Honeywell P520 User Manual

Put Bar Code Here
P520 Signal Processor

SPECIFICATIONS

Electrical Ratings
Input Power: 22 - 26VDC, 130mA (plus 100mA for each
Viewing Head.)
Battery Backup: 24VDC, 130mA (plus 100mA for each
Viewing Head.) Main Voltage > Battery Voltage
Ambient Temperature:
0°C to 52°C (32°F to 125°F) CSA Rating 0°C to 60°C (32°F to 140°F) FM Rating
Outputs:
Flame Relay: 2 Form C Contacts (DPDT) Self-Checking Relay: 1 Form C Contact (SPDT) Contact Ratings: 5A at 30 VDC, 125 VAC and 277 VAC
Max switching voltage 220Vdc, 250Vac
Analog Flame Signal: 0 to 19.8mA current output for
remote meters and 4 to 19.8mA output. (360 ohm max. resistance.)
Power to Viewing Head:
+26VDC maximum, fused 0.25A (self-resetting) +14.3VDC pulsing 0.2 seconds ON, 0.8 seconds OFF
USER MANUAL

APPLICATION

The Honeywell P520 is a rack mounting signal processor that is compatible with viewing heads in the S5XX and S55XB/BE series. These include models S506, S509, S511 and S512, and the advanced viewing head series models S550B/BE, S552B/BE and S556B/BE. There is only one model of the P520 available, which is DC powered. A rear backplane PC Board is required for termination (order part number REARPCB separately for initial installation).

FEATURES

• Rack mounted system, designed to conform to the DIN 41494 19 inch card frame system
• 3U high and 21HP wide, or 5.06 x 4.18 inches with a length of 8.66 inches (220mm)
• Once rack mounted, together with a power supply and appropriate viewing head makes up a complete flame monitoring system
Inputs:
Channel Select (Isolated Input):
7.5-30VDC range Input resistance 3900 ohms 26VDC maximum, 6.4mA 10VDC, 2.3mA Flame Signal from Viewing Head (Isolated Input):
7.5-30VDC range Input resistance 3900 ohms
13.6VDC, 3.2mA
Serial Communications:
RS-422 (Differential) 4800 or 9600 baud (user selected) 4 wire / 2 twisted pair
Cable (between viewing head and signal processor):
4 conductor, #16 AWG or #18 AWG, one wire shielded with
braided shield for flame signal. Honeywell C328 cable is recommended.
66-2066-01
P520 SIGNAL PROCESSOR
M33219
4-3/16 (106)
5-1/16
(129)
M33226
9-3/32 (231)
5-1/16
(129)
35/64
(14)
Fig. 1. P520 front faceplate dimensions.
Fig. 2. P520 side view dimensions.

INSTALLATION

When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced, flame safe­guard control technician.
4. After installation is complete, check out product opera­tion as provided in these instructions.
66-2066—01 2

Grounding and Shielding

NOTE: Installer must be a trained, experienced flame
safeguard service technician and should be familiar with the equipment operation and limita­tions and be aware of any applicable local codes and regulations.
1. Connect a safety ground to the viewing head housing (if
applicable).
2. The viewing head and all associated cable/conduit must be at least 12 inches (31 cm) from any source of high energy or voltage (for example, igniter equipment).
P520 SIGNAL PROCESSOR
3. Install a ground wire from the ignition transformer case to the igniter assembly.
4. Ensure all igniter wires and cables show no signs of wear. Replace any igniter cables or wires that are frayed or cracked.
5. The viewing head must be electrically isolated from the burner front. a. Electrical isolation can be accomplished by install-
ing an Ultem nipple or an Ultem locking coupler adapter in conjunction with a locking coupler between the viewing head flange and the burner mount.
b. The purge air line should also be isolated from the
viewing head. This can be accomplished by install­ing any insulating material, for example a rubber hose, in between the purge air line and the viewing head.
6. On the terminals going to the viewing heads on the back of the P520, the terminals marked GND go to pin 5 of the S5XX and S55XB viewing head plug and to the des­ignated ground pin for the S55XBE viewing head plug. Pin 5 of the S5XX and S55XB and the ground pin for the S55XBE viewing head male receptacles have an inter­nal tab that grounds this connection to the viewing head housing. The terminal marked GND connects to the chassis ground of the P520. This ground is made through the internal PCB to the metal base of the P520.
It is important that good grounding practices be followed when connecting power supplies. Interference problems can occur if the power supply chassis and the P520 chassis are at a different ground potential than the viewing head housing, which will be at a ground potential associated with the burner front. In these situations, the Honeywell viewing head effectively supplies a plant ground between the burner front and the panel enclosure. If there is a large potential difference between these points, considerable current can flow through the viewing head cable, which can, in turn, damage the P520 signal processor or the associated power supply.

Card Frames

Four card guides are required for each P520 module; therefore, a total of sixteen card guides would be required to mount four P520 modules. Card guides are available as off the shelf parts and are not available from Honeywell.
The resulting rack will require spacers for the top and bottom of the rear backplane PCB. Card guides are required as well for installation. Spacers and card guides are available from electronic vendors and are not available from Honeywell.
A half-card frame, or “half rack” (9.5 inches wide) may be used as an alternative to the 19-inch card frame. A half rack will mount two P520 modules.

Wiring the Rear PC Board

A diagram of the rear backplane circuit board is shown in Fig.
1. The relay outputs are located on the nine-contact terminal block located on the upper right of the board
RC C refers to the common terminal of the self-checking relay. There is only one pair of contacts used for the self-checking function. Here, the designation ON refers to the self-checking taking place in a normal manner. OFF indicates a failure in the viewing head or processor resulting from
- the internal or external hardware
- electronic critical component failure
- the power to the unit is OFF – the most likely condition
The horizontal set of six terminals (top left) is used for the main power into this plug-in module (PWR IN). Each designated terminal is a double terminal, or pair, so that the wiring from the power supply can be “daisy chained” from one P520 to the next without having to twist wires together into one termination.
The pair designated BAT is for battery backup, if used. The backup battery, if used, should be 24 volts, to ensure that the 24VDC power feeding the P520 will not feed back into the battery. In other words, no current will flow from the battery as long as voltage of the main power supply is above that of the battery. The negative side of the battery goes to the GND terminal on the right.
Fig. 1 shows how these terminals are connected inside the P520. Note the two fuses marked F1 and F2. F1 is the main power fuse for the signal processor as well as the viewing head(s), and is rated at .75 Amp. Fuse F2 feeds only to the viewing head(s), and is rated at .25 Amp. Each viewing head draws about 100mA, so this output can supply up to two viewing heads. On all currently manufactured units, these fuses are self-resetting types, and will recover from an overload automatically after power is removed from the P520 for 10 seconds.
Just below the six-pin PWR IN terminals are two, five-pin vertically-mounted viewing head terminals identified as V.H. A. and V.H. B. If only one viewing head is used, you must wire to the V.H. A. terminals. Below the V.H. A. terminals are two terminals marked V.H. SEL (viewing head selector relay). Energizing this connection with 24VDC will cause the relay on this PCB to switch to viewing head B.
Only the viewing head signal wire (SIG) and the signal ground wire (SIG GND) are switched with this changeover relay; the 24VDC and power ground circuit is not disturbed. Make sure that the viewing head signal wire and signal ground (braided shield in the four-conductor cable) are both connected, because this ground connection is the only return path for the signal and self-checking circuit. The 24VDC used to switch this relay can be connected without regard to polarity. The two terminals marked V.H. SEL go directly to the relay coil.
The two-pin terminal to the right of V.H. SEL designated CHAN SEL is used for selecting channel A or channel B on the P520. Energizing this pair of terminals causes the B channel to be selected.
3 66-2066—01
P520 SIGNAL PROCESSOR
P520
F1/.75A
M33217
F2/.25A
P520 RELAYS
FLAME RELAY
RF
RF
RC
SELF CHECKING RELAY
PWR IN
BAT
+26VDC
GND
RF C
OFF
ON ON
OFF
RF C
ON
OFF
RC C
GND
+V SC
SIG
SIG
GND
+
GND
REMOTE METER V.H. SEL
CHAN SEL
TX+ TX- TX+ TX-
RX- RX+ RX- RX+
Fig. 3. Rear PCB terminal wiring.
Polarity must be observed when wiring this connection (the positive terminal is on the top). This is an isolated input, so two wires are required. Any DC voltage from 7.5 to 30 may be used. The current required will depend upon the voltage, because this is a photocoupler interface circuit with a 3900 ohm resistor feeding the LED light source.
For example: a 26VDC voltage will result in a current flow of 25/3900 =.0064 Amp.
If flame is being detected and the channels are switched, the flame relay will remain energized for one cycle regardless of the new set points, allowing channel changes “on the fly,” so to speak. If the new flame OFF set point is equal to or greater than the current signal count, then the flame relay will de­energize on the subsequent cycle.
The remaining two-pin terminal designated REMOTE METER (to the left of the V.H. SEL terminals) is for the remote meter connection. This output is a current-driven signal that ranges from 0 to 20mA for remote meters, and can be switched to a range of 4 to 20mA (refer to section 4-20mA REMOTE OUTPUT). Connect the terminal marked “positive” to the positive meter terminal. This current signal can be used with a volt meter by feeding the signal to a resistor connected to the ground. The voltage developed across the resistor will follow Ohm’s law V=IR.
For example: a 3-volt meter can be used with a resistor of 3/ .02 = 150 ohms, which will result in a full-scale reading of 3 volts for a 20mA output.
The terminals called TX+, TX-, RX+, and RX- (at the bottom of the PCB) are used for the serial communication link. They are also in pairs to accommodate “daisy chaining,” but the pairs are arranged for twisted pairs instead of adjacent redundancy. The serial communication is achieved by using ASCII character code transmission at 4800 through the USB port on the host computer. The P520 uses RS-422 data transmission which is over two, twisted pairs that are differentially transmitted and received, allowing long wire runs to be used through noisy environments. A USB to RS422 converter must be used to communicate with the P520, and the connections are made to the terminals marked TX+, TX-, RX+ and RX-. The transmitting, twisted pair goes to the TX terminals, and the receiving, twisted pair goes to the RX terminals.
NOTE: The terms “transmit” and “receive” used here
with respect to the P520 will be reversed with respect to the converter connection on the host computer. Refer to later sections in this manual for a detailed description of the software and how it is to be used with the P520.
66-2066—01 4
P520 SIGNAL PROCESSOR
M33509
CABLE CLAMP
CONNECTOR WITH REAR COVER REMOVED
CONNECTOR JACKSCREW
FINAL ASSEMBLY
OPTIONAL LTA5XX ADAPTER
CONNECT SHIELD TO TERM 3 USE SHRINK TUBING
WIRING SIDE VIEW – COVER REMOVED
P520
RED
GREEN
BLACK
WHITE
SHIELD
C20
C28
A24
A26
A28
+24 VDC
GND
SHUTTER DRIVE
GND
SIGNAL
R
4
3
2
1
5
G
W
B

Wiring the Viewing Head

Wiring of the viewing head is made to the terminals on the rear backplane PCB. These terminals are described as follows:
Table 1. Terminal Descriptions.
Terminal Description
+V 24VDC power to viewing head
GND Power Ground
SC Self-check/shutter drive signal to viewing head
SIG Flame signal from viewing head
SIG GND Signal ground
Fig. 4 and 5 show four-conductor cable to the viewing head. Note that the flame signal wire going to terminal SIG is shielded, and the shield is terminated at both ends of the cable to SIG GND.
IMPORTANT
Source impedance resistor required at the signal processor between SC and SIG GND terminals for proper signal trans­mission. For resistor value, refer to Wiring of Viewing Head section.
Fig. 4. Viewing head wiring.
5 66-2066—01
Loading...
+ 11 hidden pages