Honeywell P531, P532UI, P532 Operating Manual

MODEL P531, P532 AND P532UI
maxon.su
FLAME MONITOR
OPERATING MANUAL

TABLE OF CONTENTS

maxon.su
DESIGN FEATURES OVERVIEW ................. 1
Viewing Head Selection.....................................1
Default Settings ................................................. 2
Numerical configuration.....................................2
Alternate – Primary............................................ 2
DEFAULT DISPLAY FOR P532, P532 UI ..... 2
Flame count.......................................................2
Lockout.............................................................. 3
Alternate Indicator .............................................3
Hot Viewing Head Indication .............................3
Primary / Alternate selection..............................3
Using the Prim/Alt switch................................... 3
To reset Modbus Prim/Alt register ..................... 3
Non-Advanced viewing heads ........................... 3
Replacing viewing heads................................... 4
Parity................................................................. 6
20ma output ...................................................... 6
Default (global default) ...................................... 6
FLAME RELAY CONTROL ............................ 6
Flame On, Flame OFF ...................................... 6
Temperature display ......................................... 6
AUTOMATIC SETUP...................................... 6
Fit ...................................................................... 6
Fit procedure ..................................................... 7
Sequence.......................................................... 7
Sequence Procedure ........................................ 7
Filter .................................................................. 8
P531 AND P532UI .......................................... 8
Display for P531................................................ 8
Flame On .......................................................... 8
Flame Signal: .................................................... 8
MENU STRUCTURE ...................................... 4
Viewing Head Set ............................................4
Viewing head parameters (gains and filters) .....4
Channel Set.......................................................4
Associate Viewing head with channel ...............4
FFRT .................................................................5
Delay On ...........................................................5
Analog out gain .................................................5
Alarm Set point..................................................5
Temperature Alarm (Viewing Head) .................. 5
Default (Channel) ..............................................5
Option Menu......................................................5
Address .............................................................5
Baud..................................................................5
Power Reset...................................................... 5
Panel ................................................................6
LOCKOUT ........................................................ 8
Status................................................................ 9
P522 MODE ....................................................9
P522 mode operation........................................ 9
INFRARED GAIN............................................ 9
Gain boundaries................................................ 9
INSTALLATION NOTES............................... 10
Mounting: ........................................................ 10
Power connection:........................................... 10
Remote 20 mA ............................................... 10
Relays ........................................................... 10
Flame Relays .................................................. 10
Alarm Relays................................................... 10
Viewing head (See Figures 1 and 2) ............... 10
Alternative Setting Selection ...........................10
P522 Mode ..................................................... 10
TROUBLESHOOTING NOTES ....................10
maxon.su
If the display is blank:...................................... 10
If only one line is blank:................................... 10
If the viewing head is not listed. .....................11
Channels display LKOUT ................................ 11
The Display flashes “HOT” ............................. 11
CODE display.................................................. 11
MODBUS PROTOCOL .................................12
Legacy Modbus support .................................. 12
Extensions ...................................................... 12
Modbus function support: ............................... 14
CONTACT INFORMATION...........................14
Sales and applications support: ...................... 14
Factory and repairs: ........................................14
SPECIFICATIONS ........................................23
Electrical - Model P531 AC, P532 AC .............23
Electrical - Model P531 DC, P532 DC............. 23
Outputs............................................................ 23
Inputs ..............................................................23
Serial Communications ...................................23
Flame ..............................................................24
Compatibility.................................................... 24
Fuses ..............................................................24
Maintenance.................................................... 24
Cleaning .......................................................... 24
Cable............................................................... 24
Environmental .................................................24
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

DESIGN FEATURES OVERVIEW

The Models P531and P532 feature a new design in flame monitoring technology. The dual processor system is capable of monitoring three viewing heads simultaneously. It can also monitor both UV and IR separately from one S55xx viewing head. In addition, three marginal alarm relays can be configured to pro­vide a secondary indication if the flame count falls be­low set point or if a viewing head temperature reaches 70° C (158° F).
The P532 and P532UI makes use of three scrolling dot matrix displays capable of displaying alphanumeric characters in three different colors as follows:
Red indication for IR
Green indications for UV
Orange indication for mixture of UV and IR
The P531 Signal Processor uses seven discrete LED’s for display. These include:
Tricolor flame strength flashing indicators for each channel.
Relay and status indicators.
In addition to automatic viewing head detection, each channel and viewing head can be associated with two sets of configuration data as follows:
1. Primary: This is the normal viewing head con- figuration.
2. Alternate: This is a set of alternate settings that can be activated by applying a voltage across the alternate select pins for each specific chan­nel or writing configuration to Modbus register.
Automatic set up functionality is a feature whereby each channel can be configured automatically in one of three ways:
1. Auto Fit: The flame is monitored and the gain is adjusted to produce an optimal count of between 1100 and 1300. The flame on will then be set at 800 and flame off will be set to 600.
2. Auto Sequence: The gain will first be adjusted as in the Auto Fit routine and then the flame on and flame off settings will be adjusted. (This requires turning off the flame).
3. Auto Filter: Used for definitive infrared calibra- tion. The sequence procedure (above) is per­formed on each of the 8 filter settings. The best­differentiated filter is chosen and configured for gain, flame on and flame off settings.
The P532 provides the use of a lockable front panel for restricting unauthorized access. The P531 uses the removable P532UI to achieve this feature.
Both Signal Processors have viewing head error de­tection with viewing head lockout capabilities. (this requires user intervention)
A P522 operation mode can be achieved by installing a jumper between the two P522 pins.
Changing viewing head types (while the system is operational) will cause the processor to go into lockout mode. (This is a safety feature).
The P531 and P532 are compatible with RS-422 and Modbus protocol, and are field upgradeable with firm­ware download capabilities.
Viewing Head Selection.
Models S702 / S802 IR and the S706 / S806 UV viewing heads can be connected to Viewing Head #3.
Viewing head #3 will default to be assigned to chan­nel “A”.
Models S552 IR and S556 UV together with the S550 that utilizes both UV and IR sensors can be con­nected to Viewing Head #1 and #2.
Viewing Head #1 will default to be assigned to channel ‘B”.
Viewing Head #2 will default to be assigned to channel “C”.
Note: Alternate channels default to NONE

USER INTERFACE OVERVIEW

The P532 front panel and the P532UI (User Interface) makes use of nine push buttons for operation. Each of these buttons has at least one specific purpose.
All access to the front panel operation is initiated by pressing and holding a button for two seconds (this eliminates the possibility of inadvertent access).
In all cases, only the available options will be dis­played.
Page 1
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
There are three menu branches:
1. Channel menu has all configuration items asso- ciated with the channel.
2. Viewing head menu has all configuration items associated with the Viewing head.
3. Options menu has global and system configu- ration items and information.
Note: The RESET button will return you to the de­fault display from any place in the menu structure. If left for a period of time without intervention, the display will revert back to the default display. (Except during auto calibration modes)
A channel (Primary and or Alternate) can be assigned to a viewing head (or viewing head sensor in the case of advanced S550x viewing heads).
Default Settings
Default choices are available in two menus.
1. Channel (Primary and or Alternate) defaults all parameters under the channel menu except for the viewing head association. The viewing head (or the viewing head sensor) assigned to the defaulted channel will also be defaulted.
Alternate – Primary (during configuration)
The top line will display ALT or PRIM, followed by :
Channel letter (A, B, or C)
OR
Viewing Head number (1, 2, or 3)
The color of this line (top)
Red indicates that this configuration is active at present
Green indicates a non active configuration.
The CHANNEL button will toggle between these two configurations.
Alternate configurations can be activated by applying a voltage across the select terminals.

DEFAULT DISPLAY FOR P532, P532 UI

The default display will appear most of the time. Each line on the display will always be associated with the same channel. The default display will show the flame count for all 3 channels.
IR saturation is indicated by flame counts of 9999
Flame count
Options defaults all channels and viewing heads
2.
as well as resetting the system wide parameters and viewing head to channel association.
Note: The response to YES is always the STORE button.
Numerical configuration.
Green is the current set point stored in memory.
Orange indicates that the setting has been changed
but not saved yet.
The speed of changing numerical values is acceler­ated as the key is held down.
The UP and DOWN buttons are used to change nu­merical values or to jump between configuration pa­rameters.
The SELECT button is used to jump to the next item in all 3 of the menu structures, or to select intermediate parameters that will not be stored.
Normal Flame counts are in the range of 0 to 3500 for the S55x viewing heads and 0 to 3000 for S70x / S80x viewing heads (viewing head #3)
A red display will indicate that channel is associated with the IR only portion of a viewing head’s output. (Saturation is indicated for advanced viewing heads only)
A green display will indicate that channel is associ­ated with the UV only portion of a viewing head’s out­put.
An orange display will indicate that channel is associ­ated with a mixture of both IR and UV from a S550 viewing head.
A Blank Line indicates that no viewing head is associ-
ated with the channel.
This could also indicate that the gain of an associated sensor is zero.
Page 2 
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
A Bar Graph will be displayed in the last digit of the default display.
The graph is proportional to the analog output (20ma) and is affected by the flame count and the analog gain for the channel.
Lockout
LKOUT will be displayed on the panel if a viewing
head error has occurred. (Flame relays will trip and the channels will remain locked out until any button is pressed on the front panel). Lockout will also occur when an unexpected viewing head is detected. This will occur when changing head types or attaching new viewing heads to a system that has been defaulted. LKOUT Cannot be cleared by a power reset (to clear push any button)
Verification of all viewing head and channel pa­rameters is required after a lockout has occurred.
Alternate Indicator
The middle pixel of the rightmost column will be illumi­nated if the Alternate configuration for that channel is currently in operation.
Hot Viewing Head Indication
The configuration is written to Modbus register
The Primary configuration will be used for operation if:
No voltage is present and Modbus is configured for Primary (default)
To reset Modbus Prim/Alt register
Use the serial RS-422 communications port (see Mod­bus register map)
Doing a system default (Options / Default) will set this register to Primary for all channels.
Non-Advanced viewing heads
(S550 models with no following letter designation)
The processor treats non-advanced viewing heads as a single sensor. The UV and IR cannot be separated as with the advanced viewing heads.
To configure for UV only the IR gain should be set to zero, conversely the IR only can be seen if the UV gain is set to zero (note the appropriate color change of flame count display).
These two configurations can be saved in primary and alternate for a single channel and switched when needed.
A warning will be displayed for 1 second in each 4 seconds if a viewing head attached to Viewing Head #1 or Viewing Head #2 terminals exceeds a tempera­ture of 70° C (158° F).
Seeing that the viewing head may not be associated with any particular channel the number of the offend­ing viewing head will be displayed.
Except for this notification, no other action is taken when a viewing head is hot.
Primary / Alternate selection
Two sets of configuration data can be stored and used for each of the 3 channels.
Both the alternate and primary configurations can be viewed and adjusted from the panel.
Using the Prim/Alt switch.
The Alternate configuration is used for operation if:
A voltage is applied across the associated alternate select pins, OR
Individual sensors of advanced viewing heads (and non-advanced viewing heads) can be assigned to channel configurations Primary and Alternate.
A sensor CANNOT be assigned to more than one channel and a primary and an alternate configura­tion all at the same time.
A sensor can be assigned to both Primary and Alter­nate configurations of the same channel (but not to another channel)
OR
A sensor can be assigned to more than one channel (all either primary or alternate).
All channel parameters settings can be configured for both Primary and Alternate usage.
The color of the words PRIM or ALT in the display indicates if it is the current configuration in use.
RED selected.
Green not selected.
Page 3
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
A letter or a number will be displayed after the selec­tion indicating the Channel of Viewing head that is being configured or viewed.
Letters (A, B, C) indicate Channels
Numbers (1, 2, 3) indicate viewing head numbers
Note: Invalid configurations will not be allowed and an “IN USE” warning will be displayed if the sensor is already in use by conflicting configuration. The offending configuration that is using the sensor must be configured to either use a different sensor or use no sensor at all (NONE).
Replacing viewing heads
If a viewing head is replaced with a different type (model), all channels using the head will lockout.
Only one button press is required to clear all lockouts.
If more than one channel or Alternate/Primary configu­ration was using the head then the channel assign­ments will be set to none.
Toggle primary and alternate viewing head parame­ters using the CHANNEL button.
The appropriate configuration can be selected with the SELECT button.
Display of (PRIM/ALT) in Red indicates that the displayed parameter is being used by the channel selection (for the control of the channel relays).
Viewing head parameters (gains and filters)
The valid parameters for the viewing head can be scrolled through using the SELECT button. The cur­rent stored setting will be displayed in green.
To adjust the gains and filters the UP and Down but­tons will be used.
The STORE button must be pressed to store the ap­propriate setting.
Channel Set
Channel selection: (See Flow Chart 2)
Advanced viewing heads will be assigned to Primary for one of the previously used channels only.
All viewing head gains and filters will be set to default values.
Both Primary and Alternate settings will be defaulted.
Note: Changing viewing heads (to that of the same Model) while the unit is operating may cause a lock­out. (Cleared with a press of a button).

MENU STRUCTURE

Three menus are accessible from the front panel. Pressing and holding the appropriate button for 2 sec­onds will open the menu.
Viewing Head Set
Viewing head selection : (See Flow Chart 1)
All attached viewing heads can be scrolled through using the UP and DOWN or the VIEWING HEAD SET buttons.
Scroll between channels “A”, “B”, and “C”, using the UP, DOWN, or CHANNEL SET buttons.
Select the Channel to view or configure with the SE­LECT button. The viewing head associated with the channel will now be displayed.
The top line of the display will indicate either PRIM or ALT along with the channel letter. Toggle between these using the CHANNEL button.
Scroll through the channel menu items using the SE­LECT button.
Associate Viewing head with channel
Associating a viewing head with the channel can be done by scrolling through the viewing heads using the UP and DOWN buttons. Then select the viewing head with the STORE button.
If an advanced viewing head is selected with the STORE button from the channel Viewing head se­lection menu, then another menu choice will appear IR UV.
The viewing head to be accessed can be selected with the SELECT button.
The top line of the display will indicate either PRIM or ALT along with the viewing head number.
Using the UP or DOWN buttons scroll among
1. Both IR and UV will be mixed for this channel
2. IR? - Only IR will be used for this channel
Page 4 
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
3. UV - Only UV will be used for this channel
Temperature Alarm (Viewing Head)
The appropriate choice must be stored with the STORE button.
If association is invalid (the sensor is associated with another channel and Alt) “IN USE” will be displayed.
The channel that is using the sensor must be disas­sociated, either by selecting another sensor for that channel or setting it’s sensor association to NONE.
FFRT
Using the UP and DOWN buttons then STORE the Flame Failure Response time.
FFRT Nominal Opening Maximum FFRT
1 1 sec 2 sec
2 2 sec 3 sec
3 3 sec 4 sec
Delay On
Using UP and DOWN button and STORE the Delay relay on time.
The Alarm relays can be configured to energize if a viewing head with a temperature sensor gets hot (70° C (158° F) or above).
Set both Primary and Alternate Alarm set points to ZERO
Channel A alarm is for Viewing head #1
Channel B alarm is for Viewing head #2
Viewing head #3 has no temperature feature.
To set both Alarm set points for one channel first set one of the set points to zero then press CHANNEL button to access the other. (note the change in the top line of the display).
Default (Channel)
To reset the channel to default values:
Scroll to YES using the UP or DOWN buttons and then press the STORE button. The STORE button must be pressed again to answer the “are you sure?” question.
Option Menu
Analog out gain
Selecting this parameter (with either the UP or DOWN button) will cause the display to change.
The Gain (0 – 100) will be displayed on the line asso­ciated with the channel being adjusted in the color associated with the flame count. There will be a bar graph that is proportional to the analog (20ma) output for that channel. (Selected channel only.)
Adjusting the gain using the UP and DOWN buttons will (in real time) produce outputs on the analog output pins and on the bar graph proportional to the current flame count.
Real time bar graph display of the analog gain set­ting will be calculated from the fame count of the channel selection
Alarm Set point
Using the UP and DOWN buttons then STORE the Alarm set point.
The alarm relay can be disabled by setting this pa­rameter to zero.
System wide configuration parameters
(See Flowchart 3)
Address
Using the UP and DOWN buttons, enter the value for the RS-422 node address. (Default is zero)
The P532 will not respond to the Zero “Broadcast” address.
Baud
Using the UP and DOWN buttons, toggle between baud rates for the RS-422 press then STORE to ac­cept. (Default is 9600)
Power Reset
To reset the power:
Scroll to YES using the UP or DOWN buttons and then press the STORE button. The STORE button must be pressed again to answer the “are you sure?” question. This cycles power to all the viewing heads and restarts both processors.
Page 5
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
Panel
The front panel can be disabled for configuration changes by entering a LOCK CODE. The lock code is
available SRVIUYIWX.
If panel is locked: All parameters are viewable but none can be changed.
Parity
Using the UP and DOWN buttons, toggle between parities for the RS-422 press then STORE to accept. (Default is none)
20ma output
Using the UP and DOWN buttons, toggle between the 0 to 20 ma output or the 4 to 20 ma output then STORE to accept. (Default is 4 to 20).
Default (global default)
To reset the system to default values:
Scroll to YES using the UP or DOWN buttons and then press the STORE button. The STORE button must be pressed again to answer the “are you sure?” question.
All channels will be associated with the default viewing heads, all channel set points will be defaulted, and all viewing head parameters will be set to default values (both Primary and Alternate). Channels will be set to 4 – 20 ma output mode.

FLAME RELAY CONTROL

The main flame relays are controlled by the Flame On and Flame Off settings. The relays are energized once the flame count has exceeded the Flame On setting for Delay ON consecutive seconds. Con­versely the relays are de-energized once the flame count has been less than Flame Off setting for FFRT consecutive seconds. (See flowchart 4)
Flame On, Flame OFF
Hold either of these buttons for 2 seconds to enter the relay menu.
Push the SELECT button at any time to change to the next available channel.
Pushing the CHANNEL button will toggle between ALT and PRIM settings (red display of Prim/Alt will indicate parameter is currently active)
Pushing either the FLAME ON or FLAME OFF will display the current set value in green.
Use the UP and DOWN buttons to change the settings of these parameters and STORE to save the values.
Temperature display
See Configuration control charts 1 and 2
The temperature of a supported viewing head will be displayed when the TEMP button is held for 2 sec­onds. This display will also show the model of the viewing head.
Certain versions of the S550 were produced without a temperature sensor. These will display zero for tem­perature.

AUTOMATIC SETUP

The flame monitor can be configured automatically in two different ways. Seeing that this configuration is for a specific channel it therefore falls under the channel menu.
Only a currently selected channel can be set up automatically, as indicated by a red Prim/Alt display
Fit
The auto fit menu is entered by selecting AUTOMATIC from the channel menu.
The auto fit configuration only affects the gain of the specific sensor selected and Flame On and Flame Off set points).
A channel utilizing 2 simultaneous sensors (S550) cannot be calibrated with this procedure.
It is necessary to have a flame present to use auto set.
The gain will be set so that the flame count for the specific sensor is between 1100 and 1300. The Flame On will be set to 800 and Flame Off to 600.
If this is unobtainable, a message will be displayed indicating the flame is too high or too low. (High flame requires the installation of an orifice).
Note: If a channel is using two sensors a choice will be given to turn one or the other of these sensors off. The corresponding gain will be set to Zero for S550 viewing heads or the sensor will be selected for the specific channel for advanced viewing heads
Page 6
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
Fit procedure
1. Using the channel menu procedure (above) se­lect the AUTOMATIC menu branch by toggling to yes using the UP or DOWN buttons and press STORE.
2. If prompted to turn off a sensor, use the UP or DOWN button to display the sensor that is to be turned off then press SELECT to turn it off.
3. If prompted to UNCAL a channel (see note above), press the STORE button to answer the YES? Query to acknowledge the side effect this will have on the other channel.
4. Using the UP or DOWN buttons, scroll to FIT and press SELECT to select the automatic fit procedure.
5. If TURN FLAME ON is displayed (the flame re­lay is not energized) turn the flame on. Calibra­tion will not continue without the flame relay be­ing energized.
Note: Calibration cannot be done with the flame relay off. Prior to entering the Automatic menu suffi­cient flame/gain combination must be available to ensure the flame relay will be energized.
6. Fit calibration will take less than 17 seconds. A countdown timer will display the maximum re­maining seconds.
A rejected gain calibration can occur if fluctuations of signals are detected during calibration or if the signal is such that the gain cannot be determined automatically.
Note: In certain cases acceptable results may be obtained by manually setting the gain to the proces­sors best guess and then re running the procedure.
Sequence
Auto Sequence configures the gain and relay set points for a specific channel.
When entering the auto sequence configuration, the auto fit procedure (above) will be automatically per­formed first.
Once the proper gain setting has been established, the system will take samples of the flame to eliminate flicker error.
Flame on will be sampled for 60 seconds and flame off (dark) will be sampled for 60 seconds.
Flame sample times can be shortened by pressing a button. However, a minimum of 10 seconds is required. If the RESET button is held for 1 second the procedure will abort.
Sequence Procedure
1. Using the channel menu procedure above, se­lect the AUTOMATIC menu branch by toggling to yes using the UP or DOWN buttons and press STORE.
7. Completion of Fit calibration will display:
AUTO FIT OK! Completion of successful gain cali­bration. New gain parameters are stored and the display will revert to default display.
LOW FLAME SIGNAL Insufficient flame signal to allow for optimal flame count output. Install orifice with larger hole. Original calibration will be re­stored.
HIGH FLAME SIGNAL flame signal too strong to allow for optimal flame count output. Install orifice with smaller hole. Original calibration will be re­stored.
GAIN REJECTED Number. If the unit cannot attain appropriate gain calibration within the time allotted “REJECTED” will be displayed along with the type of gain being adjusted and the processors best guess for gain calibration.
Page 7
2. Using the procedure outlined in Fit Procedure above, follow all steps except SELECT SE­QUENCE from step 4 above.
3. Once the Fit portion of the Sequence calibration has been successfully completed:
4. START BURN YES? Question will be asked, press the STORE button to start the 60-second count down for the flame on (bright) portion of the calibration.
5. Flame samples times can be shortened by pressing a button for 1 second. However, a mini­mum of 10 seconds is required.
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
6. A countdown clock will be displayed on the bot­tom line indicating the remaining time in sec­onds.
7. After the completion of the bright time period a TURN FLAME OFF command will be displayed followed shortly with the FLAME OFF? Question.
8. The Flame must now be turned off.
9. Once the flame is off, pressing the STORE but-
ton to start the dark period counter. (Dark sam­ple times can be shortened by pressing a button for one second. However, a minimum of 10 sec­onds are required.)
10. After completion of the dark sequence portion, an evaluation will take place and a prompt will appear.
If the setting parameters are outside of reasonable bounds, the sequence will be rejected (SEQUENCE REJECTED). The problem should be corrected be­fore another sequence is attempted.
A successful sequence is indicated by all green display.
The Gain will be readjusted at each filter setting and the flame will be sampled for 20 seconds at each level.
This calibration will take about 8 minutes
Flame on will be sampled for 20 seconds and flame off (dark) will be sampled for 20 seconds.
Flame sample times cannot be shortened in the auto Filter procedure. The filter can be aborted by holding the reset button for one second.

P531 AND P532UI

Setup and operation of the P531 is the same as for the P532 when using the P532UI
The P532 UI can be connected to and disconnected from the P531 during operation for monitoring and configuration. Other methods of monitoring and con­figuration include Modbus devices (either through the RS-422 port or the RS-232 port).
Display for P531
The 7 LED’s on the P531 will provide information about status and flame signals for all channels.
Flame On
A marginal sequence is indicated by an orange display.
Top line will display Flame On set point.
Second line will display Flame Off set point
Third line will display the channel that was ad-
justed. In the case of a marginal sequence, a YES prompt will have to be answered with the STORE
11. If the Sequence is rejected, either automatically or by the user, the original settings will be re­stored.
Filter
Auto Filter configures the gain and relay set points for a specific infrared channel
When entering the auto Filter configuration, the auto fit procedure (above) will be automatically performed first.
IF proper gain setting can be established, the system automatically runs a shortened version of the Se­quence (above) configuration on all 8 filter levels.
The display has software indication that the Flame relay is energized
Note: as with the P532 this is not a hardware LED
Flame Signal:
Indication of the flame strength flashes
From one flash every few seconds to rapid flash
The color indicates signal configuration: (channel con­figured for: )
Red indicates IR only
Green indicates UV only
Orange indicates the channel is configured to detect both UV and IR
LOCKOUT
Red Green Red Green ….. Flashes once a second.
The Flame On indicator will be out.
Push the reset button to clear lockouts. (This is the only way to clear a LOCKOUT)
Page 8
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
Status

INFRARED GAIN

A Green heartbeat (one quick green flash each sec­ond) indicates system normal (self check)
A Red / Green heartbeat (alternating color one quick flash each second) indicates one or more viewing heads are Hot (70 deg C or more). Other system functions are normal.
A Red Inverted heartbeat (Red light with one quick flash dark each second): The display processor is not receiving data from signal processor. (Inter­processor communications error.)
A solid color light or no light or any other flash pat­tern indicates a system failure. No LED’s illuminated could also indicate a power loss.

P522 MODE

The P532 can be made to behave like the P522
Connect a jumper between ground and the P522 pin.
The unit will revert to P522 the next time it is powered up.
There is no support for viewing head #3 in this mode.
NOTE: If the jumper is installed or removed and the power is reset then the entire system will revert back to default settings.
Analysis of the Electrical and Digital (Software) gains for the S55xx Viewing Heads.
The Sx55x viewing heads that are IR equipped have a two stage gain system.
There is a 7 step electrical “analog” gain that is used external to the processor to amplify the signal before it enters the processor. Indicated by the left digit.
Once the signal is at the processor, a “digital” software gain can then be applied. Indicated by the last two digits.
These gain adjustments may not be transparent to the user as a slight amount of non-linearity may occur when changing from one electrical gain setting to an­other.
During setting a hysteresis is built in to keep small changes in the digital range. If an analog gain bound­ary is crossed, a finer adjustment can be achieved by going back in the other direction.
Note: illegal values for gain between x00 and x37 (except for low range).
Gain boundaries
P522 mode operation
Channel Viewing Head assignments:
Channel A Only will be operational (both Prim or Alt)
P 522 will be displayed on the second line
Only channel A Flame relays will operate
If power is applied across Alternate 1 pins, the channel will revert to the Channel A Alternate con­figuration parameters.
The bottom line will display the active selection.
The channel A marginal alarm will function inde­pendently.
The alarm can be disabled by setting the trip point to zero.
Separation of UV and IR is supported for advanced viewing heads.
The following table is a list of boundaries, for changing the electrical gain.
IR gain settings transitions for the S55xx viewing heads.
From
0
138
238
338
438 538 599 32
638
To
99
199
299
399
499
699
Electrical gain
1
2
4
8
16
64
Page 9
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

INSTALLATION NOTES

Mounting:
The P531 or P532 Signal processor should be mounted (using the 4 holes in the corners of the base) to a ver­tical surface in a location with free air circulation on the top, bottom and sides.
Power connection:
DC units should be connected to a stable 24-volt DC supply.
AC units should be connected to an AC mains supply
Battery backup can be connected to the +24 BATT terminal.
To prevent discharging the battery, its voltage must be less than the main supply (for DC units) or less than 24 volts (for AC units). This can be adjusted using series silicon diodes to provide a voltage drop of 0.7 volts each.
Remote 20 mA
Viewing head (See Figures 1 and 2)
Viewing heads are connected to the appropriate termi­nals using the compatibility list.
Source Impedance Resistors 470 Ohm ¼ Watt must be installed between SC and SGND for all cable runs to S55x viewing heads between 300 and 700 ft.
Alternative Setting Selection
For each of the 3 viewing heads:
Connect +Sel and ground through a switch from a DC supply for selecting alternate viewing head settings.
The +24v OUT terminal can be used to supply power for this purpose (on AC units).
P522 Mode
To Use the P532 in Reduced Feature mode install a jumper between the P522 mode terminal and ground.
Then power must then be cycled.
Current meters can be connected to the remote meter outputs with the RET as a common return.
Relays
(See Figures 4 and 5)
Self-check contacts are provided for both normally open and normally closed positions.
Connect the Self-check actuator to whichever of these terminals is required.
The Self-check relay is internally interlocked with the flame relays so that whenever the Self-check relay opens all of the flame relays will open as well.
Flame Relays
Each of the flame relays provides 2 sets of normally open and normally closed positions.
Connect the Burner supply to the required flame termi­nals.
WARNING: Do NOT connect P522 mode terminal to a power source.

TROUBLESHOOTING NOTES

If the display is blank:
Unplug all viewing heads (should display “NO VH# DETECTED”).
If display still blank then:
Hold the Reset button for 2 seconds:
If address is displayed then reset factory defaults:
Else return unit to factory for service.
If only one line is blank:
Check that the channel is associated with an opera­tional viewing head.
Push channel until the channel letter is displayed then push select.
Alarm Relays
Alarm contact is a normally open contact that will pro­vide a connection to it’s RET when the flame count falls below the set point. Or (if configured) the viewing head temperature exceeds 70° C (158° F). Connect the Alarm actuator to these terminals.
Scroll through viewing heads and store the one re­quired.
If the Channel is associated with a viewing head, check that the viewing head’s gain is not set at zero.
Page 10
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
If the viewing head is not listed.
If the viewing head is not listed as a choice in either the Viewing head or the channel branch:
Check that the viewing head is compatible with the P531/P532.
Check that the viewing head cable is in good condi­tion.
Verify that 24 volts DC is present at the cable head.
Note: power to VH #3 is pulsed when no viewing head has answered. Check that the viewing head is operational.
A meter or Oscilloscope on the SC with reference to ground will show:
At least 20% duty cycle at 15 volts Peak for S55x viewing heads.
At least 10% duty cycle at 24 volts Peak for S70x/S80x viewing heads.
With S70x and S80x viewing heads the Green LED will flash once per second.
If the unit is not restored by cycling the power and set­ting factory defaults:
Record the numbers on the display.
Remove the unit from service and return it to the factory for failure analysis and repair.
S55xx viewing heads will show a number on the display.
Viewing heads without numeric displays will flash if flame signal is present.
Substitute a known good viewing head using a known good cable.
Channels display LKOUT
Channels display LKOUT that will not stay cleared (after pressing any key).
Viewing head problem or cable problem. See above steps. (Reset OPTION defaults).
The Display flashes “HOT”
Indicates that the viewing head listed is nearing or exceeded maximum operational temperature. The system will try to continue operating as long as it can and the flashing display is only a warning.
CODE display.
This is an indication of a processor failure.
It can be caused by a power failure during a memory store operation or other more serious fault.
Page 11
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

MODBUS PROTOCOL

Legacy Modbus support
* 40001 Flame Count (active channel in 522 mode) other wise ZERO * 40002 Processor Status R/O 0x or Discrete * 000001 viewing head channel selected 0=Chan A (same pin 4 VH1 gain select) * 000002 flame on relay status (not used for P532) (reads zero) * 000003 Processor Lockout status 0 = lockout (any channel locked out) * 000004 Panel access disabled 0 = disabled * 000005 4 - 20 ma output 0 = 0 to 20 ma output

Primary

* 40003 Flame On Channel A (0 -> 2999) * 40004 Flame On Channel B (0 -> 2999) * 40005 Flame Off Channel A (0 -> 2999) * 40006 Flame Off Channel B (0 -> 2999) * 40007 Gain Channel A 20ma Gain Primary (0 -> 99)(0 – 100 for P532) * 40008 Gain Channel B 20ma Gain Primary(0 -> 99) (0 – 100 for P532) * 40009 IR Analog Gain VH 1 (portion of total IR gain) (R/O P532) * 40010 IR Digital Gain VH 1 (portion of total IR gain) (R/O P532) * 40011 IR Filter VH 1 (unsigned char) (1 -> 8) * 40012 UV Gain VH 1(unsigned char) (0 -> 99) * 40013 IR Analog Gain VH 2 (portion of total IR gain) (R/O P532) * 40014 IR Digital Gain VH 2 (portion of total IR gain) (R/O P532) * 40015 IR Filter VH 2 ( 1 -> 8) * 40016 UV Gain VH 2 ( 0 -> 99 ) * 40017 Viewing head type Viewing head #1 R/O * 40018 Viewing head type Viewing head #2 R/O * 40019 Temperature Channel A R/O * 40020 Temperature Channel B R/O * 40021 Time Delay (upper nibble Ch B) Lower nibble channel A (Read change Write) * 40022 FFRT (upper nibble Ch B) Lower nibble channel A (Read change Write) * 40023 Software Versions R/O * 40024 Model number P522 version 5.2 and earlier will read 0 P522 version 5.3 and later will read 520

Extensions
(for P531/P532 (RS-422) to the Modbus protocol)
* 40024 Model R/O P532 will read 532 * 40025 Flame Count channel A (R/O) * 40026 Flame Count Channel B (R/O) * 40027 Flame Count Channel C (R/O) * 40028 Flame On Channel C Primary * 40029 Flame Off Channel C Primary * 40030 Gain Channel C 20ma Gain Primary (0 -> 100) * 40031 IR gain VH 3 (1 to 9) Primary * 40032 UV Gain VH 3 (Total UV gain for P532) (unsigned char) (1 -> 9) Primary * 40033 Viewing head #3 type R/O * 40034 Time Delay Channel C Primary * 40035 FFRT Lower nibble channel C Primary * 40036 IR Gain Viewing Head #1 (primary) (equivalent to 40009 and 40010) * 40037 IR Gain Viewing Head #2 (primary) (equivalent to 40013 and 40014)

Alternate viewing head #1

* 40038 IR Gain VH 1 * 40039 IR Filter VH 1 * 40040 UV Gain VH 1

Alternate viewing head #2

* 40041 IR Gain VH 2 * 40042 IR Filter VH 2 * 40043 UV Gain VH 2

Alternate viewing head #3

* 40044 IR Gain VH 3 * 40045 UV Gain VH 3

Alarm set points Primary

* 40046 Alarm set point Channel A (0 -> 2999) * 40047 Alarm set point Channel B (0 -> 2999) * 40048 Alarm set point Channel C (0 -> 2999)

Advanced viewing head flame counts for S550A and later

*40049 Viewing head #1 IR component *40050 Viewing head #1 UV component *40051 Viewing head #2 IR component *40052 Viewing head #2 UV component

*40053

Channel "A" R/O

* 000001 bit 0 flame relay status * 000002 bit 1 alarm relay status * 000003 bit 2 channel Autoset (Primary or Alter­nate) * 000004 bit 3 channel lockout (Primary or Alternate) * 000005 bit 4 Primary active = 1 Alternate active = 0 * 000006 * 000007 * 000008

*40054

Channel "B" R/O

* 000001 bit 0 flame relay status * 000002 bit 1 alarm relay status * 000003 bit 2 channel Autoset (Primary or Alter­nate) * 000004 bit 3 channel lockout (Primary or Alternate) * 000005 bit 4 Primary active = 1 Alternate active = 0 * 000006 * 000007 * 000008

*40055

Channel "C" R/O

* 000001 bit 0 flame relay status * 000002 bit 1 alarm relay status * 000003 bit 2 channel Autoset (Primary or Alter­nate) * 000004 bit 3 channel lockout (Primary or Alter­nate) * 000005 bit 4 Primary active = 1 Alternate active = 0 * 000006 bit 5 * 000007 bit 6 * 000008 bit 7
Page 12
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

*40056

Channel "A” Primary Read/Write

* 000001 bit 0 * 000002 bit 1 * 000003 bit 2 * 000004 bit 3 * 000005 bit 4 (bit 4 and 5 are viewing head attached to channel) * 000006 bit 5 0 ,0 = no viewing head 0,1 = vh #1 ….etc. * 000007 bit 6 IR // for Advanced heads * 000008 bit 7 UV // for Advanced heads

*40057

Channel "B” Primary Read/Write

* 000001 bit 0 * 000002 bit 1 * 000003 bit 2 * 000004 bit 3 * 000005 bit 4 (bit 4 and 5 are viewing head attached to channel) * 000006 bit 5 0 ,0 = no viewing head 0,1 = vh #1 ….etc. * 000007 bit 6 IR // for Advanced heads * 000008 bit 7 UV // for Advanced heads

*40058

Channel "C" Primary Read/Write

* 000001 bit 0 * 000002 bit 1 * 000003 bit 2 * 000004 bit 3 * 000005 bit 4 (bit 4 and 5 are viewing head attached to channel) * 000006 bit 5 0 ,0 = no viewing head 0,1 = vh #1 ….etc. * 000007 bit 6 IR // for Advanced viewing heads * 000008 bit 7 UV // for Advanced viewing heads

*40059

Pin status R/O

* 000001 * 000002 * 000003 * 000004 bit 3 522 mode pin PORTC.3 * 000005 bit 4 Channel A Primary = 1 Alt = 0 PORTC.4 (same as 400002 00001) * 000006 bit 5 Channel B Primary = 1 Alt = 0 PORTC.5 * 000007 bit 6 Channel B Primary = 1 Alt = 0 PORTC.6 * 000008

*40060 SERIAL Number R/O *40061 ID number READ and WRITE (Signed Integer) *40062 Operational time each unit = 2 hours of continuous power on time (R/O)
*40063 Flame On Channel A alternate (0 -> 2999) *40064 Flame On Channel B alternate (0 -> 2999) *40065 Flame On Channel C alternate (0 -> 2999) *40066 Flame Off Channel A alternate (0 -> 2999) *40067 Flame Off Channel B alternate (0 -> 2999) *40068 Flame Off Channel C alternate (0 -> 2999)

*40069

Channel "A” Alternate Read/Write

* 000001 bit 0 * 000002 bit 1 * 000003 bit 2 * 000004 bit 3 * 000005 bit 4 (bit 4 and 5 are viewing head attached to channel) * 000006 bit 5 0 ,0 = no viewing head 0,1 = vh #1 ….etc. * 000007 bit 6 IR // for Advanced viewing heads * 000008 bit 7 UV // for Advanced viewing heads

*40070

Channel "B” Alternate Read/Write

* 000001 bit 0 * 000002 bit 1 * 000003 bit 2 * 000004 bit 3 * 000005 bit 4 (bit 4 and 5 are viewing head attached to channel) * 000006 bit 5 0 ,0 = no viewing head 0,1 = vh #1 ….etc. * 000007 bit 6 IR // for Advanced viewing heads * 000008 bit 7 UV // for Advanced viewing heads

*40071

Channel "C" Alternate Read/Write

* 000001 bit 0 * 000002 bit 1 * 000003 bit 2 * 000004 bit 3 * 000005 bit 4 (bit 4 and 5 are viewing head attached to channel) * 000006 bit 5 0 ,0 = no viewing head 0,1 = vh #1 ….etc. * 000007 bit 6 IR // for Advanced viewing heads * 000008 bit 7 UV // for Advanced viewing heads
*40072 Gain Channel A 20ma Gain Alternate (0 – 100 ) *40073 Gain Channel B 20ma Gain Alternate (0 – 100 ) *40074 Gain Channel C 20ma Gain Alternate (0 – 100 )

Alarm set points Alternate

*40075 Alarm set point Channel A (0 -> 2999) *40076 Alarm set point Channel B (0 -> 2999) *40077 Alarm set point Channel C (0 -> 2999)

Alarm set points Alternate

*40078 Time Delay (upper nibble Ch B) Lower nibble channel A (Read change Write) *40079 FFRT (upper nibble Ch B) Lower nibble channel A(Read change Write) *40080 Reserved (do not write to this location) reads zero. *40081 Time Delay Channel C Alternate *40082 FFRT Channel C Alternate

*40083

Alternate / Primary Switch register Read/(Write RS-422 only)

* 000001 * 000002 * 000003 * 000004 * 000005 bit 4 Channel A Primary = 1 Alt = 0 * 000006 bit 5 Channel B Primary = 1 Alt = 0 * 000007 bit 6 Channel B Primary = 1 Alt = 0 * 000008
Page 13
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
To reset factory defaults for P531 front port write 30064 (RS-
232)
*40084 Error code RS422 port only (P531 front port is unde­fined)
P531 front panel access only (RS232) *40085 Baud for the RS422 port *40086 Parity for the RS 422 port *40087 Modbus Address for the RS 422 port
Modbus function support:
* 03 Holding Register Read * 06 Preset Single Holding Register * 16 Preset Multiple (Maximum 5 consecutive locations per message)
Note: If writing multiple presets a failure message may occur if one of the presets does not fall within parameters. Presets before the invalid data will be written correctly to the register. All parameters after invalid parameter are ignored and an “Illegal data value” message is returned.
 
 
Page 14
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
Channel V H # Sensor Flame
ON
A Prim.
A Alt.
B Prim.
B Alt.
C Prim.
C Alt.

TABLE 1: Temperature Configuration Control Chart 1

Flame
OFF
FFRT Time
Delay
Analog
Gain
Alarm
IR Gain IR Filter UV Gain Channel Association
VH#1 Prim.
VH#1 Alt.
VH#2 Prim.
VH#2 Alt.
VH#3 Prim. N/A
VH#3 Alt N/A

TABLE 2: Temperature Configuration Control Chart 2

Page 15
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

FIGURE 1: Wiring and connections S55xx Viewing Head

FIGURE 2: Model 700 and 800 viewing head cable connections

Page 16
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
MODULAR
CONN.
1 NC WHI BLU NC NC -
2 TX- BLK YEL RD (A) FROM
3 TX+ RED GRN RD (B) FROM
4 RX- GRN RED TD (A) TO
5 RX+ YEL BLK TD (B) TO
6 GND BLU WHI GND GROUND GND
+12VDC POWER +12VDC
CAUTION: The order of the colors in the cable can be TYPE A or TYPE B. Check colors at the connector.
FIGURE 3: Wiring of RS-422 to RS-232 Converter to processor
Page 17
SCHEM
LABEL
COLOR TYPE A
COLOR TYPE B
INTERFACE
LABEL
DESCRIPTION POWER
SUPPLY
-
PROCESSOR
-
PROCESSOR
-
PROCESSOR
-
PROCESSOR
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

FIGURE 4: P532 DC Wiring Diagram

Page 18
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

FIGURE 5: P532 AC Wiring Diagram

Page 19
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
5.80"
TYP
P531
1.63"
TEMP
TEMP
#1 V. H.
#2 V. H.
RESET
OPTIONS
MODEL 532UI
SELECT
FLAME
PRESS BUTTONS 2 SECONDS TO ACTUATE
TOP
VIEW
P532UI
TOP VIEW
P531
P531
TOP VIEW
FLAME MONITOR
CHAN A
CHAN B
ON
FLAME
FLAME
SIGNAL
CHAN C
SET
SET
CHANNEL
VIEW HEAD
ON
RESET
STATUS
FLAME MONITOR
OFF
FLAME
STORE
USER INTERFACE
TEMP
TEMP
#1 V. H.
#2 V. H.
RESET
MODEL 532
4.25" TYP
P532
TOP VIEW
4.19" TYP
SELECT
FLAME
PRESS BUTTONS 2 SECONDS TO ACTUATE
OPTIONS
SET
SET
CHANNEL
VIEW HEAD
ON
FLAME MONITOR
OFF
FLAME
STORE
P532 FRONT VIEW P531 FRONT VIEW P532UI FRONT VIEW
TYP
4.56"
FIGURE 6: P531, P532, P532UI Dimensions
Page 20
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
Viewing Head Setup
Channel
(Prim/Alt)
Select
IR Gain UV Gain IR Filter
#2 Temp #1 Temp
STORE
- - - - - -

FLOWCHART 1: Viewing Head Set, Channel Set and Option

CHAN SET
Viewing Head Selected
“1, 2 or 3”
VH Sell

FLOWCHART 2: Channel Set

FFRT Alarm Default Auto
#1 Temp.
Select
Delay On
#2 Temp #1 Temp
Analog out
Channel Prim/Alt
STORE
- - - - - -
Page 21
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
Address
#2 Temp #1 Temp
Options
STORE
- - - - - -
Select
Baud Power Reset Default0-20 4-20ParityPanel
#1 Temp
STORE
- - - - - -
Reset Heads
And
Processor
#1 Temp
STORE
- - - - - -
Enter Code
Lock/Unlock
Routine
#2 Temp #1 Temp
STORE
- - - - - -
#1 Temp
STORE
- - - - - -
Reset
System
Defaults

FLOWCHART 3: Option Menu - System wide configuration parameters

Select
(Channel)
Flame On Flame Off
#2 Temp #1 Temp
STORE
- - - - - -
Channel
(Prim/Alt)

FLOWCHART 4: Flame On / Flame Off

Page 22
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su

SPECIFICATIONS

Models P531, P532 and P532 UI

Electrical - Model P531 AC, P532 AC
Primary Input Power 85 – 264 VAC, 47-63 Hz
Battery Backup Voltage 24 VDC (voltage above 24 volt will be the power source)
Electrical - Model P531 DC, P532 DC
Primary Input Power 24 VDC
Battery Backup Voltage 24 VDC (power source is taken from the highest voltage)
Power (DC unit tested at 100 ms sampling time)
13.2 Watts max. Average (including 3 viewing heads)
16.2 Watts max. Peak (including 3 heads in normal operation)
Outputs
Flame Relay 3 channels of 2 Form C Contacts (DPDT)
Self-Check Relay 1 channel of 1 Form C Contact (SPDT)
Contact Rating 5A at 32 VDC and at 250 VAC
Alarm Relays 3 channels of 1 Form A Contact (SPST-N.O.)
Contact Rating 2 A at maximum 250 VDC or 230 VAC
Analog Flame Signal 0 – 20 mA or 4 – 20 mA 1000 ohm maximum resistance
Power To Viewing heads 100 mA (maximum average) 24 VDC (rated) Current limited to 200 mA
24v output 24-volt output 50 mA For Instrumentation use only Provided for use with Isolated Select inputs
Inputs
Isolated Select 7.5 30 VDC Input Resistance 3900 ohm
Aux Mode Connect to ground only (WARNING: do not apply Power) Sources 1 mA at 5 VDC
Viewing head Signal (for 55x and 70x) 26-Volt P-P Maximum, 1 MA
Serial Communications
RS-422 / 4 wire (two twisted pair) Baud 38400, 19200, 9600 or 4800
Parity None, Even or Odd
Protocol Modbus (RTU)
Page 23
MODELS P531, P532 AND P532UI OPERATING MANUAL
maxon.su
RS-232 (P531 front panel port only) Baud 19200 Parity None Protocol Modbus(RTU) fixed address of 64
Flame
Maximum flame detector response time 5 second
Minimum flame detector self-checking rate 1 second
Maximum flame failure “lock-out” time 2 to 4 seconds (adjustable)
Maximum flame failure response time 2 to 4 seconds (adjustable)
Signal for presence of flame Flame on set point (adjustable)
Signal for absence of flame Flame off set point (adjustable)
No large Maximum flame signal will cause lost flame indication.
Compatibility
Viewing head #3 S702, S706, S802 or S806 (and -PH and –HF versions)
Viewing head #1 or #2 S550x, S552x, S556x (and –PF versions)
Fuses
No user serviceable components are inside.
Self-resetting fuses are provided internally on the following connections:
+24 PWR DC input voltage supply (DC units only) +24 BATT Battery input voltage supply These require cooling off period (of no load) to reset.
Cleaning
Turn power off before cleaning.
Only wipe Panel front with a soft cloth (dry or slightly dampened with water).
Cable
Connection from the Signal processor to the viewing heads shall use approved cable: Cable can be Instrument Tray cable with CIC C22.2 No. 239 certification C330 Or must be run inside of Conduit (with properly sealed ends).
Environmental
Ambient Temperature -40° C to 60° C (FM) or 0° C to 52° C (CSA)
Humidity non-condensing Maximum 80% for temperatures below 31° C Decreasing to 50% maximum at 40° C and above
Vibration +1 g at 10 to 150 Hz
Rev.0405
Page 24
Loading...