Honeywell MP953C-F Data Sheet

MP953C-F
Pneumatic Actuators
SPECIFICATION DATA
• Rolling diaphragm for long life and low hysteresis
• Easily attached to valve
• May be installed after piping valve
• Slide lock feature permits simple engagement to valve stem
• Direct- or reverse-action control
• Models available with positive positioning relay
MP953EMP953C
GENERAL
MP953 Pneumatic Actuators operate V5011 and V5013 Valves to provide proportional control of steam or hot and cold liquids of HVAC systems.
RC145 RC146
Copyright © 1993 Honeywell Inc. • All Rights Reserved
77-3001
MP953C-F PNEUMA TIC ACTUAT ORS
DESCRIPTION
MP953 Pneumatic Actuators operate V5011 and V5013 Valves to provide proportional control of steam or hot and cold liquids of HVAC systems.
SPECIFICATIONS
Models:
Diaphragm
Model Action
MP953C Direct No 5 (130) 11 3/4 (19) 2 to 7 (12 to 50) or
MP953D Reverse No 7 (180) 21.6 3/4 (19) 3 to 7 (20 to 50) or
MP953E Direct Yes 5 (130) 11 3/4 (19) 3, 5 or 10
MP953F Reverse Yes 7 (180) 21.6 3/4 (19) Same as MP953E
1
Start point is adjustable from 1-1/2 (10) to 13 psi (90 kPa) in 1/4 psi (1-1/2 kPa) increments.
Maximum Actuator Diaphragm Temperature:
MP953C and E: 160F (71C) MP953D and F: 200F (93C)
Maximum Positive Positioner Diaphragm Temperature:
160F (71C)
Maximum Safe Operating Pressure:
25 psi (172 kPa)
Positive
Positioner
Diameter in
Inches
(mm)
8 (203) 33 3/4 (19) 4 to 11 (30 to 75) or
13 (330) 99 3/4 (19 or 1-1/2 (38) 4 to 11 (30 to 75) or
8 (203) 33 3/4 (19) or 1-1/2 (38)
13 (330) 99 3/4 (19) or 1-1/2 (38)
Effective
Arrea of
Diaphragm
in Sq.
Inches
Accessories:
Position Indicator for:
14000501-001: Valve Bonnet Extension Kit (separates
CCT 3858: Corrosion-Resistant Spray
Stroke in Inches
(mm)
5-in. (127 mm) dia: 316028A 7-in. (178 mm) dia: 316035A 8-in. (203 mm) dia: 316037A 13-in. (330 mm) dia, 3/4 in. (19 mm) stroke: 14004722-001 13-in. (330 mm) dia, 1-1/2 in. (38 mm) stroke: 316036A
actuator 2-1/2 in. [64 mm] from valve for high-temperature applications)
Operating Range in
8 to 12 (55 to 85)
2 to 7 (12 to 50)
4 to 11 (30 to 75) or 8 to 13 (55 to 90)
(20, 35, or 70)
psi (kPa)
1
77-3001
2
Dimensions in Inches (Millimeters):
MP953C-F PNEUMA TIC ACTUA T ORS
S16770-2
3
77-3001
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Home and Building Control
Honeywell Inc.
Honeywell Latin American Division
77-3001 Rev. 12-88