
P7640A,B
Differential Pressure Sensors
INSTALLATION INSTRUCTIONS
APPLICATION
The P7640A Panel Mount and P7640B Duct Mount
Differential Pressure Sensors provide reliable, accurate
measurement and control. Proper applications include
measurement of extremely low pressure applications such
as: building/room pressure, air flow, variable air volume,
filter status, and duct pressure. They are ideal for clean
rooms, hospitals, fume hoods, and computer rooms.
The P7640 Pressure Sensors are designed with fieldselectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The four
pressure ranges fall between 0–1 in. w.c./0–250 Pa or 0–
10 in. w.c./0–2500 Pa, depending on the model.
Accessory
32003169-001 Duct Pressure Pick-up Probe, 4 in.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Mounting
Screw holes are accessed inside the enclosure (with the
cover removed) and are located in the upper left and
lower right corners.
Panel Mount
Run tubing from one (static) or both (differential) barb
fittings, making sure the typically higher pressure source
is connected to the port labeled HI, and the typically
lower pressure source is connected to the port labeled
LO.
Duct Mount
The units with the integral probe should typically be
mounted at the high pressure location when used for
differential control.
CONFIGURATION
Select the proper output, mode, and pressure range
using the switches and jumpers:
1. Select output using the output switch:
a. Current: mA (then skip to step 3), or
b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
3. Select bi- or uni-directional mode using jumper J5.
NOTE: Setting for 0 to 1 in. w.c. and bi-directional
4. Select inches w.c. or Pascal scale using jumper J7.
5. Select fast or standard response time using jumper
J8.
6. Select appropriate full-scale pressure range using
the rotary switch. Align arrow (not the slot) to the
desired range. See Table 2 for the range selection
guide.
NOTE: Note that either the 1 in. w.c. or 10 in. w.c.
7. Set output according to Table 1.
Controller
W7750, W7760, W7761 4-20 mA FilterPress or
W7750B, W7760C,
W7753, W7760
Non-Honeywell 0-5 Vdc n/a
will give output from -1.0 to 1.0 in. w.c.
scale is marked. This is the available
scale for that given model. When the
range is changed, the LCD models
momentarily indicate selected range.
Table 1. Controller Compatibility
and Output Settings.
Required Sensor
Output Setting
0-10 Vdc (default) FilterPress or
L
P7610B
P7610F, or voltage
ONSPEC™
Setting

P7640A,B DIFFERENTIAL PRESSURE SENSORS
12 TO 30 Vdc
POWER SUPPLY
CONTROLLER,
METER OR
RECORDER
INPUT SIGNAL
COMMON
+
+
–
–
M27292
ZERO
PWR OUT COM ZERO
RESPONSE
FAST/STD
mA
VOLT
1
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR
UPON CLOSURE. (OPTIONAL)
1
OUTPUT
JP8
UNITS
IN. W.C./PA
JP7
MODE
BI/UNI
JP5
VOLT
SV/10V
JP4
7
1
2
3
4
5
6
E
GND
OUT1OUT2OUT3OUT4OUT5OUT6OUT7OUT8DI1DI2DI3DI4GND GND
24
VAC
COM
24
VAC
COM
24
VAC24VAC24VAC24VAC24VAC
OUT
COM
21
VDC
OUT
GND E-BUS E-BUS
AI1AI
2
AI3AI
4
AI5AI
6
AI7AI
8
ANALOG
OUT
AO1AO
2
17 18 19 20 21 22 23 24 25 26 27 28 29
L1
(HOT)
L2
31 32 33 34 35 36 37 38 39 40 41 42 43
44
12345 678 9101112 14 1615
13
W7760A
AI
GND
AI
GND
AI
GND
AI
GND
AO
GND
+
–
O
P7640
+
–
O
P7640
+
–
O
H76XX
+
–
M18302B
Vin (Vac)
Gnd
Vo (0-10 Vdc)
PWR
COM
OUT
PWR
COM
OUT
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TEMPERATURE SIGNAL CONNECTIONS ARE NOT POLARITY SENSITIVE.
1
1
2
2
WIRING (FIG. 1 THROUGH 3)
Equipment Damage Hazard.
Can damage the device beyond repair.
Disconnect power supply before installation.
NOTE: Wiring to the ZERO terminals is optional.
ZERO
RESPONSE
FAST/STD
JP8
1
2
VOLT
IN. W.C./PA
JP7
JP5
JP4
1
M27291
UNITS
SV/10V
2
MODE
BI/UNI
7
6
5
3
4
–
+
mA
OUTPUT
+
–
3
L1
L2
PWR OUT COM ZERO
CONTROLLER,
METER OR
RECORDER
INPUT SIGNAL
+
COMMON
–
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
POLARIZED SECONDARY INDICATIONS FOR USE WITH DC POWER
2
SUPPLY ONLY.
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON
3
CLOSURE. (OPTIONAL)
Fig. 1. Wiring for voltage (Vdc) output.
Equipment Damage Hazard.
Can damage the device beyond repair.
Do not apply power to output terminal. Permanent
equipment damage will result.
VOLT
Fig. 2. Wiring for current (mA) output.
62-0210—07 2
Fig. 3. Typical wiring for three-wire pressure sensor with Vdc output (used with the XL15A Controller).