Honeywell P7640U Installation Instructions Manual

INSTALLATION INSTRUCTIONS
62-0282-02
P7640U Differential Pressure Sensors
APPLICATION
The P7640U Universal Differential Pressure Sensors provide reliable, accurate measurement and control. Proper applications include measurement of extremely low pressure applications such as: building/room pressure, air flow, variable air volume, filter status, and duct pressure. They are ideal for clean rooms, hospitals, fume hoods, and computer rooms.
The P7640 Pressure Sensors are designed with field­selectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The pressure ranges fall between 0–10 in. w.c./0–2500 Pa. See Table 2.
Accessory
32003169-001 Duct Pressure Pick-up Probe, 4 in.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Mounting
Screw holes are accessed inside the enclosure (with the cover removed) and are located in the upper left and lower right corners.
Panel Mount
Run tubing from one (static) or both (differential) barb fittings, making sure the typically higher pressure source is connected to the port labeled HI, and the typically lower pressure source is connected to the port labeled LO.
Configure the internal tubing as shown in Fig. 1. Use small diameter tubing for panel mount configuration.
Duct Mount
1. Thread probe into the back of the housing.
2. Configure internal tubing as shown in Fig. 2. Use
large diameter tubing for duct mounting configuration.
3. Unit is typically mounted at the high pressure loca­tion when used for differential control.
CONFIGURATION
Select the proper output, mode, and pressure range using the switches and jumpers:
1. Select output using the output switch: a. Current: mA (then skip to step 3), or b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
3. Select bi- or uni-directional mode using jumper J5.
NOTE: Setting for 0 to 10 in. w.c. and bi-direc-
tional will give output from -10 to 10 in. w.c.
4. Select inches w.c. or Pascal scale using jumper J7.
5. Select fast or standard response time using jumper
J8.
6. Select appropriate full-scale pressure range using the rotary switch. Align arrow (not the slot) to the desired range. See Table 2 for the range selection guide.
NOTE: The universal model is marked full scale.
When the range is changed, the LCD models momentarily indicate selected range.
7. Set output according to Table 1.
P7640U DIFFERENTIAL PRESSURE SENSORS
62-0282—02 2
Table 1. Controller Compatibility
and Output Settings.
Fig. 1. Tubing for panel mount.
Fig. 2. Tubing for duct mount
WIRING (FIG. 3 THROUGH 5)
CAUTION
Equipment Damage Hazard. Can damage the device beyond repair.
Disconnect power supply before installation.
NOTE: Wiring to the ZERO terminals is optional.
Fig. 3. Wiring for voltage (Vdc) output.
CAUTION
Equipment Damage Hazard. Can damage the device beyond repair.
Do not apply power to output terminal. Permanent equipment damage will result.
Fig. 4. Wiring for current (mA) output.
Controller
Required Sensor
Output Setting
L
ONSPEC
Setting
W7750, W7760, W7761 4-20 mA FilterPress or
P7610B
W7750B, W7760C, W7753, W7760
0-10 Vdc (default) FilterPress or
P7610F, or voltage
Non-Honeywell 0-5 Vdc n/a
SMALLER DIAMETER TUBE FOR PANEL CONFIGURATION
M27485
USE THE FRONT BARB
LARGER DIAMETER TUBE FOR DUCT CONFIGURATION
M27484
USE THE FRONT BARB
L1
L2
CONTROLLER, METER OR RECORDER
INPUT SIGNAL
COMMON
+
+
+
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
POLARIZED SECONDARY INDICATIONS FOR USE WITH DC POWER SUPPLY ONLY.
3
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON CLOSURE. (OPTIONAL)
3
2
1
ZERO
PWR OUT COM ZERO
RESPONSE
FAST/STD
mA
VOLT
OUTPUT
JP8
UNITS
IN. W.C./PA
JP7
MODE BI/UNI
JP5
VOLT
SV/10V
JP4
7
1
2
3
4
5
6
M27291
12 TO 30 Vdc POWER SUPPLY
CONTROLLER, METER OR RECORDER
INPUT SIGNAL
COMMON
+
+
M27292
ZERO
PWR OUT COM ZERO
RESPONSE
FAST/STD
mA
VOLT
1
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON CLOSURE. (OPTIONAL)
1
OUTPUT
JP8
UNITS
IN. W.C./PA
JP7
MODE BI/UNI
JP5
VOLT
SV/10V
JP4
7
1
2
3
4
5
6
Loading...
+ 2 hidden pages