches the main burner. In this test, the pilot flame is just
sufficient enough to hold in the power unit or just above the
point of flame extinction (whichever occurs at a higher pilot
gas flow rate).
1. With the pilot and main burner operating, shut off the
main burner by either lowering the thermostat temperature
setting or turning the gas control knob to the PILOT position.
NOTE: If using a Honeywell W129A Millivoltmeter, turn
the pilot gas adjustment screw until the thermocouple
open circuit voltage is 2 mV. Omit steps 2,3, and 4 and
proceed with step 5.
2. Turn the p ilot gas adjustment screw clockwise until
the pilot begins to decrease in size. Then, turn the pilot gas
adjustment screw clockwise1/4 turn a time (waiting
one minute between each turn to allow the thermocouple to
cool) until safety shutoff power unit just drops, causing safety
shutdown.
3. Turn pilot gas adjustment screw counterclockwise
slightly.
4. Relight pilot burner. The power unit should hold in.
5. Turn gas control knob to ON position and set thermo-
stat temperature setting above room temperature. Main burner
should light within four seconds without flame rollout. If not,
check pilot mounting and location instructions in Location
section and repeat Pilot Turndown Test.
6. Readjust pilot burner flame. See Adjust Pilot Flame
section.
EFFECTIVE IGNITION TEST (750 mV SYSTEMS)
The Effective Ignition Test assures that the pilot flame
ignites the main burner within four seconds from the time gas
reaches the main burner. In this test, the pilot flame is just
sufficient to open the main gas valve.
1. Light the main burner according to the appliance
manufacturer’s instructions and allow to burn at least five
minutes.
2. Remove one thermostat lead (TH) at the gas control
terminal.
3. Using the pilot gas adjustment screw, decrease the
pilot flame until it begins to pull away from the thermopile.
Allow thermopile to cool for one minute.
4. Temporarily jumper the thermostat terminals (TH) on
the gas control.
5. If the main burner ignites, reduce the pilot flame by
turning the pilot adjustment screw 1/4 turn at a time until the
valve fails to pull in. Allow the thermocouple to cool at least
one minute between each reduction in the pilot flame level.
6. Increase the pilot flame just enough to pull in the gas
control main valve.
7. Jumper the thermostat terminals. The main burner
should light within four seconds and without flame roll-out.
If it does not, check the Location and Mounting instructions
on page 1 and repeat steps 1 through 6.
8. If main burner still does not light, replace thermopile
and repeat steps 1 through 6.
9. Remove the jumper to shut off the main burner.
10. Readjust pilot burner flame. See Adjust Pilot Flame
section.
11. Reconnect the thermopile lead and ensure all connec-
tions are correct and the system is functioning properly.
569-0519—3
6
769-0519—3
Home and Building ControlHome and Building ControlHelping You Control Your World
Honeywell Inc.Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North740 Ellesmere Road
Golden Valley, MN 55422Scarborough, Ontario
M1P 2V9
Printed in U.S.A.
QUALITY IS KEY
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.