Honeywell P7640A, P7640B Installation Instructions Manual

62-0210-07
P7640A,B Differential Pressure Sensors
INSTALLATION INSTRUCTIONS
APPLICATION
The P7640A Panel Mount and P7640B Duct Mount Differential Pressure Sensors provide reliable, accurate measurement and control. Proper applications include measurement of extremely low pressure applications such as: building/room pressure, air flow, variable air volume, filter status, and duct pressure. They are ideal for clean rooms, hospitals, fume hoods, and computer rooms.
The P7640 Pressure Sensors are designed with field­selectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The four pressure ranges fall between 0–1 in. w.c./0–250 Pa or 0– 10 in. w.c./0–2500 Pa, depending on the model.
Accessory
32003169-001 Duct Pressure Pick-up Probe, 4 in.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Mounting
Screw holes are accessed inside the enclosure (with the cover removed) and are located in the upper left and lower right corners.
Panel Mount
Run tubing from one (static) or both (differential) barb fittings, making sure the typically higher pressure source is connected to the port labeled HI, and the typically lower pressure source is connected to the port labeled LO.
Duct Mount
The units with the integral probe should typically be mounted at the high pressure location when used for differential control.
CONFIGURATION
Select the proper output, mode, and pressure range using the switches and jumpers:
1. Select output using the output switch: a. Current: mA (then skip to step 3), or b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
3. Select bi- or uni-directional mode using jumper J5.
NOTE: Setting for 0 to 1 in. w.c. and bi-directional
4. Select inches w.c. or Pascal scale using jumper J7.
5. Select fast or standard response time using jumper
J8.
6. Select appropriate full-scale pressure range using the rotary switch. Align arrow (not the slot) to the desired range. See Table 2 for the range selection guide.
NOTE: Note that either the 1 in. w.c. or 10 in. w.c.
7. Set output according to Table 1.
Controller
W7750, W7760, W7761 4-20 mA FilterPress or
W7750B, W7760C, W7753, W7760
Non-Honeywell 0-5 Vdc n/a
will give output from -1.0 to 1.0 in. w.c.
scale is marked. This is the available scale for that given model. When the range is changed, the LCD models momentarily indicate selected range.
Table 1. Controller Compatibility
and Output Settings.
Required Sensor
Output Setting
0-10 Vdc (default) FilterPress or
L
P7610B
P7610F, or voltage
ONSPEC
Setting
P7640A,B DIFFERENTIAL PRESSURE SENSORS
CAUTION
CAUTION
12 TO 30 Vdc POWER SUPPLY
CONTROLLER, METER OR RECORDER
INPUT SIGNAL
COMMON
+
+
M27292
ZERO
PWR OUT COM ZERO
RESPONSE
FAST/STD
mA
VOLT
1
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON CLOSURE. (OPTIONAL)
1
OUTPUT
JP8
UNITS
IN. W.C./PA
JP7
MODE BI/UNI
JP5
VOLT
SV/10V
JP4
7
1
2
3
4
5
6
E
GND
OUT1OUT2OUT3OUT4OUT5OUT6OUT7OUT8DI1DI2DI3DI4GND GND
24 VAC COM
24 VAC COM
24
VAC24VAC24VAC24VAC24VAC
OUT COM
21 VDC OUT
GND E-BUS E-BUS
AI1AI
2
AI3AI
4
AI5AI
6
AI7AI
8
ANALOG
OUT
AO1AO
2
17 18 19 20 21 22 23 24 25 26 27 28 29
L1
(HOT)
L2
31 32 33 34 35 36 37 38 39 40 41 42 43
44
12345 678 9101112 14 1615
13
W7760A
AI
GND
AI
GND
AI
GND
AI
GND
AO
GND
+ –
O
P7640
+ –
O
P7640
+ –
O
H76XX
+ –
M18302B
Vin (Vac)
Gnd
Vo (0-10 Vdc)
PWR
COM
OUT
PWR
COM
OUT
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TEMPERATURE SIGNAL CONNECTIONS ARE NOT POLARITY SENSITIVE.
1
1
2
2
WIRING (FIG. 1 THROUGH 3)
Equipment Damage Hazard. Can damage the device beyond repair.
Disconnect power supply before installation.
NOTE: Wiring to the ZERO terminals is optional.
ZERO
RESPONSE
FAST/STD
JP8
1
2
VOLT
IN. W.C./PA
JP7
JP5
JP4
1
M27291
UNITS
SV/10V
2
MODE BI/UNI
7
6
5
3
4
+
mA
OUTPUT
+
3
L1
L2
PWR OUT COM ZERO
CONTROLLER, METER OR RECORDER
INPUT SIGNAL
+
COMMON
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED. POLARIZED SECONDARY INDICATIONS FOR USE WITH DC POWER
2
SUPPLY ONLY.
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON
3
CLOSURE. (OPTIONAL)
Fig. 1. Wiring for voltage (Vdc) output.
Equipment Damage Hazard. Can damage the device beyond repair.
Do not apply power to output terminal. Permanent equipment damage will result.
VOLT
Fig. 2. Wiring for current (mA) output.
62-0210—07 2
Fig. 3. Typical wiring for three-wire pressure sensor with Vdc output (used with the XL15A Controller).